2.3 Psychrometric Processes & Air Mixture Calculations
Arkansas HVAC/R Contractor License Exam
Track your progress as you read
Finished sections get a check mark.
1 Arkansas HVAC/R Licensing Law, Board Rules & Administration
1.1 Arkansas HVAC/R Board Authority, Statutes & Definitions 1.2 License Classifications & Capacity Limitations 1.3 Registrant Requirements, Apprenticeship & Experience Verification 1.4 License Renewal, Continuing Education & Disciplinary Actions
2 HVAC Thermodynamics, Psychrometrics & Gas Laws
2.1 Principles of Heat Transfer & Thermodynamic Fundamentals 2.2 Psychrometric Chart Dynamics & Air Properties 2.3 Psychrometric Processes & Air Mixture Calculations 2.4 Gas Laws Applied to HVAC/R Systems
3 Heating and Cooling Load Calculations (Manual J & S)
3.1 ACCA Manual J Design Conditions & Thermal Envelopes 3.2 Peak Cooling Load Calculations: Sensible vs. Latent Heat Gain 3.3 Heating Load Calculations & Infiltration Rates 3.4 ACCA Manual S Equipment Selection & Verification
4 Ductwork Design, Sizing & SMACNA Standards (Manual D)
4.1 ACCA Manual D Airflow Fundamentals & External Static Pressure 4.2 Equal Friction & Static Regain Duct Sizing Methods 4.3 Duct Fittings, Equivalent Length & Dynamic Losses 4.4 SMACNA Duct Construction Standards & Joint Sealing
5 Air Distribution, Balancing & Ventilation Codes
5.1 Supply & Return Air Distribution Hardware (Grilles, Registers, Diffusers) 5.2 System Airflow Testing, Adjusting & Balancing (TAB) 5.3 Ventilation Standards: ASHRAE 62.1, 62.2 & 2021 IMC Ventilation Air
6 Mechanical Refrigeration Cycle & Components
6.1 The Vapor-Compression Refrigeration Cycle 6.2 Compressors & Operating Characteristics 6.3 Condensers & Evaporators 6.4 Metering Devices & Refrigerant Flow Controls 6.5 Refrigerant Line Sizing, Oil Return & Field Piping Practices
7 Refrigerants, Oils & EPA Section 608 Regulations
7.1 Refrigerant Chemistry, ASHRAE Standard 34 & A2L Transition 7.2 Lubricating Oils & System Compatibility 7.3 EPA Section 608 Regulatory Mandates & Recovery Standards 7.4 System Evacuation, Dehydration & Leak Detection
8 Air Conditioning & Heat Pump Systems
8.1 Residential & Commercial Split Systems and Package RTUs 8.2 Air-Source Heat Pumps & The Reversing Valve 8.3 Supplemental & Emergency Heating Systems 8.4 Dual-Fuel & Geothermal (Ground-Source) Heat Pump Systems
9 Gas Furnaces, Combustion Air & Venting (IFGC / IMC)
9.1 Gas Furnace Types, AFUE Ratings & Sequence of Operation 9.2 Gas Burners, Ignition Systems & Flame Safeguard Controls 9.3 Combustion Air Requirements (IFGC Chapter 3 / IMC Chapter 7) 9.4 Flue Gas Venting & Category I-IV Venting Systems
10 Boilers, Hydronics & Fuel Gas Piping
10.1 Hydronic Heating Systems, Low-Pressure Boilers & ASME Code 10.2 Hydronic Distribution, Circulator Pumps & Piping Loops 10.3 Fuel Gas Piping Materials, Sizing & Pressure Testing (IFGC Chapter 4) 10.4 Gas Regulators, Manifold Pressure & Gas Meter Sizing 10.5 Condensate Disposal, Piping Support & Mechanical Insulation
11 Electrical Fundamentals, Motors & Control Circuits
11.1 HVAC Electrical Fundamentals, Ohm's Law & Power Calculations 11.2 Single-Phase & Three-Phase Electric Motors in HVAC 11.3 Low-Voltage Control Circuits & Thermostats
12 National Electrical Code (NEC) for HVAC Equipment
12.1 NEC Article 440: Hermetic Refrigerant Motor-Compressors & Branch Circuits 12.2 Equipment Disconnecting Means & Overcurrent Protective Devices (OCPD) 12.3 Motor Branch Circuit Sizing & Conductor Ampacity (NEC Article 430 & Tables)
13 System Maintenance, Troubleshooting & Safety Standards
13.1 Systematic Mechanical & Electrical Troubleshooting 13.2 Airflow & Refrigerant Charge Diagnostics 13.3 Jobsite Safety, OSHA Standards & Personal Protective Equipment
14 Plan Reading, Estimating & HVAC/R Trade Math
14.1 Mechanical Plan Symbols, Schedules & Abbreviations 14.2 Architectural Scales, Dimensions & Quantity Takeoff 14.3 Material, Labor & Bid Estimating 14.4 Applied HVAC/R Trade Math & Unit Conversions
2.3 Psychrometric Processes & Air Mixture Calculations
Key Takeaways Explain This Topic AI
Sensible heating and cooling follow horizontal lines across the psychrometric chart, changing dry-bulb temperature while humidity ratio and dew-point temperature remain constant.
Cooling and dehumidification occurs when air contacts a coil operating below its entering dew point, traversing diagonally downward and to the left toward the Apparatus Dew Point (ADP) on the saturation line.
The fundamental HVAC airflow heat equations are derived from standard air constants (density 0.075 lb/ft³, specific heat 0.24): Q_sensible = 1.08 · CFM · ΔT, Q_latent = 4,840 · CFM · ΔW_lb (or 0.68 · CFM · ΔW_grains), and Q_total = 4.5 · CFM · Δh.
Mixed air conditions represent a mass-weighted linear average: T_mixed = [(CFM_return · T_return) + (CFM_outdoor · T_outdoor)] / CFM_total.
The Coil Bypass Factor (BF) defines the percentage of air passing through a coil without contacting heat transfer surfaces, establishing the leaving air condition relative to the Apparatus Dew Point (ADP).
Last updated: September 2026
2.3 Psychrometric Processes & Air Mixture Calculations
Note
Engineering Applied Psychrometrics : In practical HVAC contracting, psychrometric processes represent the physical changes that air undergoes as it passes through blowers, filters, heating exchangers, cooling coils, humidifiers, and mixing plenums. Thermodynamic calculations establish whether a system meets sensible cooling, latent dehumidification, and outdoor ventilation code mandates. Mastering airflow heat formulas and mixed-air equations is mandatory for passing the Arkansas HVAC/R Contractor License exam.
The Psychrometric Process Compass
Every environmental conditioning process traces a distinct vector path across the psychrometric chart. Understanding the directional movement across the chart enables rapid visual diagnosis of system behavior. Sensible Humidification
- ▲ (Pure Moisture Addition)
- │ [Steam Injection]
- Evaporative Cooling │
- (Adiabatic Saturation) │ Heating & Humidifying
- ▲ │ ▲
- \ │ /
- \ │ /
- \ │ /
- Sensible \ │ / Sensible
- Cooling ◄──────────────────────●──────────────────────► Heating
- (No Dehum) / │ (No Moisture)
- / │ \
- / │ \
- / │ ▼
- ▼ │ Chemical Dehumidification
- Cooling & Dehumidifying │ (Desiccant Drying)
- (Standard AC Coil Process) ▼
- Sensible Dehumidification
- The Eight Primary Psychrometric Processes
Pure Sensible Heating : Path moves horizontally to the right . Dry-bulb temperature increases, enthalpy increases, and relative humidity decreases. Humidity ratio ( W W W ) and dew-point temperature remain strictly constant because no water is added or removed (e.g., electric resistance duct heater or hot gas reheat).
Pure Sensible Cooling : Path moves horizontally to the left . Dry-bulb temperature decreases, enthalpy decreases, and relative humidity increases. Humidity ratio and dew point remain constant because the coil surface temperature is higher than the air's dew point (e.g., chilled water coil operating dry).
Pure Humidification (Steam Injection) : Path moves vertically straight upward . Moisture is added with negligible sensible heat change. Humidity ratio, dew point, relative humidity, and enthalpy increase while dry-bulb temperature remains unchanged.
Pure Dehumidification (Solid Desiccant / Chemical) : Path moves vertically straight downward (or down and slightly right). Water vapor is extracted via desiccant adsorption, lowering humidity ratio and dew point.
Cooling and Dehumidification (Standard AC Cycle) : Path moves diagonally downward and to the left . Air passes across an evaporator coil whose surface temperature is below the entering air's dew point. Dry bulb drops (sensible cooling) and moisture condenses out on fins (latent dehumidification). Both enthalpy and humidity ratio decrease.
Heating and Humidification : Path moves diagonally upward and to the right . Winter air conditioning where cold outdoor air is heated by a furnace or heat pump and moisture is introduced via an evaporative or steam humidifier.
Cooling and Humidification (Evaporative Cooling / Swamp Cooler) : Path moves upward and to the left along a constant wet-bulb / enthalpy line . Water evaporates into the airstream, absorbing its latent heat of vaporization from the sensible heat of the air. Dry-bulb drops while relative humidity and humidity ratio increase, but total enthalpy ( h h h ) remains constant (adiabatic process).
Heating and Dehumidification : Typically occurs in industrial desiccant wheel systems where moisture adsorption releases latent heat of condensation, warming the discharged dry airstream.
Mathematical Derivations of the Standard HVAC Airflow Formulas
On the licensing examination, three fundamental heat transfer equations are applied to calculate equipment capacity and airflow rates: Sensible Heat ( Q s Q_s Q s ) , Latent Heat ( Q l Q_l Q l ) , and Total Heat ( Q t Q_t Q t ) . These equations are derived directly from standard air density ( 0.075 lb/ft 3 0.075\text{ lb/ft}^3 0.075 lb/ft 3 ) and specific heat ( 0.24 BTU / [ lb ⋅ ∘ F ] 0.24\text{ BTU}/[\text{lb}\cdot^\circ\text{F}] 0.24 BTU / [ lb ⋅ ∘ F ] ).
Derivation of the Sensible Heat Formula ( Q s = 1.08 × CFM × Δ T Q_s = 1.08 \times \text{CFM} \times \Delta T Q s = 1.08 × CFM × Δ T )
Sensible heat transfer is defined as: Q s = m ˙ air × c p × Δ T Q_s = \dot{m}_{\text{air}} \times c_p \times \Delta T Q s = m ˙ air × c p × Δ T
To convert volumetric airflow in Cubic Feet per Minute (CFM) to mass airflow rate in pounds of dry air per hour ( m ˙ air \dot{m}_{\text{air}} m ˙ air ): m ˙ air = CFM ( ft 3 min ) × 60 ( min hr ) × 0.075 ( lb da ft 3 ) = 4.5 × CFM ( lb da hr ) \dot{m}_{\text{air}} = \text{CFM} \left(\frac{\text{ft}^3}{\text{min}}\right) \times 60 \left(\frac{\text{min}}{\text{hr}}\right) \times 0.075 \left(\frac{\text{lb}_{\text{da}}}{\text{ft}^3}\right) = 4.5 \times \text{CFM} \left(\frac{\text{lb}_{\text{da}}}{\text{hr}}\right) m ˙ air = CFM ( min ft 3 ) × 60 ( hr min ) × 0.075 ( ft 3 lb da ) = 4.5 × CFM ( hr lb da )
Substituting this mass flow rate into the sensible equation along with the specific heat of standard dry air ( c p = 0.24 BTU / [ lb ⋅ ∘ F ] c_p = 0.24\text{ BTU}/[\text{lb}\cdot^\circ\text{F}] c p = 0.24 BTU / [ lb ⋅ ∘ F ] ): Q s = ( 4.5 × CFM ) × 0.24 × Δ T = ( 4.5 × 0.24 ) × CFM × Δ T Q_s = (4.5 \times \text{CFM}) \times 0.24 \times \Delta T = (4.5 \times 0.24) \times \text{CFM} \times \Delta T Q s = ( 4.5 × CFM ) × 0.24 × Δ T = ( 4.5 × 0.24 ) × CFM × Δ T Q s = 1.08 × CFM × Δ T Q_s = 1.08 \times \text{CFM} \times \Delta T Q s = 1.08 × CFM × Δ T
Where:
- Q s Q_s Q s = Sensible heat capacity (BTU/hr)
- CFM \text{CFM} CFM = Volumetric airflow rate (Cubic Feet per Minute)
Δ T \Delta T Δ T = Temperature difference between entering and leaving air ( T entering − T leaving T_{\text{entering}} - T_{\text{leaving}} T entering − T leaving in °F)
1.08 \mathbf{1.08} 1.08 = Standard air sensible constant ( 60 min/hr × 0.075 lb/ft 3 × 0.24 BTU / [ lb ⋅ ∘ F ] 60\text{ min/hr} \times 0.075\text{ lb/ft}^3 \times 0.24\text{ BTU}/[\text{lb}\cdot^\circ\text{F}] 60 min/hr × 0.075 lb/ft 3 × 0.24 BTU / [ lb ⋅ ∘ F ] )
Derivation of the Total Heat Formula ( Q t = 4.5 × CFM × Δ h Q_t = 4.5 \times \text{CFM} \times \Delta h Q t = 4.5 × CFM × Δ h )
Total heat transferred across a coil accounts for both sensible temperature drop and latent condensation, calculated directly from entering and leaving specific enthalpies ( h 1 h_1 h 1 and h 2 h_2 h 2 ): Q t = m ˙ air × Δ h = ( 4.5 × CFM ) × ( h entering − h leaving ) Q_t = \dot{m}_{\text{air}} \times \Delta h = (4.5 \times \text{CFM}) \times (h_{\text{entering}} - h_{\text{leaving}}) Q t = m ˙ air × Δ h = ( 4.5 × CFM ) × ( h entering − h leaving ) Q t = 4.5 × CFM × Δ h Q_t = 4.5 \times \text{CFM} \times \Delta h Q t = 4.5 × CFM × Δ h
Where:
Q t Q_t Q t = Total cooling capacity (BTU/hr)
Δ h \Delta h Δ h = Enthalpy difference ( h 1 − h 2 h_1 - h_2 h 1 − h 2 in BTU/lb da \text{BTU/lb}_{\text{da}} BTU/lb da )
4.5 \mathbf{4.5} 4.5 = Standard air mass flow constant ( 60 min/hr × 0.075 lb/ft 3 60\text{ min/hr} \times 0.075\text{ lb/ft}^3 60 min/hr × 0.075 lb/ft 3 )
Derivation of the Latent Heat Formula ( Q l = 4 , 840 × CFM × Δ W lb Q_l = 4,840 \times \text{CFM} \times \Delta W_{\text{lb}} Q l = 4 , 840 × CFM × Δ W lb or 0.68 × CFM × Δ W grains 0.68 \times \text{CFM} \times \Delta W_{\text{grains}} 0.68 × CFM × Δ W grains )
Latent heat transfer is the heat removed during moisture condensation: Q l = m ˙ air × h f g × Δ W Q_l = \dot{m}_{\text{air}} \times h_{fg} \times \Delta W Q l = m ˙ air × h f g × Δ W
Where h f g h_{fg} h f g is the latent heat of vaporization of water vapor at coil condensing temperatures (~ 50 ∘ F 50^\circ\text{F} 5 0 ∘ F ), which equals approximately 1 , 075.8 BTU/lb 1,075.8\text{ BTU/lb} 1 , 075.8 BTU/lb .
Using Humidity Ratio in Pounds of Moisture per Pound of Dry Air ( Δ W lb \Delta W_{\text{lb}} Δ W lb ) : Q l = ( 4.5 × CFM ) × 1 , 075.8 × Δ W lb = 4 , 840 × CFM × Δ W lb Q_l = (4.5 \times \text{CFM}) \times 1,075.8 \times \Delta W_{\text{lb}} = \mathbf{4,840 \times \text{CFM} \times \Delta W_{\text{lb}}} Q l = ( 4.5 × CFM ) × 1 , 075.8 × Δ W lb = 4 , 840 × CFM × Δ W lb
Using Humidity Ratio in Grains of Moisture per Pound of Dry Air ( Δ W grains \Delta W_{\text{grains}} Δ W grains ) :
Because 1 lb of water = 7 , 000 grains 1\text{ lb of water} = 7,000\text{ grains} 1 lb of water = 7 , 000 grains : Constant = 4 , 840 7 , 000 = 0.691 ≈ 0.68 \text{Constant} = \frac{4,840}{7,000} = 0.691 \approx \mathbf{0.68} Constant = 7 , 000 4 , 840 = 0.691 ≈ 0.68 Q l = 0.68 × CFM × Δ W grains Q_l = 0.68 \times \text{CFM} \times \Delta W_{\text{grains}} Q l = 0.68 × CFM × Δ W grains
Heat Form Master Formula Operating Units Constant Derivation
Sensible Heat ( Q s Q_s Q s ) Q s = 1.08 × CFM × Δ T Q_s = 1.08 \times \text{CFM} \times \Delta T Q s = 1.08 × CFM × Δ T BTU/hr \text{BTU/hr} BTU/hr , CFM \text{CFM} CFM , ∘ F ^\circ\text{F} ∘ F 60 × 0.075 × 0.24 = 1.08 60 \times 0.075 \times 0.24 = 1.08 60 × 0.075 × 0.24 = 1.08
Total Heat ( Q t Q_t Q t ) Q t = 4.5 × CFM × Δ h Q_t = 4.5 \times \text{CFM} \times \Delta h Q t = 4.5 × CFM × Δ h BTU/hr \text{BTU/hr} BTU/hr , CFM \text{CFM} CFM , BTU/lb \text{BTU/lb} BTU/lb 60 × 0.075 = 4.5 60 \times 0.075 = 4.5 60 × 0.075 = 4.5
Latent Heat ( Q l Q_l Q l ) Q l = 0.68 × CFM × Δ W gr Q_l = 0.68 \times \text{CFM} \times \Delta W_{\text{gr}} Q l = 0.68 × CFM × Δ W gr BTU/hr \text{BTU/hr} BTU/hr , CFM \text{CFM} CFM , grains/lb \text{grains/lb} grains/lb ( 60 × 0.075 × 1 , 075.8 ) / 7 , 000 = 0.68 (60 \times 0.075 \times 1,075.8) / 7,000 = 0.68 ( 60 × 0.075 × 1 , 075.8 ) /7 , 000 = 0.68
Latent Heat ( Q l Q_l Q l ) Q l = 4 , 840 × CFM × Δ W lb Q_l = 4,840 \times \text{CFM} \times \Delta W_{\text{lb}} Q l = 4 , 840 × CFM × Δ W lb BTU/hr \text{BTU/hr} BTU/hr , CFM \text{CFM} CFM , lb w / lb da \text{lb}_w/\text{lb}_{\text{da}} lb w / lb da 60 × 0.075 × 1 , 075.8 = 4 , 840 60 \times 0.075 \times 1,075.8 = 4,840 60 × 0.075 × 1 , 075.8 = 4 , 840
Air Mixture Mechanics: Mixed Air Equations
In commercial HVAC systems, fresh outdoor ventilation air is introduced through an economizer or outside air damper and blended with recirculated return air in the mixing plenum before entering the cooling or heating coil. The resulting mixture condition is a direct mass-weighted average of the two converging airstreams. Outdoor Air (OA): CFM_oa, T_oa, W_oa, h_oa
- ───────────────►\
- \──────► Mixed Air (MA): CFM_total, T_ma, W_ma, h_ma ───► [Cooling Coil]
- /
- ───────────────►/
- Return Air (RA): CFM_ra, T_ra, W_ra, h_ra
Mixed Air Temperature Formula T ma = ( CFM ra × T ra ) + ( CFM oa × T oa ) CFM total T_{\text{ma}} = \frac{(\text{CFM}_{\text{ra}} \times T_{\text{ra}}) + (\text{CFM}_{\text{oa}} \times T_{\text{oa}})}{\text{CFM}_{\text{total}}} T ma = CFM total ( CFM ra × T ra ) + ( CFM oa × T oa )
Where:
CFM total = CFM ra + CFM oa \text{CFM}_{\text{total}} = \text{CFM}_{\text{ra}} + \text{CFM}_{\text{oa}} CFM total = CFM ra + CFM oa
- T ma T_{\text{ma}} T ma = Mixed air dry-bulb temperature (°F)
- T ra T_{\text{ra}} T ra = Return air dry-bulb temperature (°F)
- T oa T_{\text{oa}} T oa = Outdoor air dry-bulb temperature (°F)
Alternatively, expressing outdoor air as a percentage fraction ( X oa = CFM oa / CFM total X_{\text{oa}} = \text{CFM}_{\text{oa}} / \text{CFM}_{\text{total}} X oa = CFM oa / CFM total ): T ma = T ra + [ X oa × ( T oa − T ra ) ] T_{\text{ma}} = T_{\text{ra}} + [X_{\text{oa}} \times (T_{\text{oa}} - T_{\text{ra}})] T ma = T ra + [ X oa × ( T oa − T ra )]
Mixed Air Humidity Ratio and Enthalpy
Identical mass-weighted equations govern humidity ratio and enthalpy: W ma = ( CFM ra × W ra ) + ( CFM oa × W oa ) CFM total and h ma = ( CFM ra × h ra ) + ( CFM oa × h oa ) CFM total W_{\text{ma}} = \frac{(\text{CFM}_{\text{ra}} \times W_{\text{ra}}) + (\text{CFM}_{\text{oa}} \times W_{\text{oa}})}{\text{CFM}_{\text{total}}} \quad \text{and} \quad h_{\text{ma}} = \frac{(\text{CFM}_{\text{ra}} \times h_{\text{ra}}) + (\text{CFM}_{\text{oa}} \times h_{\text{oa}})}{\text{CFM}_{\text{total}}} W ma = CFM total ( CFM ra × W ra ) + ( CFM oa × W oa ) and h ma = CFM total ( CFM ra × h ra ) + ( CFM oa × h oa )
Calculating Outdoor Air Percentage from Temperature Readings
A common field diagnostic and exam requirement is calculating the actual percentage of outside air entering an air handler when CFM values are unknown: % OA = T ma − T ra T oa − T ra × 100 % \%\text{OA} = \frac{T_{\text{ma}} - T_{\text{ra}}}{T_{\text{oa}} - T_{\text{ra}}} \times 100\% % OA = T oa − T ra T ma − T ra × 100%
Coil Apparatus Dew Point (ADP) and Bypass Factor (BF)
When moist air passes through a finned cooling coil, not all air molecules make direct physical contact with the cold copper tubes or aluminum fins. A portion of the air passes through the center of the fin openings untouched.
Apparatus Dew Point (ADP) : The theoretical effective surface temperature of the cooling coil. On the psychrometric chart, if the process line connecting entering air to leaving air is extended straight to the 100% saturation curve, the point of intersection is the Apparatus Dew Point (ADP) .
Coil Bypass Factor (BF) : The fraction of total entering air that completely bypasses the coil surface without conditioning. Residential coils typically have a bypass factor of 0.10 to 0.20 (10% to 20% bypass); commercial coils with 6 to 8 rows of fins achieve bypass factors of 0.03 to 0.08 (3% to 8% bypass).
Contact Factor (CF) : The fraction of air that makes direct contact with the coil: CF = 1 − BF \text{CF} = 1 - \text{BF} CF = 1 − BF .
The leaving air dry-bulb temperature is calculated from the ADP and Bypass Factor: T leaving = T adp + [ BF × ( T entering − T adp ) ] T_{\text{leaving}} = T_{\text{adp}} + [\text{BF} \times (T_{\text{entering}} - T_{\text{adp}})] T leaving = T adp + [ BF × ( T entering − T adp )]
- Step-by-Step Worked Engineering Calculations
- Calculation 1: Complete Air Handler Capacity & SHR Determination
Problem : A commercial packaged rooftop unit delivers 4 , 000 CFM 4,000\text{ CFM} 4 , 000 CFM of supply air. Air enters the cooling coil at 80 ∘ F DB 80^\circ\text{F DB} 8 0 ∘ F DB and 67 ∘ F WB 67^\circ\text{F WB} 6 7 ∘ F WB ( h 1 = 31.62 BTU/lb h_1 = 31.62\text{ BTU/lb} h 1 = 31.62 BTU/lb , W 1 = 78 gr/lb W_1 = 78\text{ gr/lb} W 1 = 78 gr/lb ). Air leaves the cooling coil at 55 ∘ F DB 55^\circ\text{F DB} 5 5 ∘ F DB and 54 ∘ F WB 54^\circ\text{F WB} 5 4 ∘ F WB ( h 2 = 22.60 BTU/lb h_2 = 22.60\text{ BTU/lb} h 2 = 22.60 BTU/lb , W 2 = 60 gr/lb W_2 = 60\text{ gr/lb} W 2 = 60 gr/lb ). Calculate: (a) Sensible cooling capacity ( Q s Q_s Q s ), (b) Latent cooling capacity ( Q l Q_l Q l ), (c) Total cooling capacity ( Q t Q_t Q t ), (d) System tonnage, and (e) Sensible Heat Ratio (SHR).
Step 1: Calculate Sensible Heat ( Q s = 1.08 × CFM × Δ T Q_s = 1.08 \times \text{CFM} \times \Delta T Q s = 1.08 × CFM × Δ T ) Δ T = 80 ∘ F − 55 ∘ F = 25 ∘ F \Delta T = 80^\circ\text{F} - 55^\circ\text{F} = 25^\circ\text{F} Δ T = 8 0 ∘ F − 5 5 ∘ F = 2 5 ∘ F Q s = 1.08 × 4 , 000 CFM × 25 ∘ F = 108 , 000 BTU/hr Q_s = 1.08 \times 4,000\text{ CFM} \times 25^\circ\text{F} = 108,000\text{ BTU/hr} Q s = 1.08 × 4 , 000 CFM × 2 5 ∘ F = 108 , 000 BTU/hr
Step 2: Calculate Latent Heat ( Q l = 0.68 × CFM × Δ W gr Q_l = 0.68 \times \text{CFM} \times \Delta W_{\text{gr}} Q l = 0.68 × CFM × Δ W gr ) Δ W = 78 gr/lb − 60 gr/lb = 18 gr/lb \Delta W = 78\text{ gr/lb} - 60\text{ gr/lb} = 18\text{ gr/lb} Δ W = 78 gr/lb − 60 gr/lb = 18 gr/lb Q l = 0.68 × 4 , 000 CFM × 18 gr/lb = 48 , 960 BTU/hr Q_l = 0.68 \times 4,000\text{ CFM} \times 18\text{ gr/lb} = 48,960\text{ BTU/hr} Q l = 0.68 × 4 , 000 CFM × 18 gr/lb = 48 , 960 BTU/hr
Step 3: Calculate Total Heat ( Q t = 4.5 × CFM × Δ h Q_t = 4.5 \times \text{CFM} \times \Delta h Q t = 4.5 × CFM × Δ h ) Δ h = 31.62 − 22.60 = 9.02 BTU/lb \Delta h = 31.62 - 22.60 = 9.02\text{ BTU/lb} Δ h = 31.62 − 22.60 = 9.02 BTU/lb Q t = 4.5 × 4 , 000 CFM × 9.02 BTU/lb = 162 , 360 BTU/hr Q_t = 4.5 \times 4,000\text{ CFM} \times 9.02\text{ BTU/lb} = 162,360\text{ BTU/hr} Q t = 4.5 × 4 , 000 CFM × 9.02 BTU/lb = 162 , 360 BTU/hr
(Cross-check: Q s + Q l = 108 , 000 + 48 , 960 = 156 , 960 BTU/hr Q_s + Q_l = 108,000 + 48,960 = 156,960\text{ BTU/hr} Q s + Q l = 108 , 000 + 48 , 960 = 156 , 960 BTU/hr , aligning within 3% due to standard rounding of the 0.68 latent constant.)
Step 4: Calculate System Tonnage Tons = 162 , 360 BTU/hr 12 , 000 BTU/ton = 13.53 Tons \text{Tons} = \frac{162,360\text{ BTU/hr}}{12,000\text{ BTU/ton}} = \mathbf{13.53\text{ Tons}} Tons = 12 , 000 BTU/ton 162 , 360 BTU/hr = 13.53 Tons
Step 5: Calculate Sensible Heat Ratio (SHR) SHR = Q s Q t = 108 , 000 162 , 360 = 0.665 \text{SHR} = \frac{Q_s}{Q_t} = \frac{108,000}{162,360} = \mathbf{0.665} SHR = Q t Q s = 162 , 360 108 , 000 = 0.665
Result : The unit produces 108,000 BTU/hr sensible , 48,960 BTU/hr latent , 13.5 tons total capacity , and operates at an SHR of 0.67 , providing strong latent dehumidification ideal for humid Arkansas weather.
Calculation 2: Commercial Economizer Mixed Air Temperature
Problem : A commercial air handling unit in Little Rock draws 3 , 000 CFM 3,000\text{ CFM} 3 , 000 CFM of return air at 74 ∘ F DB 74^\circ\text{F DB} 7 4 ∘ F DB and blends it with 1 , 000 CFM 1,000\text{ CFM} 1 , 000 CFM of hot outdoor ventilation air at 94 ∘ F DB 94^\circ\text{F DB} 9 4 ∘ F DB . Calculate the resulting mixed air dry-bulb temperature entering the filter rack.
Step 1: Calculate total system airflow CFM total = 3 , 000 + 1 , 000 = 4 , 000 CFM \text{CFM}_{\text{total}} = 3,000 + 1,000 = 4,000\text{ CFM} CFM total = 3 , 000 + 1 , 000 = 4 , 000 CFM
Step 2: Apply the mixed air temperature formula T ma = ( 3 , 000 CFM × 74 ∘ F ) + ( 1 , 000 CFM × 94 ∘ F ) 4 , 000 CFM T_{\text{ma}} = \frac{(3,000\text{ CFM} \times 74^\circ\text{F}) + (1,000\text{ CFM} \times 94^\circ\text{F})}{4,000\text{ CFM}} T ma = 4 , 000 CFM ( 3 , 000 CFM × 7 4 ∘ F ) + ( 1 , 000 CFM × 9 4 ∘ F ) T ma = 222 , 000 + 94 , 000 4 , 000 = 316 , 000 4 , 000 = 79.0 ∘ F T_{\text{ma}} = \frac{222,000 + 94,000}{4,000} = \frac{316,000}{4,000} = \mathbf{79.0^\circ\text{F}} T ma = 4 , 000 222 , 000 + 94 , 000 = 4 , 000 316 , 000 = 79. 0 ∘ F
Result : The air mixture enters the cooling coil at 79.0°F DB .
Calculation 3: Verifying Outside Air Ventilation Percentage
Problem : An HVAC contractor tests an air handling unit during a ventilation compliance audit. The field technician measures the following temperatures: Return air = 72°F, Outdoor air = 32°F (winter conditions), and Mixed air plenum = 62°F. What percentage of the total airflow is outdoor ventilation air? % OA = T ma − T ra T oa − T ra × 100 % = 62 − 72 32 − 72 × 100 % = − 10 − 40 × 100 % = 25 % \%\text{OA} = \frac{T_{\text{ma}} - T_{\text{ra}}}{T_{\text{oa}} - T_{\text{ra}}} \times 100\% = \frac{62 - 72}{32 - 72} \times 100\% = \frac{-10}{-40} \times 100\% = \mathbf{25\%} % OA = T oa − T ra T ma − T ra × 100% = 32 − 72 62 − 72 × 100% = − 40 − 10 × 100% = 25%
Result : Outdoor ventilation air constitutes 25% of the total supply airflow.
Exam Traps & Common Field Pitfalls
Warning
Exam Trap 1: Misapplying Wet-Bulb in Mixed Air Equations : Never calculate mixed air wet-bulb temperature by taking a linear weighted average of entering wet-bulb temperatures! Wet-bulb lines are non-linear. To find mixed wet-bulb accurately, calculate mixed enthalpy ( h ma h_{\text{ma}} h ma ) and mixed humidity ratio ( W ma W_{\text{ma}} W ma ), plot that intersection point on the chart, and read the wet bulb.
Exam Trap 2: Constant Inconsistency (0.68 vs. 4,840) : Do not plug grains into the 4,840 latent formula or pounds into the 0.68 formula! Using 70 grains in 4 , 840 × CFM × Δ W 4,840 \times \text{CFM} \times \Delta W 4 , 840 × CFM × Δ W creates a massive mathematical error ( 7 , 000 × 7,000\times 7 , 000 × too large). Remember: 0.68 pairs with grains ; 4,840 pairs with pounds .
Exam Trap 3: Thermal Stratification in Mixed Plenums : When cold winter outdoor air enters a mixing box, it tends to sink to the bottom while warm return air rides along the top without mixing. If this stratified cold air hits a hydronic hot water coil, it can freeze the lower coil tubes and trip the low-limit freezestat, even if the "average" mixed air temperature is 50°F. Modern commercial designs require mechanical air blenders or baffles.