6.2 Compressors & Operating Characteristics
Arkansas HVAC/R Contractor License Exam
Track your progress as you read
Finished sections get a check mark.
1 Arkansas HVAC/R Licensing Law, Board Rules & Administration
1.1 Arkansas HVAC/R Board Authority, Statutes & Definitions 1.2 License Classifications & Capacity Limitations 1.3 Registrant Requirements, Apprenticeship & Experience Verification 1.4 License Renewal, Continuing Education & Disciplinary Actions
2 HVAC Thermodynamics, Psychrometrics & Gas Laws
2.1 Principles of Heat Transfer & Thermodynamic Fundamentals 2.2 Psychrometric Chart Dynamics & Air Properties 2.3 Psychrometric Processes & Air Mixture Calculations 2.4 Gas Laws Applied to HVAC/R Systems
3 Heating and Cooling Load Calculations (Manual J & S)
3.1 ACCA Manual J Design Conditions & Thermal Envelopes 3.2 Peak Cooling Load Calculations: Sensible vs. Latent Heat Gain 3.3 Heating Load Calculations & Infiltration Rates 3.4 ACCA Manual S Equipment Selection & Verification
4 Ductwork Design, Sizing & SMACNA Standards (Manual D)
4.1 ACCA Manual D Airflow Fundamentals & External Static Pressure 4.2 Equal Friction & Static Regain Duct Sizing Methods 4.3 Duct Fittings, Equivalent Length & Dynamic Losses 4.4 SMACNA Duct Construction Standards & Joint Sealing
5 Air Distribution, Balancing & Ventilation Codes
5.1 Supply & Return Air Distribution Hardware (Grilles, Registers, Diffusers) 5.2 System Airflow Testing, Adjusting & Balancing (TAB) 5.3 Ventilation Standards: ASHRAE 62.1, 62.2 & 2021 IMC Ventilation Air
6 Mechanical Refrigeration Cycle & Components
6.1 The Vapor-Compression Refrigeration Cycle 6.2 Compressors & Operating Characteristics 6.3 Condensers & Evaporators 6.4 Metering Devices & Refrigerant Flow Controls 6.5 Refrigerant Line Sizing, Oil Return & Field Piping Practices
7 Refrigerants, Oils & EPA Section 608 Regulations
7.1 Refrigerant Chemistry, ASHRAE Standard 34 & A2L Transition 7.2 Lubricating Oils & System Compatibility 7.3 EPA Section 608 Regulatory Mandates & Recovery Standards 7.4 System Evacuation, Dehydration & Leak Detection
8 Air Conditioning & Heat Pump Systems
8.1 Residential & Commercial Split Systems and Package RTUs 8.2 Air-Source Heat Pumps & The Reversing Valve 8.3 Supplemental & Emergency Heating Systems 8.4 Dual-Fuel & Geothermal (Ground-Source) Heat Pump Systems
9 Gas Furnaces, Combustion Air & Venting (IFGC / IMC)
9.1 Gas Furnace Types, AFUE Ratings & Sequence of Operation 9.2 Gas Burners, Ignition Systems & Flame Safeguard Controls 9.3 Combustion Air Requirements (IFGC Chapter 3 / IMC Chapter 7) 9.4 Flue Gas Venting & Category I-IV Venting Systems
10 Boilers, Hydronics & Fuel Gas Piping
10.1 Hydronic Heating Systems, Low-Pressure Boilers & ASME Code 10.2 Hydronic Distribution, Circulator Pumps & Piping Loops 10.3 Fuel Gas Piping Materials, Sizing & Pressure Testing (IFGC Chapter 4) 10.4 Gas Regulators, Manifold Pressure & Gas Meter Sizing 10.5 Condensate Disposal, Piping Support & Mechanical Insulation
11 Electrical Fundamentals, Motors & Control Circuits
11.1 HVAC Electrical Fundamentals, Ohm's Law & Power Calculations 11.2 Single-Phase & Three-Phase Electric Motors in HVAC 11.3 Low-Voltage Control Circuits & Thermostats
12 National Electrical Code (NEC) for HVAC Equipment
12.1 NEC Article 440: Hermetic Refrigerant Motor-Compressors & Branch Circuits 12.2 Equipment Disconnecting Means & Overcurrent Protective Devices (OCPD) 12.3 Motor Branch Circuit Sizing & Conductor Ampacity (NEC Article 430 & Tables)
13 System Maintenance, Troubleshooting & Safety Standards
13.1 Systematic Mechanical & Electrical Troubleshooting 13.2 Airflow & Refrigerant Charge Diagnostics 13.3 Jobsite Safety, OSHA Standards & Personal Protective Equipment
14 Plan Reading, Estimating & HVAC/R Trade Math
14.1 Mechanical Plan Symbols, Schedules & Abbreviations 14.2 Architectural Scales, Dimensions & Quantity Takeoff 14.3 Material, Labor & Bid Estimating 14.4 Applied HVAC/R Trade Math & Unit Conversions
6.2 Compressors & Operating Characteristics
Key Takeaways Explain This Topic AI
The compressor is the mechanical pump of the refrigeration circuit, creating the pressure differential between the high side and low side that establishes the saturation temperatures necessary for heat absorption and rejection.
The five fundamental compressor types used in HVAC/R are reciprocating, rotary, scroll, screw, and centrifugal, categorized broadly into positive displacement and dynamic aerodynamic designs.
Compression ratio (CR) must be calculated strictly using absolute pressures: CR = (P_discharge, psig + 14.7) / (P_suction, psig + 14.7); operating above 10:1 severely degrades volumetric efficiency and elevates discharge temperatures above the safe 275°F thermal limit of compressor lubricants.
Scroll compressors feature axial and radial compliance mechanisms that seal compression pockets against gas leakage while flexing outward or downward to tolerate incompressible liquid droplets without mechanical damage.
Crankcase heaters prevent off-cycle refrigerant migration and subsequent bearing failure by keeping the compressor oil 10°F to 20°F warmer than the surrounding system, preventing liquid refrigerant from dissolving into the oil sump during off cycles.
Last updated: September 2026
6.2 Compressors & Operating Characteristics
Note
The Mechanical Vapor Pump : Often referred to as the "heart" of the refrigeration system, the compressor performs two indispensable thermodynamic functions: first, it lowers the pressure in the evaporator to allow liquid refrigerant to boil at low temperatures; second, it raises the pressure and temperature of the vapor so that it can reject heat into ambient outdoor air or water. Compressors handle vapor exclusively. Liquid refrigerant is practically incompressible; allowing liquid into the compression chamber leads to hydraulic lock, broken valves, blown scroll wraps, and bent connecting rods.
The Five Primary Compressor Classifications
Refrigeration compressors are categorized by their operating principle into two broad families: positive displacement compressors (which trap a fixed volume of vapor and mechanically reduce its volume) and dynamic displacement compressors (which impart high kinetic velocity to vapor using high-speed spinning impellers and convert it into static pressure). +-------------------------------------------------------------------------+
- | REFRIGERATION COMPRESSOR TAXONOMY |
- +-------------------------------------------------------------------------+
- | POSITIVE DISPLACEMENT (Traps volume & physically reduces pocket size) |
- | * Reciprocating --> Pistons, connecting rods, reed valves |
- | * Rotary --> Rolling piston or sliding vane, stationary casing|
- | * Scroll --> Stationary involute scroll & orbiting scroll wrap|
- | * Screw (Helical)--> Intermeshing male and female helical rotors |
- +-------------------------------------------------------------------------+
- | DYNAMIC / AERODYNAMIC (Imparts kinetic velocity -> converts to pressure)|
- | * Centrifugal --> High-speed spinning impellers, diffuser volute |
- +-------------------------------------------------------------------------+
- 1. Reciprocating Compressors
Operating Principle : Utilizes one or more pistons driven by a crankshaft and connecting rods reciprocating inside precision-honed cast iron cylinders. Directional flow is controlled by flexible spring steel reed valves (suction and discharge).
Clearance Volume & Volumetric Efficiency : At the top of the piston stroke (top dead center, TDC), a small clearance volume remains between the piston crown and the cylinder valve plate. High-pressure vapor trapped in this clearance space re-expands as the piston descends, preventing the suction valve from opening until cylinder pressure falls below suction line pressure. This re-expansion limits volumetric efficiency ( V E VE V E ) : V E = Actual Volume Drawn Theoretical Cylinder Displacement × 100 VE = \frac{\text{Actual Volume Drawn}}{\text{Theoretical Cylinder Displacement}} \times 100 V E = Theoretical Cylinder Displacement Actual Volume Drawn × 100
Applications : Widely used in commercial refrigeration, transport cooling, and legacy split systems; highly durable and rebuildable in semi-hermetic configurations.
2. Rotary Compressors (Rolling Piston & Sliding Vane)
Operating Principle : Employs an eccentric roller or slotted rotor spinning within a stationary cylindrical housing. A spring-loaded sliding vane rides continuously against the eccentric roller surface, separating the suction chamber from the compression chamber. As the shaft rotates, the crescent-shaped compression volume shrinks continuously until the discharge valve opens.
Characteristics : Compact footprint, low noise, minimal clearance volume, and very high volumetric efficiency at low pressure ratios. Widely utilized in ductless mini-split systems, packaged terminal air conditioners (PTAC), window units, and domestic refrigerators up to approximately 3 to 5 tons.
3. Scroll Compressors
Operating Principle : Consists of two interleaving, involute spiral scrolls: a stationary (fixed) scroll and an orbiting scroll . The orbiting scroll is driven by an eccentric crankshaft, describing an orbit without rotating on its own axis. As it orbits, crescent-shaped pockets of vapor are formed at the outer perimeter and driven continuously toward the center discharge port, shrinking in volume and increasing in pressure.
Zero Clearance Volume : Because the compression pockets move continuously into the discharge port, there is virtually zero re-expansion volume. Scroll compressors achieve 100% theoretical volumetric efficiency at design conditions.
Advantages : 60% fewer moving parts than reciprocating compressors, smooth continuous torque (eliminating pressure pulsation), low vibration, high SEER2 efficiency, and exceptional tolerance to transient liquid mist.
4. Screw Compressors (Helical Rotary)
Operating Principle : Positive displacement machine utilizing two intermeshing helical rotors (a male rotor with lobes and a female rotor with matching flutes) enclosed in a precision-machined casing. Vapor enters the suction port at one end, fills the helical cavities, and is squeezed axially along the length of the rotors toward the discharge port at the opposite end.
Applications & Capacity : Dominates medium-to-large water chillers and commercial/industrial refrigeration systems from 50 to 500+ tons . Exceptionally robust, high reliability, capable of continuous 24/7 operation, and handles high compression ratios without valve fatigue.
5. Centrifugal Compressors
Operating Principle : Dynamic displacement machine with no pistons, valves, or intermeshing scrolls. One or more high-speed impellers (spinning at 3,000 to 30,000+ RPM) draw vapor into the impeller "eye" and accelerate it radially outward using centrifugal force. The high-velocity vapor enters an expanding stationary casing (the diffuser volute ), where kinetic energy converts into static pressure (Bernoulli's principle).
Applications : Applied almost exclusively in large central chilled water plants ranging from 200 to 3,000+ tons . Utilizes low-to-medium pressure refrigerants (e.g., R-1233zd, R-513A, R-134a). Features magnetic levitation (oil-free) bearings in cutting-edge high-efficiency models.
Compression Ratio: Calculation, Significance, and Limits
The Compression Ratio (CR) is the single most critical operating parameter governing compressor volumetric efficiency, motor electrical current, and discharge temperature.
Mathematical Formulation
Compression ratio is defined strictly as the ratio of absolute discharge pressure to absolute suction pressure : CR = P discharge, absolute P suction, absolute = P discharge, psig + 14.7 P suction, psig + 14.7 \text{CR} = \frac{P_{\text{discharge, absolute}}}{P_{\text{suction, absolute}}} = \frac{P_{\text{discharge, psig}} + 14.7}{P_{\text{suction, psig}} + 14.7} CR = P suction, absolute P discharge, absolute = P suction, psig + 14.7 P discharge, psig + 14.7
Warning
The Absolute Pressure Exam Trap : Never calculate the compression ratio using gauge pressures (psig). Dividing psig by psig yields an erroneous, meaningless number that will fail exam calculation questions. You must always add atmospheric pressure ( 14.696 psi ≈ 14.7 psi 14.696\text{ psi} \approx 14.7\text{ psi} 14.696 psi ≈ 14.7 psi ) to both gauge readings before dividing.
Operational Impact of High Compression Ratios
Volumetric Efficiency Collapse : As CR rises, the re-expansion of clearance gas in reciprocating compressors expands further down the stroke, drastically reducing the volume of fresh suction vapor drawn in. At high ratios, net capacity drops precipitously.
Elevated Discharge Temperatures & Lubricant Breakdown : High compression ratios generate excessive discharge gas temperatures. Standard field rule of thumb mandates that the discharge line temperature (measured 6 inches from the compressor body) must never exceed 225°F . Because cylinder and discharge port internal temperatures are 50°F to 75°F hotter than the exterior pipe, exterior temperatures exceeding 225°F indicate internal temperatures exceeding 275°F to 300°F —the point where polyolester (POE) and mineral oils chemically decompose, carbonizing into abrasive sludge and acid.
Target Operating Thresholds : Comfort air conditioning typically operates at compression ratios between 2.5:1 and 4.0:1 . Commercial refrigeration systems operate at 5:1 to 8:1 . When low-temperature applications require a CR exceeding 10:1 to 12:1 , single-stage compression becomes thermodynamically unfeasible, requiring compound / two-stage compression with interstage cooling or liquid injection.
Mechanical Compliance Mechanisms in Scroll Compressors
Traditional reciprocating compressors suffer catastrophic mechanical failure ("slugging") if incompressible liquid refrigerant or oil droplets enter the cylinder. Modern scroll compressors avoid this through patented mechanical compliance mechanisms : AXIAL COMPLIANCE (Vertical Relief)
- [ Fixed Scroll Housing ]
- ^^
- || Floating Seal allows wrap to lift
- vv vertically if liquid pressure spikes
- [ Orbiting Scroll Flank ]
- <===========>
- RADIAL COMPLIANCE (Horizontal Swing)
- Swing-link drive allows orbiting wrap to separate
- horizontally from fixed wrap to pass debris/droplets
Radial Compliance : The orbiting scroll is coupled to the motor drive shaft via an eccentric swing-link bushing. Centrifugal force and drive torque bias the flank of the orbiting scroll against the flank of the fixed scroll with just enough contact force to establish an airtight gas seal. If an incompressible slug of liquid enters the pocket, the hydraulic force overcomes the centrifugal bias, allowing the orbiting wrap to swing momentarily away radially, venting the liquid into the center without fracturing the metal wraps.
Axial Compliance : An intermediate gas cavity or floating annular seal beneath the scroll base uses discharge or intermediate pressure to hold the scroll tips lightly against the opposing scroll plate vertically. If excessive liquid enters, the scrolls are forced axially apart against the gas spring, relieving pressure instantly.
Compressor Capacity Modulation Technologies
Operating compressors exclusively at fixed 100% capacity creates severe short-cycling during partial load conditions, degrading dehumidification and wasting energy. Modern systems employ four primary capacity modulation technologies:
Modulation Technology Mechanism of Action Common Systems Efficiency Characteristics
Cylinder Unloading Mechanical lifters hold suction valves open, or solenoids block suction ports on individual cylinders. Semi-hermetic reciprocating compressors (commercial RTUs, supermarkets). Steps capacity down in discrete increments (e.g., 100% -> 66% -> 33%); modest power savings.
Two-Stage Scroll Internal bypass port opens via DC solenoid, venting intermediate compression pockets back to suction to bypass ~33% displacement. Residential two-stage heat pumps and high-efficiency split AC (e.g., Copeland UltraTech). Operates at two discrete stages: Stage 1 (~67% capacity) and Stage 2 (100% capacity).
Inverter Variable Speed (VFD) Inverter rectifies AC to DC, then synthesizes variable frequency/voltage AC (15 Hz to 120+ Hz) to power brushless DC (BLDC/ECM) motors. Ductless mini-splits, VRV/VRF commercial systems, high-SEER2 inverter heat pumps. Continuous, stepless modulation from 15% to 120% capacity; extraordinary partial-load efficiency.
Slide Valve Modulation Hydraulically actuated slide valve moves axially along the rotor casing to uncover a portion of the rotor flutes back to suction. Large helical screw chillers and industrial refrigeration racks. Continuous, stepless capacity modulation from 10% to 100% displacement without motor speed changes.
Crankcase Lubrication, Refrigerant Migration & Protection
Refrigeration oil (mineral, alkylbenzene, or polyolester - POE) circulates throughout the system to lubricate compressor bearings, shaft seals, and cylinder walls. Under normal conditions, oil and refrigerant are fully miscible (they dissolve into each other).
The Physics of Off-Cycle Refrigerant Migration
In accordance with Henry's Law of gas solubility , the solubility of refrigerant vapor in lubricating oil increases dramatically as oil temperature decreases. When a system cycles off, the compressor crankcase cools down. If the outdoor ambient drops, the cold oil acts as a powerful chemical sponge, drawing refrigerant vapor out of the warmer indoor evaporator and condensing it directly into the compressor oil sump.
The Destructive "Foaming" Phenomenon
If a compressor starts while its oil sump is saturated with liquid refrigerant:
The suction stroke causes crankcase pressure to drop violently.
The sudden drop in pressure causes the liquid refrigerant dissolved in the oil to flash instantaneously into a violent, boiling foam.
The foam fills the entire crankcase cavity, stripping oil away from the oil pump pick-up tube.
The oil pump cavitates, pumping refrigerant foam instead of a solid hydraulic wedge of liquid lubricant to the journal bearings.
Massive quantities of oil are forced past the piston rings or scrolls into the discharge line, starving the crankcase and causing bearing seizure within seconds. OFF-CYCLE MIGRATION: AT COMPRESSOR STARTUP:
- +---------------------------+ +---------------------------+
- | Cold Compressor Sump | | Pressure Plunges Rapidly |
- | Oil absorbs refrigerant |-->| Refrigerant flashes! |
- | Liquid settles at bottom | | Violent foaming erupts |
- | Viscosity plummets | | Bearing oil film destroyed|
- +---------------------------+ +---------------------------+
- Crankcase Heaters (CCH)
A crankcase heater is an electric resistance element (belly-band style clamped around the compressor base, or insertion style seated directly inside an oil well) designed to maintain the oil sump temperature 10°F to 20°F higher than the saturation temperature of the coldest part of the system during off-cycles. Because warm oil cannot absorb refrigerant vapor, migration is prevented. CCH power must be energized continuously for at least 12 to 24 hours prior to initial system startup following any extended power shutdown.
- Step-by-Step Worked Calculations: Compression Ratio Comparisons
- Calculation 1: High-Efficiency Comfort Air Conditioning System
Problem : A residential split-system operating with R-410A on a 95°F day shows a suction gauge pressure of 118.0 psig 118.0\text{ psig} 118.0 psig and a liquid discharge gauge pressure of 388.0 psig 388.0\text{ psig} 388.0 psig . Calculate the absolute compression ratio.
Step 1: Convert gauge pressures to absolute pressures (psia) P suction, absolute = 118.0 + 14.7 = 132.7 psia P_{\text{suction, absolute}} = 118.0 + 14.7 = 132.7\text{ psia} P suction, absolute = 118.0 + 14.7 = 132.7 psia P discharge, absolute = 388.0 + 14.7 = 402.7 psia P_{\text{discharge, absolute}} = 388.0 + 14.7 = 402.7\text{ psia} P discharge, absolute = 388.0 + 14.7 = 402.7 psia
Step 2: Calculate the compression ratio CR = 402.7 psia 132.7 psia = 3.035 ≈ 3.04 : 1 \text{CR} = \frac{402.7\text{ psia}}{132.7\text{ psia}} = 3.035 \approx 3.04:1 CR = 132.7 psia 402.7 psia = 3.035 ≈ 3.04 : 1
Assessment : A ratio of 3.04:1 is optimal for comfort air conditioning, ensuring high volumetric efficiency and low discharge temperatures.
Calculation 2: Low-Temperature Commercial Walk-in Freezer
Problem : A commercial low-temperature walk-in freezer running R-404A exhibits a suction pressure of 14.7 psig 14.7\text{ psig} 14.7 psig (evaporating temperature approx. -20°F) and a condensing discharge pressure of 245.0 psig 245.0\text{ psig} 245.0 psig (condensing temp approx. 105°F). Calculate the compression ratio and evaluate compressor thermal risk.
Step 1: Convert gauge pressures to absolute pressures (psia) P suction, absolute = 14.7 + 14.7 = 29.4 psia P_{\text{suction, absolute}} = 14.7 + 14.7 = 29.4\text{ psia} P suction, absolute = 14.7 + 14.7 = 29.4 psia P discharge, absolute = 245.0 + 14.7 = 259.7 psia P_{\text{discharge, absolute}} = 245.0 + 14.7 = 259.7\text{ psia} P discharge, absolute = 245.0 + 14.7 = 259.7 psia
Step 2: Calculate the compression ratio CR = 259.7 psia 29.4 psia = 8.83 : 1 \text{CR} = \frac{259.7\text{ psia}}{29.4\text{ psia}} = 8.83:1 CR = 29.4 psia 259.7 psia = 8.83 : 1
Assessment : A ratio of 8.83:1 is extremely demanding. The high ratio will substantially reduce compressor mass flow and elevate internal discharge temperatures. This system requires auxiliary head cooling fans, demand cooling liquid injection, or multi-stage compression to prevent oil thermal breakdown.