Study guide

2.2 Psychrometric Chart Dynamics & Air Properties

Arkansas HVAC/R Contractor License Exam

Track your progress as you read

Finished sections get a check mark.

1 Arkansas HVAC/R Licensing Law, Board Rules & Administration

1.1 Arkansas HVAC/R Board Authority, Statutes & Definitions 1.2 License Classifications & Capacity Limitations 1.3 Registrant Requirements, Apprenticeship & Experience Verification 1.4 License Renewal, Continuing Education & Disciplinary Actions

2 HVAC Thermodynamics, Psychrometrics & Gas Laws

2.1 Principles of Heat Transfer & Thermodynamic Fundamentals 2.2 Psychrometric Chart Dynamics & Air Properties 2.3 Psychrometric Processes & Air Mixture Calculations 2.4 Gas Laws Applied to HVAC/R Systems

3 Heating and Cooling Load Calculations (Manual J & S)

3.1 ACCA Manual J Design Conditions & Thermal Envelopes 3.2 Peak Cooling Load Calculations: Sensible vs. Latent Heat Gain 3.3 Heating Load Calculations & Infiltration Rates 3.4 ACCA Manual S Equipment Selection & Verification

4 Ductwork Design, Sizing & SMACNA Standards (Manual D)

4.1 ACCA Manual D Airflow Fundamentals & External Static Pressure 4.2 Equal Friction & Static Regain Duct Sizing Methods 4.3 Duct Fittings, Equivalent Length & Dynamic Losses 4.4 SMACNA Duct Construction Standards & Joint Sealing

5 Air Distribution, Balancing & Ventilation Codes

5.1 Supply & Return Air Distribution Hardware (Grilles, Registers, Diffusers) 5.2 System Airflow Testing, Adjusting & Balancing (TAB) 5.3 Ventilation Standards: ASHRAE 62.1, 62.2 & 2021 IMC Ventilation Air

6 Mechanical Refrigeration Cycle & Components

6.1 The Vapor-Compression Refrigeration Cycle 6.2 Compressors & Operating Characteristics 6.3 Condensers & Evaporators 6.4 Metering Devices & Refrigerant Flow Controls 6.5 Refrigerant Line Sizing, Oil Return & Field Piping Practices

7 Refrigerants, Oils & EPA Section 608 Regulations

7.1 Refrigerant Chemistry, ASHRAE Standard 34 & A2L Transition 7.2 Lubricating Oils & System Compatibility 7.3 EPA Section 608 Regulatory Mandates & Recovery Standards 7.4 System Evacuation, Dehydration & Leak Detection

8 Air Conditioning & Heat Pump Systems

8.1 Residential & Commercial Split Systems and Package RTUs 8.2 Air-Source Heat Pumps & The Reversing Valve 8.3 Supplemental & Emergency Heating Systems 8.4 Dual-Fuel & Geothermal (Ground-Source) Heat Pump Systems

9 Gas Furnaces, Combustion Air & Venting (IFGC / IMC)

9.1 Gas Furnace Types, AFUE Ratings & Sequence of Operation 9.2 Gas Burners, Ignition Systems & Flame Safeguard Controls 9.3 Combustion Air Requirements (IFGC Chapter 3 / IMC Chapter 7) 9.4 Flue Gas Venting & Category I-IV Venting Systems

10 Boilers, Hydronics & Fuel Gas Piping

10.1 Hydronic Heating Systems, Low-Pressure Boilers & ASME Code 10.2 Hydronic Distribution, Circulator Pumps & Piping Loops 10.3 Fuel Gas Piping Materials, Sizing & Pressure Testing (IFGC Chapter 4) 10.4 Gas Regulators, Manifold Pressure & Gas Meter Sizing 10.5 Condensate Disposal, Piping Support & Mechanical Insulation

11 Electrical Fundamentals, Motors & Control Circuits

11.1 HVAC Electrical Fundamentals, Ohm's Law & Power Calculations 11.2 Single-Phase & Three-Phase Electric Motors in HVAC 11.3 Low-Voltage Control Circuits & Thermostats

12 National Electrical Code (NEC) for HVAC Equipment

12.1 NEC Article 440: Hermetic Refrigerant Motor-Compressors & Branch Circuits 12.2 Equipment Disconnecting Means & Overcurrent Protective Devices (OCPD) 12.3 Motor Branch Circuit Sizing & Conductor Ampacity (NEC Article 430 & Tables)

13 System Maintenance, Troubleshooting & Safety Standards

13.1 Systematic Mechanical & Electrical Troubleshooting 13.2 Airflow & Refrigerant Charge Diagnostics 13.3 Jobsite Safety, OSHA Standards & Personal Protective Equipment

14 Plan Reading, Estimating & HVAC/R Trade Math

14.1 Mechanical Plan Symbols, Schedules & Abbreviations 14.2 Architectural Scales, Dimensions & Quantity Takeoff 14.3 Material, Labor & Bid Estimating 14.4 Applied HVAC/R Trade Math & Unit Conversions

2.2 Psychrometric Chart Dynamics & Air Properties

Key Takeaways Explain This Topic AI

The standard psychrometric chart graphically correlates the thermodynamic properties of moist air at sea-level barometric pressure (29.92 in. Hg / 14.696 psia), where establishing any two independent properties defines all remaining properties.

Dry-bulb temperature is sensible heat measured vertically, wet-bulb temperature reflects evaporative cooling capacity along diagonal lines, and dew point is the saturation temperature where condensation begins read horizontally to the saturation line.

At 100% relative humidity (along the saturation curve), dry-bulb temperature, wet-bulb temperature, and dew-point temperature are precisely identical.

Humidity ratio (W) defines the absolute moisture mass per pound of dry air in grains (7,000 grains = 1 lb of water) and remains constant during pure sensible heating or sensible cooling.

Standard atmospheric air has a nominal density of 0.075 lb/ft³ and a specific volume of 13.33 ft³/lb at 70°F dry bulb, forming the mathematical basis for airflow constant derivations.

Last updated: September 2026

2.2 Psychrometric Chart Dynamics & Air Properties

Note

Psychrometric Foundations : Psychrometrics is the field of engineering science evaluating the thermodynamic and physical properties of gas-and-vapor mixtures, specifically atmospheric air combined with water vapor. Air conditioning is not simply heating or cooling air temperature; it is the simultaneous control of temperature, moisture content, cleanliness, and air distribution. The psychrometric chart translates complex thermodynamic equations into a graphical map that service technicians and system designers use to diagnose performance, calculate coil loads, and troubleshoot comfort complaints.

Atmospheric Air Composition and Standard Air Conditions

Atmospheric air is a binary thermodynamic mixture composed of dry atmospheric air and a variable concentration of water vapor (moisture). Dry air consists of approximately 78.08% nitrogen ( N 2 N_2 N 2 ​ ), 20.95% oxygen ( O 2 O_2 O 2 ​ ), 0.93% argon ( A r Ar A r ), and trace concentrations of carbon dioxide and noble gases, having an apparent average molecular weight of 28.966 lb/lbmol .

Water vapor consists of evaporated water molecules ( H 2 O H_2O H 2 ​ O ) with a molecular weight of 18.015 lb/lbmol . Because water vapor has a lower molecular weight than dry air, moist humid air is actually less dense than dry air at the same temperature and barometric pressure.

Standard Air Constants in HVAC Design

To standardize engineering calculations and equipment capacity ratings across manufacturers (AHRI standards), the HVAC industry defines Standard Air at sea level under the following parameters:

Standard Atmospheric Barometric Pressure : 29.921 inches of mercury (in. Hg) = 14.696 pounds per square inch absolute (psia) = 1 , 013.25 millibars (hPa) 29.921\text{ inches of mercury (in. Hg)} = 14.696\text{ pounds per square inch absolute (psia)} = 1,013.25\text{ millibars (hPa)} 29.921 inches of mercury (in. Hg) = 14.696 pounds per square inch absolute (psia) = 1 , 013.25 millibars (hPa) .

Standard Dry-Bulb Temperature : 70.0 ∘ F 70.0^\circ\text{F} 70. 0 ∘ F ( 21.1 ∘ C 21.1^\circ\text{C} 21. 1 ∘ C ).

Standard Air Density ( ρ \rho ρ ) : 0.075 lb of dry air per cubic foot 0.075\text{ lb of dry air per cubic foot} 0.075 lb of dry air per cubic foot ( 0.075 lb da / ft 3 0.075\text{ lb}_{\text{da}}/\text{ft}^3 0.075 lb da ​ / ft 3 ).

Standard Specific Volume ( v v v ) : The reciprocal of density: v = 1 ρ = 1 0.075 = 13.33 ft 3 per pound of dry air v = \frac{1}{\rho} = \frac{1}{0.075} = \mathbf{13.33\text{ ft}^3\text{ per pound of dry air}} v = ρ 1 ​ = 0.075 1 ​ = 13.33 ft 3 per pound of dry air ( ft 3 / lb da \text{ft}^3/\text{lb}_{\text{da}} ft 3 / lb da ​ ).

Standard Air Specific Heat ( c p c_p c p ​ ) : 0.24 BTU / ( lb ⋅ ∘ F ) 0.24\text{ BTU}/(\text{lb}\cdot^\circ\text{F}) 0.24 BTU / ( lb ⋅ ∘ F ) .

The Seven Fundamental Psychrometric Properties

A psychrometric state point represents a specific sample of moist air and is uniquely determined when any two independent psychrometric properties are known. Once this point is plotted on the chart, the remaining five properties can be read directly. +-----------------------------------------------------------------------------------+

  • | Summary of 7 Psychrometric Properties |
  • +-----------------------------------------------------------------------------------+
  • | 1. Dry-Bulb Temperature (DB) | Sensible temperature read on vertical lines |
  • | 2. Wet-Bulb Temperature (WB) | Evaporative cooling limit read on diagonal lines |
  • | 3. Dew-Point Temperature (DP) | Saturation threshold read horizontally to curve |
  • | 4. Relative Humidity (RH) | Degree of saturation read on curved lines |
  • | 5. Humidity Ratio (W) | Moisture mass (grains/lb) on horizontal axis |
  • | 6. Specific Volume (v) | Space occupied (ft³/lb) on steep diagonal lines |
  • | 7. Enthalpy (h) | Total heat content (BTU/lb) on diagonal scale |
  • +-----------------------------------------------------------------------------------+
  • 1. Dry-Bulb Temperature ( T db T_{\text{db}} T db ​ or DB)

Dry-bulb temperature is the sensible temperature of the air measured by an ordinary, freely exposed thermometer that is shielded from direct radiant heat sources and moisture. On the psychrometric chart, dry-bulb temperature is plotted along the bottom horizontal axis (graduated in degrees Fahrenheit), with lines of constant dry-bulb extending vertically straight upward across the chart.

2. Wet-Bulb Temperature ( T wb T_{\text{wb}} T wb ​ or WB)

Wet-bulb temperature is the lowest equilibrium temperature attainable by evaporating pure liquid water into an airstream at constant pressure. It is physically measured by covering a thermometer bulb with a clean cotton wick saturated with distilled water and passing air across it at high velocity ( 900 feet per minute 900\text{ feet per minute} 900 feet per minute or higher). As moisture evaporates from the wick, it absorbs latent heat of vaporization from the bulb, depressing the thermometer reading.

On the psychrometric chart, lines of constant wet-bulb temperature originate along the curved 100% saturation curve (upper left) and extend diagonally downward to the right , having a slightly steeper slope than constant enthalpy lines.

3. Dew-Point Temperature ( T dp T_{\text{dp}} T dp ​ or DP)

Dew-point temperature is the temperature to which a given sample of moist air must be cooled at constant barometric pressure and moisture content for water vapor to begin condensing into liquid water droplets. When an air sample reaches its dew point, it has attained 100% relative humidity (saturation).

On the psychrometric chart, lines of constant dew point are strictly horizontal lines that extend leftward to intersect the curved 100% saturation line . Because dew point depends strictly on the absolute quantity of moisture in the air, any pure sensible heating or cooling process moves horizontally across the chart at a constant dew-point temperature.

4. Relative Humidity (RH or ϕ \phi ϕ )

Relative humidity is the ratio of the actual partial pressure of water vapor in the air ( p v p_v p v ​ ) to the saturation pressure of water vapor ( p v s p_{vs} p v s ​ ) at the identical dry-bulb temperature and barometric pressure, expressed as a percentage: RH = ( p v p v s ) T , P × 100 % \text{RH} = \left( \frac{p_v}{p_{vs}} \right)_{T,P} \times 100\% RH = ( p v s ​ p v ​ ​ ) T , P ​ × 100%

On the psychrometric chart, lines of constant relative humidity appear as smooth curved lines sweeping upward from the lower left to the upper right. The outermost, uppermost boundary curve represents the 100% Relative Humidity line , also called the Saturation Curve . The lower horizontal boundary represents 0% RH (completely dry air).

5. Humidity Ratio ( W W W or Specific Humidity)

Humidity ratio (also termed absolute humidity or moisture content) is the actual mass of water vapor present per unit mass of bone-dry air. It is expressed in either pounds of moisture per pound of dry air ( lb w / lb da \text{lb}_w/\text{lb}_{\text{da}} lb w ​ / lb da ​ ) or in grains of moisture per pound of dry air ( grains/lb da \text{grains/lb}_{\text{da}} grains/lb da ​ ).

In U.S. Customary HVAC calculations, the grain is the preferred unit of moisture measurement: 1 pound of liquid water = 7 , 000 grains of moisture 1\text{ pound of liquid water} = 7,000\text{ grains of moisture} 1 pound of liquid water = 7 , 000 grains of moisture

On the psychrometric chart, humidity ratio is plotted along the far-right vertical scale , and lines of constant humidity ratio run horizontally from left to right , exactly parallel to constant dew-point lines.

6. Specific Volume ( v v v )

Specific volume is the cubic feet of moist air mixture occupied by exactly one pound of dry air plus its associated moisture content ( ft 3 / lb da \text{ft}^3/\text{lb}_{\text{da}} ft 3 / lb da ​ ). Specific volume is the mathematical reciprocal of air density. On the chart, lines of constant specific volume are widely spaced, steep diagonal lines sloping downward from left to right, typically ranging between 12.5 ft 3 / lb 12.5\text{ ft}^3/\text{lb} 12.5 ft 3 / lb for cold dry air and 14.5 ft 3 / lb 14.5\text{ ft}^3/\text{lb} 14.5 ft 3 / lb for hot humid air.

7. Specific Enthalpy ( h h h )

Enthalpy represents the total thermodynamic heat content per pound of dry air, incorporating both sensible heat of the air-vapor mixture and latent heat of the evaporated water vapor, expressed in BTU per pound of dry air ( BTU/lb da \text{BTU/lb}_{\text{da}} BTU/lb da ​ ). On the chart, enthalpy is read along an external diagonal scale positioned beyond the 100% saturation curve, utilizing an alignment straightedge or following diagonal enthalpy lines that run closely parallel to lines of constant wet-bulb temperature.

The Saturation Relationship Rule

A critical conceptual rule governing psychrometric properties involves the mathematical relationship between Dry Bulb (DB), Wet Bulb (WB), and Dew Point (DP): At 100% Relative Humidity (Saturation Curve): D B = W B = D P At Less Than 100% Relative Humidity (Unsaturated Air): D B > W B > D P \begin{aligned}

  • \text{At 100\% Relative Humidity (Saturation Curve): } & \mathbf{DB = WB = DP} \\
  • \text{At Less Than 100\% Relative Humidity (Unsaturated Air): } & \mathbf{DB > WB > DP}

\end{aligned} At 100% Relative Humidity (Saturation Curve): At Less Than 100% Relative Humidity (Unsaturated Air): ​ DB = WB = DP DB > WB > DP ​

When air is completely saturated with moisture (100% RH), zero net evaporation can occur from a wet-bulb wick; therefore, evaporative cooling ceases and the wet bulb equals the dry bulb. Simultaneously, because the air is at capacity, condensation will initiate upon the slightest drop in temperature, meaning the dew point also equals the dry bulb.

In all unsaturated air samples (e.g., 75°F DB and 50% RH), dry bulb is always the highest value (75°F), wet bulb is intermediate due to evaporative depression (~62.5°F), and dew point is the lowest value (~55.1°F).

Measuring Psychrometric Air Properties: The Sling Psychrometer

Technicians verify indoor and outdoor air properties using a mechanical sling psychrometer or a digital psychrometer probe. +==================[ Swivel Handle ]==================+

  • | |
  • | [============== Dry-Bulb Thermometer ===============]
  • | |
  • | [==== Wet-Bulb Thermometer ====[ Wetted Wick ]=====]
  • +=====================================================+
  • Instrument Mechanics and Operational Procedure

Wick Preparation : The wet-bulb sensor is sleeved in a clean, porous cotton or silk sock wetted with pure distilled or deionized water . Tap water containing dissolved mineral salts must never be used because mineral deposits calcify on the fabric, impeding evaporation and causing falsely elevated wet-bulb readings.

Aspiration : The technician whirls the psychrometer rapidly by its swivel handle at a rate of 2 to 3 revolutions per second , establishing a minimum air velocity of 900 feet per minute (FPM) 900\text{ feet per minute (FPM)} 900 feet per minute (FPM) across the thermometer bulbs to maximize convective evaporative heat transfer.

Equilibrium Reading : After whirling for 60 to 90 seconds, the technician quickly reads the wet-bulb thermometer first (before evaporation slows and the wick warms up), followed immediately by reading the dry-bulb thermometer.

Wet-Bulb Depression : The difference between the dry-bulb reading and the wet-bulb reading is the wet-bulb depression : Depression = T db − T wb \text{Depression} = T_{\text{db}} - T_{\text{wb}} Depression = T db ​ − T wb ​ A large wet-bulb depression indicates very dry air with high evaporative cooling potential (low RH). A small depression indicates humid air. A depression of zero indicates 100% RH.

Master Psychrometric Property Matrix

Property Name Symbol Standard Engineering Units Chart Line Geometry Practical Field / Exam Interpretation

Dry-Bulb Temperature T db T_{\text{db}} T db ​ Degrees Fahrenheit (°F) Vertical lines (straight up from bottom axis) Sensible air temperature sensed by thermostats

Wet-Bulb Temperature T wb T_{\text{wb}} T wb ​ Degrees Fahrenheit (°F) Diagonal lines (sloping down to the right) Evaporative cooling capacity; diagnostic airflow check

Dew-Point Temperature T dp T_{\text{dp}} T dp ​ Degrees Fahrenheit (°F) Horizontal lines (extending left to saturation curve) Temperature where coil condensation or sweating begins

Relative Humidity RH \text{RH} RH / ϕ \phi ϕ Percentage (%) Curved lines (sweeping up to saturation curve) Comfort index; mold hazard threshold (>60% RH)

Humidity Ratio W W W Grains of water / lb dry air (gr/lb) Horizontal lines (extending right to vertical scale) Absolute moisture mass ( 7 , 000 grains = 1 lb 7,000\text{ grains} = 1\text{ lb} 7 , 000 grains = 1 lb water)

Specific Volume v v v Cubic feet / lb dry air ( ft 3 / lb \text{ft}^3/\text{lb} ft 3 / lb ) Steep diagonal lines (sloping down to right) Air density reciprocal; airflow mass conversions

Enthalpy h h h BTU / lb dry air ( BTU/lb da \text{BTU/lb}_{\text{da}} BTU/lb da ​ ) Diagonal lines (read on outer border scale) Total thermal energy content (sensible + latent)

  • Step-by-Step State Point Identification Examples
  • Example 1: Determining Properties for Standard Indoor Comfort Design

Problem : An indoor residential living space in Little Rock, Arkansas, is maintained at standard ACCA Manual J indoor summer design conditions: 75°F Dry Bulb and 50% Relative Humidity . Using a standard psychrometric chart, determine all remaining properties.

Locate State Point : Find 75 ∘ F 75^\circ\text{F} 7 5 ∘ F along the bottom dry-bulb axis and move vertically upward until intersecting the curved 50% Relative Humidity line .

Read Wet-Bulb Temperature : Follow the diagonal wet-bulb line upward and to the left to the saturation curve: T wb = 62.5 ∘ F T_{\text{wb}} = \mathbf{62.5^\circ\text{F}} T wb ​ = 62. 5 ∘ F .

Read Dew-Point Temperature : Move horizontally to the left to intersect the 100% saturation curve: T dp = 55.1 ∘ F T_{\text{dp}} = \mathbf{55.1^\circ\text{F}} T dp ​ = 55. 1 ∘ F .

Read Humidity Ratio ( W W W ) : Move horizontally to the right vertical scale: W = 64.8 grains/lb W = \mathbf{64.8\text{ grains/lb}} W = 64.8 grains/lb (or 0.00926 lb w / lb da 0.00926\text{ lb}_w/\text{lb}_{\text{da}} 0.00926 lb w ​ / lb da ​ ).

Read Specific Enthalpy ( h h h ) : Follow the diagonal enthalpy line to the outer scale: h = 28.1 BTU/lb da h = \mathbf{28.1\text{ BTU/lb}_{\text{da}}} h = 28.1 BTU/lb da ​ .

Read Specific Volume ( v v v ) : Interpolate between the steep volume lines: v = 13.68 ft 3 / lb da v = \mathbf{13.68\text{ ft}^3/\text{lb}_{\text{da}}} v = 13.68 ft 3 / lb da ​ .

Diagnostic Conclusion : Because the room dew point is 55.1°F, any supply ductwork, cold water pipe, or building surface cooler than 55.1°F will sweat and condense moisture.

Example 2: Determining Properties for Arkansas Outdoor Summer Design

Problem : According to ACCA Manual J Table 1A, the 1% summer outdoor design condition for Fort Smith, Arkansas, is 95°F Dry Bulb and 75°F Wet Bulb . Determine the remaining properties.

Locate State Point : Find 95 ∘ F 95^\circ\text{F} 9 5 ∘ F on the bottom axis and follow vertically to its intersection with the diagonal 75 ∘ F 75^\circ\text{F} 7 5 ∘ F wet-bulb line.

Read Relative Humidity : The point falls between the 40% and 50% curves, yielding 40 % RH \mathbf{40\%\text{ RH}} 40% RH .

Read Dew-Point Temperature : Project horizontally to the left saturation curve: T dp = 67.2 ∘ F T_{\text{dp}} = \mathbf{67.2^\circ\text{F}} T dp ​ = 67. 2 ∘ F .

Read Humidity Ratio ( W W W ) : Project horizontally to the right scale: W = 98.5 grains/lb W = \mathbf{98.5\text{ grains/lb}} W = 98.5 grains/lb .

Read Enthalpy ( h h h ) : Follow diagonal enthalpy lines to the outer scale: h = 38.5 BTU/lb da h = \mathbf{38.5\text{ BTU/lb}_{\text{da}}} h = 38.5 BTU/lb da ​ .

Read Specific Volume ( v v v ) : Interpolate between diagonal lines: v = 14.30 ft 3 / lb da v = \mathbf{14.30\text{ ft}^3/\text{lb}_{\text{da}}} v = 14.30 ft 3 / lb da ​ .

Barometric Pressure and Altitude Adjustments

A standard psychrometric chart is calibrated exclusively for sea-level barometric pressure ( 29.92 in. Hg 29.92\text{ in. Hg} 29.92 in. Hg / 14.7 psia 14.7\text{ psia} 14.7 psia ). At higher elevations, such as the Ozark and Ouachita mountain regions of Arkansas (elevations between 1 , 500 and 2 , 800 feet 1,500\text{ and } 2,800\text{ feet} 1 , 500 and 2 , 800 feet above sea level), barometric pressure drops to 28.3 to 27.0 in. Hg 28.3\text{ to } 27.0\text{ in. Hg} 28.3 to 27.0 in. Hg .

Physical Effect of Reduced Atmospheric Pressure : At lower barometric pressures, air molecules are less compressed. Air density decreases, specific volume increases, and water evaporates more readily at lower temperatures.

Chart Deviation : Plotted on a standard sea-level chart, high-elevation air appears to have a lower moisture capacity than it actually possesses. Contractors performing commercial testing, adjusting, and balancing (TAB) or psychrometric verification at elevations above 1,500 feet must utilize altitude-corrected psychrometric charts or apply density correction factors to prevent significant airflow and sensible heat calculation errors.

Loading diagram... Anatomy and Geometry of Psychrometric Chart Property Lines