Study guide
6.3 Condensers & Evaporators
Arkansas HVAC/R Contractor License Exam
Track your progress as you read
Finished sections get a check mark.
1 Arkansas HVAC/R Licensing Law, Board Rules & Administration
1.1 Arkansas HVAC/R Board Authority, Statutes & Definitions 1.2 License Classifications & Capacity Limitations 1.3 Registrant Requirements, Apprenticeship & Experience Verification 1.4 License Renewal, Continuing Education & Disciplinary Actions
2 HVAC Thermodynamics, Psychrometrics & Gas Laws
2.1 Principles of Heat Transfer & Thermodynamic Fundamentals 2.2 Psychrometric Chart Dynamics & Air Properties 2.3 Psychrometric Processes & Air Mixture Calculations 2.4 Gas Laws Applied to HVAC/R Systems
3 Heating and Cooling Load Calculations (Manual J & S)
3.1 ACCA Manual J Design Conditions & Thermal Envelopes 3.2 Peak Cooling Load Calculations: Sensible vs. Latent Heat Gain 3.3 Heating Load Calculations & Infiltration Rates 3.4 ACCA Manual S Equipment Selection & Verification
4 Ductwork Design, Sizing & SMACNA Standards (Manual D)
4.1 ACCA Manual D Airflow Fundamentals & External Static Pressure 4.2 Equal Friction & Static Regain Duct Sizing Methods 4.3 Duct Fittings, Equivalent Length & Dynamic Losses 4.4 SMACNA Duct Construction Standards & Joint Sealing
5 Air Distribution, Balancing & Ventilation Codes
5.1 Supply & Return Air Distribution Hardware (Grilles, Registers, Diffusers) 5.2 System Airflow Testing, Adjusting & Balancing (TAB) 5.3 Ventilation Standards: ASHRAE 62.1, 62.2 & 2021 IMC Ventilation Air
6 Mechanical Refrigeration Cycle & Components
6.1 The Vapor-Compression Refrigeration Cycle 6.2 Compressors & Operating Characteristics 6.3 Condensers & Evaporators 6.4 Metering Devices & Refrigerant Flow Controls 6.5 Refrigerant Line Sizing, Oil Return & Field Piping Practices
7 Refrigerants, Oils & EPA Section 608 Regulations
7.1 Refrigerant Chemistry, ASHRAE Standard 34 & A2L Transition 7.2 Lubricating Oils & System Compatibility 7.3 EPA Section 608 Regulatory Mandates & Recovery Standards 7.4 System Evacuation, Dehydration & Leak Detection
8 Air Conditioning & Heat Pump Systems
8.1 Residential & Commercial Split Systems and Package RTUs 8.2 Air-Source Heat Pumps & The Reversing Valve 8.3 Supplemental & Emergency Heating Systems 8.4 Dual-Fuel & Geothermal (Ground-Source) Heat Pump Systems
9 Gas Furnaces, Combustion Air & Venting (IFGC / IMC)
9.1 Gas Furnace Types, AFUE Ratings & Sequence of Operation 9.2 Gas Burners, Ignition Systems & Flame Safeguard Controls 9.3 Combustion Air Requirements (IFGC Chapter 3 / IMC Chapter 7) 9.4 Flue Gas Venting & Category I-IV Venting Systems
10 Boilers, Hydronics & Fuel Gas Piping
10.1 Hydronic Heating Systems, Low-Pressure Boilers & ASME Code 10.2 Hydronic Distribution, Circulator Pumps & Piping Loops 10.3 Fuel Gas Piping Materials, Sizing & Pressure Testing (IFGC Chapter 4) 10.4 Gas Regulators, Manifold Pressure & Gas Meter Sizing 10.5 Condensate Disposal, Piping Support & Mechanical Insulation
11 Electrical Fundamentals, Motors & Control Circuits
11.1 HVAC Electrical Fundamentals, Ohm's Law & Power Calculations 11.2 Single-Phase & Three-Phase Electric Motors in HVAC 11.3 Low-Voltage Control Circuits & Thermostats
12 National Electrical Code (NEC) for HVAC Equipment
12.1 NEC Article 440: Hermetic Refrigerant Motor-Compressors & Branch Circuits 12.2 Equipment Disconnecting Means & Overcurrent Protective Devices (OCPD) 12.3 Motor Branch Circuit Sizing & Conductor Ampacity (NEC Article 430 & Tables)
13 System Maintenance, Troubleshooting & Safety Standards
13.1 Systematic Mechanical & Electrical Troubleshooting 13.2 Airflow & Refrigerant Charge Diagnostics 13.3 Jobsite Safety, OSHA Standards & Personal Protective Equipment
14 Plan Reading, Estimating & HVAC/R Trade Math
14.1 Mechanical Plan Symbols, Schedules & Abbreviations 14.2 Architectural Scales, Dimensions & Quantity Takeoff 14.3 Material, Labor & Bid Estimating 14.4 Applied HVAC/R Trade Math & Unit Conversions
6.3 Condensers & Evaporators
Key Takeaways Explain This Topic AI
Condensers must reject the combined thermal load of the indoor evaporator plus the mechanical work of compression (THR = Q_evap + W_comp), making condenser heat rejection 20% to 50% greater than nominal cooling capacity.
Air-cooled condensers are evaluated by the Condensing Temperature Difference (CTD = T_condensing - T_ambient), while water-cooled condenser systems are evaluated by Cooling Tower Approach (T_leaving water - T_ambient wet-bulb) and Cooling Range (T_entering water - T_leaving water).
Water-cooled condensers on open cooling tower loops require a standard water flow rate of 3.0 GPM per ton of cooling (operating across a 10°F range, typically 95°F entering / 85°F leaving), whereas city water once-through systems require 1.5 to 2.0 GPM per ton.
Direct Expansion (DX) evaporators feed refrigerant through multi-circuit distributors and ensure 8°F to 12°F of vapor superheat at the outlet, whereas Flooded evaporators submerge all heat transfer surfaces in liquid refrigerant to maximize heat transfer coefficients.
Frost accumulation on sub-32°F evaporator coils restricts airflow and insulates heat transfer surfaces, requiring timed, electric resistance, or hot-gas defrost systems terminated by temperature or pressure switches with fail-safe time backups.
Last updated: September 2026
6.3 Condensers & Evaporators
Note
The Primary Heat Exchangers : The condenser and the evaporator are the thermal interfaces where mechanical refrigeration interacts with the environment. The evaporator absorbs heat from the conditioned space or fluid by boiling liquid refrigerant at low saturation pressure. The condenser rejects that absorbed heat—plus the heat generated by the mechanical work of compression—to an external sink (outdoor air, cooling tower water, or an evaporative spray). Understanding heat exchanger design, flow hydraulics, approach temperatures, and frost dynamics is fundamental for trade licensing and field diagnostics.
Condenser Fundamentals and Heat Rejection Dynamics
Under the First Law of Thermodynamics , energy cannot be destroyed. Therefore, the Total Heat of Rejection (THR) that a condenser must discharge to the outdoor sink always exceeds the evaporator net refrigerating capacity ( Q evap Q_{\text{evap}} Q evap ): THR = Q evaporator + W compressor \text{THR} = Q_{\text{evaporator}} + W_{\text{compressor}} THR = Q evaporator + W compressor
In typical comfort air conditioning systems, the compressor adds roughly 3 , 000 BTU/hr 3,000\text{ BTU/hr} 3 , 000 BTU/hr of electrical/mechanical heat per ton ( 12 , 000 BTU/hr 12,000\text{ BTU/hr} 12 , 000 BTU/hr ), resulting in a THR of approximately 15 , 000 BTU/hr 15,000\text{ BTU/hr} 15 , 000 BTU/hr per nominal ton (a Heat Rejection Factor of 1.25).
In low-temperature refrigeration systems (operating at high compression ratios and high work inputs), the compressor may add 5 , 000 to 6 , 000 BTU/hr 5,000\text{ to }6,000\text{ BTU/hr} 5 , 000 to 6 , 000 BTU/hr per ton, resulting in a THR of 17 , 000 to 18 , 000 BTU/hr 17,000\text{ to }18,000\text{ BTU/hr} 17 , 000 to 18 , 000 BTU/hr per ton (a Heat Rejection Factor of 1.45 to 1.50). +-------------------------------------------------------------------------+
- | CONDENSER HEAT REJECTION SPECTRUM |
- +-------------------------------------------------------------------------+
- | [1. Desuperheating Zone] Sensible heat removal (Gas cools from 180°F |
- | down to 120°F saturation) (~10-15% of total) |
- +-------------------------------------------------------------------------+
- | [2. Condensing Zone] Latent heat removal (Isothermal phase change |
- | from 100% vapor to 100% liquid) (~75-80%) |
- +-------------------------------------------------------------------------+
- | [3. Subcooling Zone] Sensible heat removal (Liquid cools below |
- | 120°F to ~108°F) (~5-10% of total) |
- +-------------------------------------------------------------------------+
- Primary Condenser Classifications
- 1. Air-Cooled Condensers
Air-cooled condensers circulate outdoor ambient air across finned tubing using propeller fans.
Coil Geometries :
Copper Tube / Aluminum Fin (RTPF) : Traditional robust design; easily cleaned and field-repaired, but larger footprint.
All-Aluminum Microchannel Coils (MCHE) : Consists of flat extruded aluminum tubes with microscopic internal ports and folded louvered fins. Microchannel coils provide up to 40% higher heat transfer density and reduce system refrigerant charge by 30% to 50% . However, they are highly sensitive to dirt fouling, difficult to clean without fin damage, and cannot be easily brazed in the field if punctured.
Airflow Requirements : Modern air-cooled condensing units require 600 to 1 , 000 CFM 600\text{ to }1,000\text{ CFM} 600 to 1 , 000 CFM of condenser airflow per ton of capacity.
Condensing Temperature Difference (CTD) : The difference between the saturated condensing temperature ( T cond T_{\text{cond}} T cond ) and the entering ambient dry-bulb temperature ( T ambient T_{\text{ambient}} T ambient ): CTD = T condensing − T ambient \text{CTD} = T_{\text{condensing}} - T_{\text{ambient}} CTD = T condensing − T ambient
Standard-efficiency units operate with a CTD of 25°F to 30°F (e.g., at 95°F ambient, condensing temp is 120°F–125°F).
High-efficiency systems (SEER2 16+) operate with large oversized coils featuring a CTD of 15°F to 20°F (e.g., at 95°F ambient, condensing temp is only 110°F–115°F, substantially lowering compressor head pressure and power draw).
2. Water-Cooled Condensers
Water-cooled condensers transfer heat to circulating liquid water. Because liquid water has a specific heat capacity four times higher than air ( c = 1.00 vs. 0.24 c = 1.00\text{ vs. }0.24 c = 1.00 vs. 0.24 ) and dramatically superior surface film coefficients, water-cooled condensers are far more compact and operate at lower condensing pressures.
Construction Types :
Tube-in-Tube (Coaxial) : Compact counter-flow heat exchanger where refrigerant flows through the outer annular space and water circulates through the inner fluted copper tube. Common in geothermal and packaged water-source heat pumps.
Shell-and-Coil : Refrigerant discharges into a welded steel shell, condensing on a submerged coiled water tube. Compact, but cannot be mechanically cleaned (requires chemical acid flushing).
Shell-and-Tube : Industrial design with straight copper or cupronickel tubes rolled into heavy steel tube sheets within an outer steel shell. Cast iron or bronze water heads (bonnets) are bolted to each end with removable gaskets, allowing mechanical cleaning with rotating nylon brushes.
Water Flow Rates and Hydraulics :
Cooling Tower Open Loops : Standard design requires 3.0 GPM per ton 3.0\text{ GPM per ton} 3.0 GPM per ton based on a 10°F water temperature rise ( 95 ∘ F 95^\circ\text{F} 9 5 ∘ F entering tower, 85 ∘ F 85^\circ\text{F} 8 5 ∘ F leaving tower returning to condenser): GPM = THR 500 × Δ T = 15 , 000 BTU/hr 500 × 10 ∘ F = 3.0 GPM/ton \text{GPM} = \frac{\text{THR}}{500 \times \Delta T} = \frac{15,000\text{ BTU/hr}}{500 \times 10^\circ\text{F}} = 3.0\text{ GPM/ton} GPM = 500 × Δ T THR = 500 × 1 0 ∘ F 15 , 000 BTU/hr = 3.0 GPM/ton
City Water (Once-Through Waste Systems) : Historically designed for 1.5 to 2.0 GPM per ton 1.5\text{ to }2.0\text{ GPM per ton} 1.5 to 2.0 GPM per ton across a 20°F to 30°F rise (e.g., 55°F entering tap water, 85°F discharge to sewer), though largely prohibited today due to water conservation laws.
3. Cooling Towers & Evaporative Condensers
Cooling towers and evaporative condensers reject heat against the outdoor ambient wet-bulb temperature through the evaporation of water droplets.
Thermodynamic Superiority : Because the summer outdoor wet-bulb temperature is typically 15°F to 25°F lower than the dry-bulb temperature (e.g., 76°F wet-bulb on a 96°F dry-bulb day in Little Rock), evaporative equipment allows the system to condense at 85°F to 90°F rather than 120°F, slashing compressor power by 30% to 40%.
Cooling Tower Approach & Range :
Approach : The temperature difference between the cold water leaving the cooling tower basin ( T leaving water T_{\text{leaving water}} T leaving water ) and the ambient outdoor wet-bulb temperature ( T wet-bulb T_{\text{wet-bulb}} T wet-bulb ): Approach = T leaving water − T wet-bulb \text{Approach} = T_{\text{leaving water}} - T_{\text{wet-bulb}} Approach = T leaving water − T wet-bulb (Standard engineering design approach is 7°F to 10°F ; an approach below 5°F requires an infinitely large tower footprint.)
Range : The temperature difference between the hot water entering the tower from the condenser ( T entering water T_{\text{entering water}} T entering water ) and the cooled water leaving the tower basin ( T leaving water T_{\text{leaving water}} T leaving water ): Range = T entering water − T leaving water \text{Range} = T_{\text{entering water}} - T_{\text{leaving water}} Range = T entering water − T leaving water (Standard nominal design range is 10°F , typically 95°F in and 85°F out.) HOT WATER FROM CONDENSER (95°F)
- |
- v
- +-------------------------+
- | SPRAY DISTRIBUTION |
- +-------------------------+
- |
- AMBIENT AIR v DRIFT ELIMINATORS
- 76°F Wet-Bulb ===> [ FILL ] ===> WARM EXHAUST AIR
- |
- v
- +-------------------------+
- | COLD WATER BASIN |
- +-------------------------+
- |
- v
- COOLED WATER TO CONDENSER (85°F)
- Approach = 85°F - 76°F = 9°F
- Range = 95°F - 85°F = 10°F
- Evaporator Fundamentals & Operating Classifications
The evaporator absorbs heat from air, water, or process fluids by boiling liquid refrigerant at low pressure.
1. Direct Expansion (DX) Evaporators
In a Direct Expansion (DX) evaporator, liquid refrigerant is metered through an expansion valve directly into multi-circuit distributor tubes. The refrigerant enters as a low-temperature, low-quality liquid/vapor mixture and boils continuously as it travels through the serpentine copper tube passes.
Superheating Requirement : In a DX coil, the final 10% to 15% of the coil surface area must be reserved to sensibly heat the dry vapor above its boiling point, establishing 8°F to 12°F of suction superheat to protect the compressor against liquid carryover.
Airflow Standards : Comfort cooling DX coils require 400 CFM 400\text{ CFM} 400 CFM of airflow per nominal ton (allowable range: 350 to 450 CFM/ton 350\text{ to }450\text{ CFM/ton} 350 to 450 CFM/ton ). If restricted air filters or failed blowers drop airflow below 300 CFM/ton 300\text{ CFM/ton} 300 CFM/ton , evaporating pressure collapses, coil temperatures drop below 32°F, and severe frost forms.
2. Flooded Evaporators
In a flooded evaporator, the entire heat transfer surface is completely submerged in boiling liquid refrigerant at all times.
Mechanics : A low-pressure liquid surge drum (separator vessel) sits above the tube bundle. Liquid refrigerant is maintained at a fixed level inside the shell or tubes via a low-pressure float switch or pilot valve. Liquid boils violently across 100% of the surface area, and the generated vapor bubbles rise into the surge drum, where liquid droplets separate out by gravity, delivering 100% dry saturated vapor to the compressor.
Heat Transfer Advantage : Because 100% of the internal tube area is wetted by boiling liquid (with zero surface area wasted on sensible vapor superheating), flooded evaporators achieve overall heat transfer coefficients ( U U U -factors) two to three times higher than DX coils.
Applications : Large centrifugal and screw water chillers (shell-and-tube configurations where chilled water flows inside tubes while refrigerant boils in the shell), and industrial food processing facilities.
Oil Management : Since refrigerant boils away leaving oil behind in the flooded vessel, dedicated oil rectifiers, skimmers, or oil stills are mandatory to prevent oil accumulation from coating tubes and starving the compressor crankcase.
3. Finned-Tube Geometry & Fin Spacing
Comfort Air Conditioning : Coils operate above 32°F evaporating temperatures without frost. They utilize closely spaced fins— 12 to 16 fins per inch (FPI) —to maximize air contact area within a compact cabinet.
Commercial Refrigeration : Medium-temperature coolers (35°F to 38°F box) operate at 25°F to 28°F evaporating temperatures, developing light frost; they use 6 to 8 FPI . Low-temperature freezers (-10°F to 0°F box) operate at -20°F to -15°F evaporating temperatures, accumulating heavy frost; they use wide 3 to 5 FPI spacing to maintain airflow passages between defrost cycles.
Frost Dynamics & Defrost Control Sequences
When an evaporator coil operates at a surface temperature below 32°F while the entering air dew-point temperature is above the coil temperature, moisture in the air deposits directly onto the cold metal surfaces as frost.
The Compounding Cycle of Coil Freezing
Frost acts as a thermal insulator ( k frost ≪ k aluminum k_{\text{frost}} \ll k_{\text{aluminum}} k frost ≪ k aluminum ). As the ice layer thickens, it chokes the air passages between fins. The reduced airflow further reduces heat transfer into the refrigerant, causing evaporating pressure and temperature to plunge even lower. This accelerates frost formation until the entire coil freezes into a solid block of ice, terminating all cooling. Coil Below 32°F --> Moisture Freezes --> Fins Clog --> Airflow Drops
- ^ |
- | v
- Complete Coil Freeze-up <-- Boiling Temp Collapses <-- Suction Drops
- Defrosting Methodologies
Off-Cycle Defrost (Air Defrost) : Used on medium-temperature walk-in coolers (35°F to 40°F room). A defrost timer de-energizes the compressor while keeping evaporator fans running. The warm 38°F room air circulates through the coil, naturally melting the frost.
Electric Resistance Defrost : Used on low-temperature walk-in freezers. Heavy-duty Calrod heating elements woven directly through the evaporator fin pack are energized. The compressor and evaporator fans are de-energized during defrost to prevent blowing heat and steam into the freezer.
Hot Gas Defrost : Highly efficient industrial method. A solenoid valve directs hot, high-pressure discharge gas straight from the compressor discharge manifold directly into the evaporator inlet. The evaporator temporarily becomes a condenser, releasing the latent heat of condensation internally through the tubes, melting ice from the inside out in 5 to 10 minutes.
Defrost Termination & Fan Delay Controls
Modern commercial refrigeration systems rely on Time-Initiated / Temperature-Terminated (or Pressure-Terminated) control sequences:
Defrost Termination Thermostat (Klixon / DTT) : Defrost initiates on a scheduled clock (e.g., every 6 hours). Once the coil fin temperature rises to 45°F to 55°F , confirming that all ice has melted, the DTT bimetal switch opens, terminating the heating elements immediately to prevent steaming the box.
Fail-Safe Timer Backup : If the temperature termination switch fails to open, a mechanical or electronic timer forcibly terminates defrost after 30 to 45 minutes , preventing box temperature runaway.
Fan Delay Thermostat : After defrost terminates, the compressor restarts, but the evaporator fans remain locked out until the coil temperature drops back below 30°F to 32°F . This fan delay prevents moisture droplets remaining on the fins from being blown into the box as warm fog or freezing onto ceiling surfaces.
- Step-by-Step Worked Engineering Calculations
- Calculation 1: Cooling Tower Water Flow Sizing
Problem : A commercial facility utilizes a 120-ton water-cooled centrifugal chiller operating with a Heat Rejection Factor of 1.25. Calculate the Total Heat of Rejection in BTU/hr and determine the required cooling tower water flow rate in GPM across a standard 10°F cooling range.
Step 1: Calculate Total Heat of Rejection (THR) Cooling Capacity = 120 tons × 12 , 000 BTU/hr/ton = 1 , 440 , 000 BTU/hr \text{Cooling Capacity} = 120\text{ tons} \times 12,000\text{ BTU/hr/ton} = 1,440,000\text{ BTU/hr} Cooling Capacity = 120 tons × 12 , 000 BTU/hr/ton = 1 , 440 , 000 BTU/hr THR = 1 , 440 , 000 BTU/hr × 1.25 = 1 , 800 , 000 BTU/hr \text{THR} = 1,440,000\text{ BTU/hr} \times 1.25 = 1,800,000\text{ BTU/hr} THR = 1 , 440 , 000 BTU/hr × 1.25 = 1 , 800 , 000 BTU/hr
Step 2: Calculate required GPM using the hydronic heat transfer formula ( Q = 500 × GPM × Δ T Q = 500 \times \text{GPM} \times \Delta T Q = 500 × GPM × Δ T ) GPM = THR 500 × Δ T = 1 , 800 , 000 500 × 10 ∘ F = 1 , 800 , 000 5 , 000 = 360 GPM \text{GPM} = \frac{\text{THR}}{500 \times \Delta T} = \frac{1,800,000}{500 \times 10^\circ\text{F}} = \frac{1,800,000}{5,000} = 360\text{ GPM} GPM = 500 × Δ T THR = 500 × 1 0 ∘ F 1 , 800 , 000 = 5 , 000 1 , 800 , 000 = 360 GPM
Shortcut Rule of Thumb Check : 120 tons × 3.0 GPM/ton = 360 GPM 120\text{ tons} \times 3.0\text{ GPM/ton} = 360\text{ GPM} 120 tons × 3.0 GPM/ton = 360 GPM . Matches exact hydronic derivation.
Calculation 2: Cooling Tower Approach and Range Evaluation
Problem : Field commissioning of a cooling tower in Fort Smith, Arkansas, records the following operating temperatures during peak summer conditions:
- Ambient Outdoor Dry-Bulb: 98°F
- Ambient Outdoor Wet-Bulb: 77°F
- Hot Water Entering Cooling Tower from Condenser: 96°F
- Cold Water Leaving Cooling Tower Basin to Condenser: 86°F
Calculate the Cooling Tower Range and Cooling Tower Approach.
Step 1: Calculate the Cooling Tower Range Range = T entering water − T leaving water = 96 ∘ F − 86 ∘ F = 10.0 ∘ F \text{Range} = T_{\text{entering water}} - T_{\text{leaving water}} = 96^\circ\text{F} - 86^\circ\text{F} = 10.0^\circ\text{F} Range = T entering water − T leaving water = 9 6 ∘ F − 8 6 ∘ F = 10. 0 ∘ F
Step 2: Calculate the Cooling Tower Approach Approach = T leaving water − T wet-bulb = 86 ∘ F − 77 ∘ F = 9.0 ∘ F \text{Approach} = T_{\text{leaving water}} - T_{\text{wet-bulb}} = 86^\circ\text{F} - 77^\circ\text{F} = 9.0^\circ\text{F} Approach = T leaving water − T wet-bulb = 8 6 ∘ F − 7 7 ∘ F = 9. 0 ∘ F
Assessment : Both metrics fall squarely within optimum industry benchmarks (10°F range, 9°F approach), indicating proper tower airflow, clean fill media, and balanced water distribution.