Study guide

12.1 NEC Article 440: Hermetic Refrigerant Motor-Compressors & Branch Circuits

Arkansas HVAC/R Contractor License Exam

Track your progress as you read

Finished sections get a check mark.

1 Arkansas HVAC/R Licensing Law, Board Rules & Administration

1.1 Arkansas HVAC/R Board Authority, Statutes & Definitions 1.2 License Classifications & Capacity Limitations 1.3 Registrant Requirements, Apprenticeship & Experience Verification 1.4 License Renewal, Continuing Education & Disciplinary Actions

2 HVAC Thermodynamics, Psychrometrics & Gas Laws

2.1 Principles of Heat Transfer & Thermodynamic Fundamentals 2.2 Psychrometric Chart Dynamics & Air Properties 2.3 Psychrometric Processes & Air Mixture Calculations 2.4 Gas Laws Applied to HVAC/R Systems

3 Heating and Cooling Load Calculations (Manual J & S)

3.1 ACCA Manual J Design Conditions & Thermal Envelopes 3.2 Peak Cooling Load Calculations: Sensible vs. Latent Heat Gain 3.3 Heating Load Calculations & Infiltration Rates 3.4 ACCA Manual S Equipment Selection & Verification

4 Ductwork Design, Sizing & SMACNA Standards (Manual D)

4.1 ACCA Manual D Airflow Fundamentals & External Static Pressure 4.2 Equal Friction & Static Regain Duct Sizing Methods 4.3 Duct Fittings, Equivalent Length & Dynamic Losses 4.4 SMACNA Duct Construction Standards & Joint Sealing

5 Air Distribution, Balancing & Ventilation Codes

5.1 Supply & Return Air Distribution Hardware (Grilles, Registers, Diffusers) 5.2 System Airflow Testing, Adjusting & Balancing (TAB) 5.3 Ventilation Standards: ASHRAE 62.1, 62.2 & 2021 IMC Ventilation Air

6 Mechanical Refrigeration Cycle & Components

6.1 The Vapor-Compression Refrigeration Cycle 6.2 Compressors & Operating Characteristics 6.3 Condensers & Evaporators 6.4 Metering Devices & Refrigerant Flow Controls 6.5 Refrigerant Line Sizing, Oil Return & Field Piping Practices

7 Refrigerants, Oils & EPA Section 608 Regulations

7.1 Refrigerant Chemistry, ASHRAE Standard 34 & A2L Transition 7.2 Lubricating Oils & System Compatibility 7.3 EPA Section 608 Regulatory Mandates & Recovery Standards 7.4 System Evacuation, Dehydration & Leak Detection

8 Air Conditioning & Heat Pump Systems

8.1 Residential & Commercial Split Systems and Package RTUs 8.2 Air-Source Heat Pumps & The Reversing Valve 8.3 Supplemental & Emergency Heating Systems 8.4 Dual-Fuel & Geothermal (Ground-Source) Heat Pump Systems

9 Gas Furnaces, Combustion Air & Venting (IFGC / IMC)

9.1 Gas Furnace Types, AFUE Ratings & Sequence of Operation 9.2 Gas Burners, Ignition Systems & Flame Safeguard Controls 9.3 Combustion Air Requirements (IFGC Chapter 3 / IMC Chapter 7) 9.4 Flue Gas Venting & Category I-IV Venting Systems

10 Boilers, Hydronics & Fuel Gas Piping

10.1 Hydronic Heating Systems, Low-Pressure Boilers & ASME Code 10.2 Hydronic Distribution, Circulator Pumps & Piping Loops 10.3 Fuel Gas Piping Materials, Sizing & Pressure Testing (IFGC Chapter 4) 10.4 Gas Regulators, Manifold Pressure & Gas Meter Sizing 10.5 Condensate Disposal, Piping Support & Mechanical Insulation

11 Electrical Fundamentals, Motors & Control Circuits

11.1 HVAC Electrical Fundamentals, Ohm's Law & Power Calculations 11.2 Single-Phase & Three-Phase Electric Motors in HVAC 11.3 Low-Voltage Control Circuits & Thermostats

12 National Electrical Code (NEC) for HVAC Equipment

12.1 NEC Article 440: Hermetic Refrigerant Motor-Compressors & Branch Circuits 12.2 Equipment Disconnecting Means & Overcurrent Protective Devices (OCPD) 12.3 Motor Branch Circuit Sizing & Conductor Ampacity (NEC Article 430 & Tables)

13 System Maintenance, Troubleshooting & Safety Standards

13.1 Systematic Mechanical & Electrical Troubleshooting 13.2 Airflow & Refrigerant Charge Diagnostics 13.3 Jobsite Safety, OSHA Standards & Personal Protective Equipment

14 Plan Reading, Estimating & HVAC/R Trade Math

14.1 Mechanical Plan Symbols, Schedules & Abbreviations 14.2 Architectural Scales, Dimensions & Quantity Takeoff 14.3 Material, Labor & Bid Estimating 14.4 Applied HVAC/R Trade Math & Unit Conversions

12.1 NEC Article 440: Hermetic Refrigerant Motor-Compressors & Branch Circuits

Key Takeaways Explain This Topic AI

NEC Article 440 governs hermetic refrigerant motor-compressors where the electric motor operates immersed in a refrigerant atmosphere, superseding or modifying general motor rules in Article 430.

Branch-Circuit Selection Current (BCSC) is marked on equipment nameplates when continuous severe loading exceeds Rated Load Amps (RLA); when present, BCSC must replace RLA in all branch circuit conductor and protection calculations.

Minimum Circuit Ampacity (MCA) dictates field wiring size using the formula MCA = 1.25 × RLA_largest + ∑ other loads, ensuring conductors carry continuous operating currents plus a 25% safety margin on the largest motor without thermal degradation.

Maximum Overcurrent Protective Device (MOCPD) provides branch-circuit short-circuit and ground-fault protection up to 225% of compressor RLA plus secondary loads, rounded down to standard fuse/breaker sizes (or up if below MCA).

HVAC equipment nameplates list both MCA and MOCPD; field conductors are sized strictly to MCA, while upstream breakers are sized up to MOCPD, forming a fully code-compliant exception to general small-conductor rules under NEC 240.4(G).

Last updated: September 2026

12.1 NEC Article 440: Hermetic Refrigerant Motor-Compressors & Branch Circuits

Note

Core Electrical & Code Foundation : In HVAC/R systems, electrical installation and circuit sizing are governed by the National Electrical Code (NEC / NFPA 70) . While conventional electric motors fall under NEC Article 430 , hermetic refrigerant motor-compressors possess distinct operational and thermodynamic characteristics that mandate specialized rules under NEC Article 440 . Arkansas HVAC/R contractor licensing candidates must master the boundary between Article 430 and Article 440, nameplate current ratings, Minimum Circuit Ampacity (MCA) derivations, and Maximum Overcurrent Protective Device (MOCPD) sizing.

Scope & Regulatory Philosophy: Article 440 vs. Article 430

Under NEC 440.1 , the provisions of Article 440 apply to electrically driven air-conditioning and refrigerating equipment that incorporates one or more hermetic refrigerant motor-compressors , as well as the branch circuits, controllers, and disconnecting means serving them. Under NEC 440.3(A) , the rules in Article 440 are specific to this equipment and amend, modify, or supersede the general motor requirements found in Article 430.

Open-Drive Motors vs. Hermetic Refrigerant Motor-Compressors

To understand why the National Electrical Code treats HVAC compressors differently from standard electric motors, one must examine the physical and thermal environments in which they operate:

Standard Open-Drive Motors (NEC Article 430) : A conventional motor (such as a belt-driven blower or centrifugal water pump) is housed in its own external frame. It relies on an external shaft seal and is cooled by ambient air circulated across its external housing by an integral shaft-mounted cooling fan (Totally Enclosed Fan Cooled - TEFC) or through open ventilation louvers (Open Drip Proof - ODP). The heat generated by electrical resistance in the stator windings is rejected directly into the surrounding ambient air.

Hermetic Motor-Compressors (NEC Article 440) : In a hermetic compressor, the electric motor stator and rotor are enclosed inside the exact same sealed welded steel dome (or semi-hermetic bolted cast-iron housing) as the mechanical compressor pump. There is no external drive shaft and no dynamic shaft seal. The motor windings operate completely immersed in a circulating bath of cold suction refrigerant vapor and lubricating oil . CONVENTIONAL OPEN MOTOR (NEC ART. 430) HERMETIC MOTOR-COMPRESSOR (NEC ART. 440)

  • +------------------------------------+ +-----------------------------------------+
  • | [Cooling Fan] | | Sealed Steel Shell (Pressure Vessel) |
  • | | | | |
  • | ▼ | | Suction Gas In (Cold Vapor) |
  • | +-------------+ External Shaft | | │ |
  • | | Motor Frame |==================>| | ▼ |
  • | +-------------+ | | +---------------+ Direct Coupling |
  • | Cooled by Ambient Air Flow | | | Motor Windings|═════════════════╗ |
  • +------------------------------------+ | +---------------+ ║ |
  • | Immersed in Refrigerant & Oil ║ |
  • | ▼ |
  • | +------------+|
  • | | Compressor ||
  • | +------------+|
  • +-----------------------------------------+

Because the rate of motor winding cooling is directly proportional to the density, temperature, and mass flow rate of returning suction refrigerant gas , a hermetic compressor's thermal capacity is decoupled from ambient air circulation. A hermetic motor can deliver substantial horsepower output in an extremely compact frame size because suction gas provides far more aggressive heat extraction than ambient air.

Conversely, if a refrigeration system experiences a loss of refrigerant charge, a restricted thermostatic expansion valve (TXV), or a frozen evaporator coil, the mass flow rate of suction vapor collapses. Under these starvation conditions, the compressor motor windings rapidly overheat—even when drawing electrical current well below normal operating levels. Because standard full-load current tables cannot account for these specialized thermodynamic interactions, NEC 440.6 explicitly prohibits using NEC Tables 430.248, 430.249, or 430.250 to size branch circuits for hermetic motor-compressors . All calculations must instead originate from nameplate data.

Motor-Compressor Nameplate Current Designations

HVAC equipment nameplates display specialized electrical metrics that differ from conventional horsepower ratings. Contractors must correctly interpret each designation:

1. Rated Load Amps (RLA) / Rated Load Current (RLC)

Under NEC 440.2 , the rated-load current (RLC) —universally marked on equipment nameplates as Rated Load Amps (RLA) —is the current drawn by the motor-compressor when operating under rated voltage, rated frequency, and standard operating conditions of suction pressure, discharge pressure, and ambient temperature established by testing laboratories (such as AHRI Standard 540 and UL 1995 / UL 60335-2-40 ).

RLA is an engineered benchmarking value, not a measured continuous operating ceiling. In the field, an air-conditioning compressor operating on an extremely hot afternoon (e.g., 105°F outdoor ambient) with an elevated condensing pressure will draw more than its marked RLA, whereas on a mild 75°F day it will draw significantly less.

2. Branch-Circuit Selection Current (BCSC)

Under NEC 440.2 , the Branch-Circuit Selection Current (BCSC) is a rated value in amperes, established by the manufacturer, that represents the continuous current drawn by the compressor under the most severe continuous thermal loading conditions permitted by the equipment design and internal overload protectors.

Important

The BCSC Substitution Rule (NEC 440.4(C)) : Whenever an HVAC manufacturer marks a Branch-Circuit Selection Current (BCSC) on the equipment nameplate that is greater than the marked rated-load current (RLA) , the BCSC MUST be used in place of the RLA for all field electrical calculations. This includes sizing branch-circuit conductors, disconnecting means, motor controllers, and branch-circuit short-circuit and ground-fault protective devices (MOCPD). If BCSC is not marked on the nameplate, the marked RLA governs.

3. Locked Rotor Amps (LRA)

Locked Rotor Amps (LRA) represents the steady-state electrical current drawn by the motor-compressor at the instant line voltage is applied across the stator windings while the rotor remains stationary (0 RPM). Because there is zero counter-electromotive force (CEMF) generated by rotor rotation, LRA is limited solely by the low DC resistance and inductive reactance of the stator copper windings.

In single-phase residential split-system compressors, LRA is typically 5 to 7 times the marked RLA.

LRA is used by field contractors and engineers under NEC 440.12 to determine the interrupting capacity and equivalent horsepower rating of disconnecting means and contactors.

LRA causes substantial line voltage drop during compressor startup, necessitating start-assist components (hard-start kits consisting of a potential relay and start capacitor) on long line sets or high-head-pressure installations.

Minimum Circuit Ampacity (MCA) Calculation & Conductor Sizing

Branch-circuit conductors supplying HVAC equipment must be sized to carry continuous operational currents without exceeding the thermal limits of the conductor insulation. The equipment manufacturer calculates and publishes the Minimum Circuit Ampacity (MCA) on the serial nameplate. Field contractors must verify that the allowable ampacity of the field-installed conductors matches or exceeds this nameplate value.

Mathematical Formulation for Single Motor-Compressor (NEC 440.32)

For a branch circuit supplying a single hermetic refrigerant motor-compressor, the branch-circuit conductors must have an allowable ampacity of not less than 125% of the motor-compressor rated-load current (RLA) or Branch-Circuit Selection Current (BCSC), whichever is greater: M C A = 1.25 × max ⁡ ( R L A , B C S C ) MCA = 1.25 \times \max(RLA, BCSC) MC A = 1.25 × max ( R L A , BCSC )

The 125% multiplier accounts for the fact that air-conditioning compressors frequently operate as continuous loads (defined by NEC Article 100 as a load where the maximum current is expected to continue for 3 hours or more) during peak summer cooling periods.

Mathematical Formulation for Multimotor and Combination Equipment (NEC 440.35)

Modern condensing units, package rooftop units (RTUs), and heat pumps house multiple electrical loads within a single cabinet—such as a hermetic motor-compressor, an outdoor condenser fan motor, an indoor blower motor, and control transformers. Under NEC 440.35 , the Minimum Circuit Ampacity for combination equipment is derived by taking 125% of the largest motor or motor-compressor rated current , plus the sum of the full-load currents (or rated currents) of all other concurrent motors and non-motor loads : M C A = 1.25 × I largest + ∑ I other MCA = 1.25 \times I_{\text{largest}} + \sum I_{\text{other}} MC A = 1.25 × I largest ​ + ∑ I other ​

Where:

I largest I_{\text{largest}} I largest ​ is the RLA or BCSC of the largest compressor (or motor) in the system.

∑ I other \sum I_{\text{other}} ∑ I other ​ is the sum of the full-load currents (FLA) of outdoor fan motors, indoor blower motors, and other concurrent operational loads.

Step-by-Step Calculation Example 1: Residential Split-System Condensing Unit

A 3-ton residential outdoor split-system condensing unit displays the following nameplate data:

Compressor: 208 / 230 V 208/230\text{ V} 208/230 V , 1-Phase, R L A = 16.4 A RLA = 16.4\text{ A} R L A = 16.4 A , L R A = 88.0 A LRA = 88.0\text{ A} L R A = 88.0 A

Outdoor Condenser Fan Motor: 230 V 230\text{ V} 230 V , 1-Phase, F L A = 1.3 A FLA = 1.3\text{ A} F L A = 1.3 A

BCSC is not specified. M C A = ( 1.25 × R L A compressor ) + F L A fan M C A = ( 1.25 × 16.4 A ) + 1.3 A M C A = 20.5 A + 1.3 A = 21.8 A \begin{aligned}

  • MCA &= (1.25 \times RLA_{\text{compressor}}) + FLA_{\text{fan}} \\[4pt]
  • MCA &= (1.25 \times 16.4\text{ A}) + 1.3\text{ A} \\[4pt]
  • MCA &= 20.5\text{ A} + 1.3\text{ A} = 21.8\text{ A}

\end{aligned} MC A MC A MC A ​ = ( 1.25 × R L A compressor ​ ) + F L A fan ​ = ( 1.25 × 16.4 A ) + 1.3 A = 20.5 A + 1.3 A = 21.8 A ​

The unit nameplate will state MCA = 21.8 A (or rounded by the manufacturer to 22 A ). The field installer must install branch-circuit conductors with an allowable ampacity of at least 21.8 A after applying all applicable temperature and raceway fill adjustment factors.

Step-by-Step Calculation Example 2: Packaged Heat Pump with Auxiliary Electric Heat (NEC 440.34)

In packaged heat pumps equipped with auxiliary electric resistance heat banks, the heating elements and the compressor may or may not be permitted to operate simultaneously. Under NEC 440.34 , the branch-circuit ampacity must be evaluated under both cooling and heating modes:

Cooling Mode : M C A = ( 1.25 × R L A compressor ) + F L A outdoor fan + F L A indoor blower MCA = (1.25 \times RLA_{\text{compressor}}) + FLA_{\text{outdoor fan}} + FLA_{\text{indoor blower}} MC A = ( 1.25 × R L A compressor ​ ) + F L A outdoor fan ​ + F L A indoor blower ​

Heating Mode with Simultaneous Heat : If the control interlocks permit the compressor and electric strip heaters to energize concurrently, the circuit ampacity must equal 1.25 × R L A compressor + Heater Amps + ∑ F L A fans 1.25 \times RLA_{\text{compressor}} + \text{Heater Amps} + \sum FLA_{\text{fans}} 1.25 × R L A compressor ​ + Heater Amps + ∑ F L A fans ​ . Because electric resistance heat is a continuous non-motor load, under NEC 424.3(B) it is computed at 125% of rated wattage if served by an individual branch circuit, or integrated into the multimotor formula per equipment listing instructions.

The field branch-circuit conductors must be sized to whichever mode produces the highest calculated MCA.

Maximum Overcurrent Protective Device (MOCPD) Calculations & NEC 440.22 Rules

While the branch-circuit conductors are sized to the Minimum Circuit Ampacity (MCA), the branch-circuit overcurrent protective device—consisting of a circuit breaker or dual-element time-delay fuses—serves a fundamentally different function: Branch-Circuit Short-Circuit and Ground-Fault Protection (BCSCGFP) . +-----------------------------------------------------------------------------------------+

  • | DUAL-LAYER MOTOR PROTECTION ARCHITECTURE |
  • +-----------------------------------------------------------------------------------------+
  • | 1. Branch-Circuit Overcurrent Device (MOCPD - Breaker/Fuse): |
  • | - Located in main panel or fused disconnect. |
  • | - Sized up to 175%–225% of compressor RLA to clear high-current short circuits and |
  • | ground faults while carrying starting inrush (LRA) without nuisance tripping. |
  • | |
  • | 2. Internal Motor Overload Protector (Thermal Klixon / Electronic Thermistor): |
  • | - Located directly inside or on the compressor motor windings. |
  • | - Sized at 115%–140% of RLA to sense running overcurrent, mechanical bearing drag, |
  • | prolonged low voltage, locked rotor, and loss of suction refrigerant cooling. |
  • +-----------------------------------------------------------------------------------------+
  • The 175% Base Rule & 225% Maximum Ceiling (NEC 440.22(A))

For an individual motor-compressor, NEC 440.22(A) specifies that the protective device rating:

Shall not exceed 175% of the motor-compressor rated-load current (RLA) or branch-circuit selection current (BCSC).

The Exception : If the protective device sized at 175% is incapable of carrying the starting current of the motor-compressor (causing nuisance tripping during locked-rotor acceleration), the rating may be increased up to a maximum of 225% of the rated-load current (or BCSC).

In no case shall the protective device rating exceed 225% .

Multimotor Equipment MOCPD Formula (NEC 440.22(B))

Under NEC 440.22(B) , for equipment containing multiple motors or a motor-compressor plus auxiliary loads, the maximum rating of the branch-circuit short-circuit and ground-fault protective device is calculated as: M O C P D calculated = 2.25 × R L A largest + ∑ I other MOCPD_{\text{calculated}} = 2.25 \times RLA_{\text{largest}} + \sum I_{\text{other}} MOCP D calculated ​ = 2.25 × R L A largest ​ + ∑ I other ​

Where:

R L A largest RLA_{\text{largest}} R L A largest ​ is the rated-load current of the largest compressor motor.

∑ I other \sum I_{\text{other}} ∑ I other ​ is the sum of the full-load currents of all other concurrently operating motors and loads.

Standard Protective Device Ratings (NEC 240.6(A)) & Rounding Rules

Under NEC 240.6(A) , standard ampere ratings for fuses and fixed-trip inverse-time circuit breakers are: 15 , 20 , 25 , 30 , 35 , 40 , 45 , 50 , 60 , 70 , 80 , 90 , 100 , 110 , 125 , 150 , 175 , 200 A \mathbf{15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200\text{ A}} 15 , 20 , 25 , 30 , 35 , 40 , 45 , 50 , 60 , 70 , 80 , 90 , 100 , 110 , 125 , 150 , 175 , 200 A

When calculating the Maximum Overcurrent Protective Device (MOCPD) for an HVAC unit nameplate, the manufacturer applies strict rounding conventions:

Round Down to Next Lower Standard Size : Because the 225% multiplier represents an absolute safety ceiling under NEC 440.22, when the calculated MOCPD falls between two standard sizes, it must be rounded DOWN to the next lower standard rating listed in NEC 240.6(A).

The MCA Floor Constraint : The rating of the branch-circuit protective device cannot be smaller than the Minimum Circuit Ampacity (MCA) of the unit. If the rounded-down value falls below the MCA, the protective device must be rounded UP to the next standard rating that equals or exceeds the MCA, provided that rating does not exceed the absolute 225% ceiling.

Step-by-Step Calculation Example 3: MOCPD Derivation

Taking the 3-ton split-system condensing unit from Example 1:

  • Compressor R L A = 16.4 A RLA = 16.4\text{ A} R L A = 16.4 A
  • Outdoor Fan F L A = 1.3 A FLA = 1.3\text{ A} F L A = 1.3 A

Calculated M C A = 21.8 A MCA = 21.8\text{ A} MC A = 21.8 A M O C P D calculated = ( 2.25 × R L A compressor ) + F L A fan M O C P D calculated = ( 2.25 × 16.4 A ) + 1.3 A M O C P D calculated = 36.9 A + 1.3 A = 38.2 A \begin{aligned}

  • MOCPD_{\text{calculated}} &= (2.25 \times RLA_{\text{compressor}}) + FLA_{\text{fan}} \\[4pt]
  • MOCPD_{\text{calculated}} &= (2.25 \times 16.4\text{ A}) + 1.3\text{ A} \\[4pt]
  • MOCPD_{\text{calculated}} &= 36.9\text{ A} + 1.3\text{ A} = 38.2\text{ A}

\end{aligned} MOCP D calculated ​ MOCP D calculated ​ MOCP D calculated ​ ​ = ( 2.25 × R L A compressor ​ ) + F L A fan ​ = ( 2.25 × 16.4 A ) + 1.3 A = 36.9 A + 1.3 A = 38.2 A ​

The calculated maximum is 38.2 A 38.2\text{ A} 38.2 A .

Referring to the standard ratings in NEC 240.6(A) , the standard sizes surrounding 38.2 A 38.2\text{ A} 38.2 A are 35 A 35\text{ A} 35 A and 40 A 40\text{ A} 40 A .

Because 38.2 A 38.2\text{ A} 38.2 A represents the upper limit, rounding up to 40 A 40\text{ A} 40 A would violate the 225% statutory ceiling. Therefore, the value is rounded down to 35 A .

Since 35 A 35\text{ A} 35 A is comfortably above the M C A = 21.8 A MCA = 21.8\text{ A} MC A = 21.8 A , the unit nameplate will specify:

  • Minimum Circuit Ampacity: 21.8 A
  • Max Overcurrent Protective Device (Fuse/Breaker): 35 A
  • Decoupling Overload Protection from Short-Circuit Protection

A central point of confusion for apprentice electricians and HVAC technicians is why the National Electrical Code permits a 35 A circuit breaker to protect a branch circuit wired with 12 AWG copper conductors (which has a general 20 A limit under NEC 240.4(D)).

Under NEC 240.4(G) , the general conductor overcurrent protection limits specified in NEC 240.4(D) do not apply to equipment governed by Article 440. In standard residential circuits (e.g., receptacle circuits), the circuit breaker must perform dual duties: it must protect against short circuits AND it must protect against running conductor overloads. If an occupant plugs in three space heaters, the breaker must trip at 20 A before the 12 AWG wire overheats in the wall framing.

In an HVAC hermetic compressor circuit, however, overload protection and short-circuit protection are physically decoupled :

Running Overload Protection (NEC Article 440 Part VI) : Handled directly at the compressor by an inherent thermal overload protector (a bimetallic snap-disc Klixon device or solid-state thermistor sensor embedded in the motor stator windings). This device trips if the motor draws excessive running current (typically calibrated between 115% and 140% of RLA), if suction cooling fails, or if the rotor locks. It protects the motor and the branch-circuit conductors from sustained thermal overload.

Short-Circuit and Ground-Fault Protection (NEC Article 440 Part III) : Handled by the upstream branch-circuit breaker or fuse. Because the internal inherent protector safeguards against overloads, the breaker is free to be sized significantly higher (up to 225% of RLA) solely to ride through the momentary 80 to 120-amp starting inrush current (LRA) without nuisance tripping.

HVAC Nameplate Data & Sizing Matrix

The following reference matrix illustrates standard engineering parameters for typical single-phase 208/230 V residential condensing units:

Nominal Tonnage Compressor RLA (A) Condenser Fan FLA (A) Compressor LRA (A) Calculated MCA (A) Minimum 75°C Copper Wire Size Calculated MOCPD (A) Standard MOCPD Nameplate Rating

  • 1.5 Ton 9.0 0.8 48.0 12.1 A 14 AWG (15 A) 21.1 A 20 A
  • 2.0 Ton 12.0 1.0 62.0 16.0 A 12 AWG (20 A) 28.0 A 25 A (or 30 A)
  • 2.5 Ton 14.1 1.1 73.0 18.7 A 12 AWG (20 A) 32.8 A 30 A
  • 3.0 Ton 16.4 1.3 88.0 21.8 A 12 AWG (25 A @ 75°C) 38.2 A 35 A
  • 3.5 Ton 18.2 1.5 96.0 24.3 A 12 AWG (25 A @ 75°C) 42.5 A 40 A
  • 4.0 Ton 21.8 1.8 117.0 29.1 A 10 AWG (35 A @ 75°C) 50.9 A 50 A
  • 5.0 Ton 26.4 2.4 134.0 35.4 A 8 AWG (50 A @ 75°C) 61.8 A 60 A

Loading diagram... NEC Article 440 Branch Circuit Sizing & Protection Workflow