11.2 Device Standards 1013, 1015, 1020, 1056

ASSE 5110 Backflow Prevention Assembly Tester Study Guide Exam

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Exam Overview

1.1 About ASSE 5110 and the Series 5000 Program 1.2 Eligibility, 40-Hour Course, Written & Practical Format 1.3 Validity, Recertification, and Retake Rules

2 Hydraulics Fundamentals

2.1 Pressure, Head, and Atmospheric Reference 2.2 Static vs Flowing Conditions for Testers 2.3 PSID and How Differentials Are Measured

3 Backpressure, Backsiphonage & Differentials

3.1 Backpressure: Causes and Field Examples 3.2 Backsiphonage: Causes and Field Examples 3.3 How Differentials Drive Relief and Air-Inlet Action 3.4 When and Why Backflow Occurs in Distribution Systems

4 Cross-Connection Recognition

4.1 Health Hazard vs Non-Health Hazard Classification 4.2 Common Cross-Connections and Correct Protection 4.3 Containment vs Isolation Strategies

5 RP and DC Assemblies

5.1 RP (ASSE 1013) Components and Operation 5.2 RP Relief Valve Theory and Zone Protection 5.3 DC (ASSE 1015) Components and Operation 5.4 When to Use RP vs DC

6 PVB, SVB & Detector Assemblies

6.1 PVB (ASSE 1020) Components and Operation 6.2 SVB (ASSE 1056) Components and Operation 6.3 RPDA and DCDA Detector Assemblies (1047/1048) 6.4 Non-Testable Devices Testers Must Recognize

7 Test Equipment & Calibration

7.1 Three-Valve Differential Pressure Gauges 7.2 Five-Valve Gauges and Hose Discipline 7.3 Bleeding, Hookup Sequence, and Air Elimination 7.4 Calibration, Accuracy, and Field Verification

8 RP & DC Field Test Procedures

8.1 RP Field Test Procedure (USC 10th Edition) 8.2 RP Pass/Fail Criteria and Troubleshooting 8.3 DC Field Test Procedure 8.4 DC Failures and Common Causes

9 PVB/SVB Tests & Practical Sequence

9.1 PVB Field Test Procedure 9.2 SVB Field Test Procedure 9.3 Comparing the Four Practical-Exam Assemblies 9.4 Hands-On Sequence Under Practical Exam Pressure

10 Installation Requirements & Inspection

10.1 Orientation, Clearance, and Elevation Rules 10.2 RP Drainage, Air Gap, and Flood Protection 10.3 Freeze Protection and Thermal Expansion 10.4 Pre-Test Visual Inspection

11 Codes, Standards & Manuals

11.1 ASSE Series 5000 and 5110 Professional Qualifications 11.2 Device Standards 1013, 1015, 1020, 1056 11.3 USC Manual of Cross-Connection Control 10th Edition 11.4 AWWA M14, EPA 816-R-03-002, and SDWA Framework

12 Reporting, Boundaries & Exam Prep

12.1 Field Test Reports and Pass/Fail Language 12.2 Purveyor Notification and Record Retention 12.3 Tester vs Repairer vs Surveyor Boundaries 12.4 Written Exam Strategy, Study Plan, and Next Credentials

11.2 Device Standards 1013, 1015, 1020, 1056

Key Takeaways Explain This Topic AI

Product performance standards (ASSE 10xx) define how assemblies must be designed and perform; personnel standards (ASSE 51xx) define who may test them

Memorize: 1013 = RP, 1015 = DC, 1020 = PVB, 1056 = SVB, 1047 = RPDA, 1048 = DCDA

Also recognize 1001 AVB, 1011/1052 hose-bibb vacuum breakers, and 1024 dual check as common non-testable or limited devices

The four practical-exam assemblies map to 1013, 1015, 1020, and 1056—all testable with shutoffs and test cocks

Exam distractors deliberately swap numbers (for example calling 1015 the RP or 1020 the SVB)—use a fixed number→assembly table

Last updated: August 2026

11.2 Device Standards 1013, 1015, 1020, 1056

Quick Answer: ASSE product (device) standards specify how backflow assemblies and devices must perform. The core testable set for ASSE 5110 is 1013 RP , 1015 DC , 1020 PVB , and 1056 SVB . Detector assemblies are 1047 RPDA and 1048 DCDA . Non-testable or limited devices you must still recognize include 1001 AVB , 1011/1052 hose-bibb vacuum breakers, and 1024 dual check. Never confuse these 10xx numbers with 5110 personnel certification.

Product standards vs personnel qualifications

Two parallel libraries exist under the ASSE brand:

Library Number family Answers the question… Example

Product / device performance 10xx How must this assembly or device be built and perform? 1013 = reduced pressure principle assembly

Professional qualifications 51xx Who is qualified to test, repair, survey, or administer? 5110 = assembly tester

A manufacturer lists an assembly to ASSE 1013 after design and laboratory evaluation against that product standard. A person becomes ASSE 5110 after training and examination against Series 5000 competencies. You may field-test a 1013-listed RP because you hold 5110 (and local acceptance)—not because your name is stamped on the product standard.

On the written exam, any option that says “ASSE 1013 certifies testers” or “ASSE 5110 is the RP device standard” is wrong by category, not by nuance.

Core memorization table (write this until automatic)

ASSE number Assembly / device Typical short name Field-testable with gauge?

  • 1013 Reduced pressure principle assembly RP / RPZ Yes
  • 1015 Double check valve assembly DC / DCVA Yes
  • 1020 Pressure vacuum breaker assembly PVB Yes
  • 1056 Spill-resistant vacuum breaker assembly SVB / SRVB Yes
  • 1047 Reduced pressure detector assembly RPDA Yes (main + bypass line methods per procedure)
  • 1048 Double check detector assembly DCDA Yes (main + bypass line methods per procedure)
  • 1001 Atmospheric vacuum breaker AVB No (no test cocks/shutoffs as a complete assembly test)
  • 1011 Hose connection vacuum breaker HCVB (hose bibb) No (device-level; not a 5110 practical assembly)
  • 1052 Hose connection backflow preventer Hose-bibb type device family No (not the four practical assemblies)
  • 1024 Dual check valve Dual check No (non-testable dual check; not DC 1015)

Practical exam focus: continuous testing of 1013, 1015, 1020, and 1056 . Detector assemblies and non-testable devices appear more often as written identification and application items.

  • Why each number exists (performance idea, not full design manual)
  • 1013 — Reduced pressure principle assembly (RP)

An RP provides high-hazard protection against backpressure and backsiphonage using two independently acting checks and a hydraulically dependent relief valve that maintains a zone at a lower pressure than supply. Product standard 1013 frames laboratory performance for that architecture. In the field you apply recognized test criteria (for example USC 10th: relief opening, check #1 strength relative to relief, check #2 tightness)—those numeric field criteria live in the procedure manual , while the product standard is what the listed hardware was built to meet.

1015 — Double check valve assembly (DC)

A DC uses two independently acting checks without an intermediate relief valve. It is not the default choice for high-hazard continuous protection where an RP is required. Product standard 1015 defines DC performance. Field testing confirms both checks hold to procedure criteria (commonly ≥ 1.0 psid tight under USC-style methods). Exam items love swapping 1015 with 1013 when the stem mentions “relief valve” or “zone of reduced pressure.”

1020 — Pressure vacuum breaker (PVB)

A PVB protects against backsiphonage (not continuous backpressure) with a check and a loaded air inlet that opens to atmosphere when supply pressure drops. Product standard 1020 is the PVB listing basis. Field tests address air-inlet opening and check tightness under a recognized procedure.

1056 — Spill-resistant vacuum breaker (SVB)

An SVB is the spill-resistant cousin of the PVB family—designed to reduce spillage while still providing atmospheric air-inlet protection appropriate to its listing and installation rules. Product standard 1056 is the number to lock to SVB . Classic distractor: calling the SVB 1020 or the PVB 1056 . Orientation, elevation, and backpressure limitations still matter; the product number does not cancel installation rules.

1047 and 1048 — Detector assemblies

Number Detector type Typical use context

1047 RPDA — reduced pressure detector assembly Fire lines needing RP-level protection plus metering of unauthorized use

1048 DCDA — double check detector assembly Fire lines where DC-level protection is accepted plus detection metering

Detector assemblies combine mainline protection with a bypass path and meter so low flows (often unauthorized domestic takeoffs) register. Testers must recognize that detector testing involves main and bypass elements per the procedure—not a single “ignore the meter” check. Do not invent that 1047 is a non-testable AVB.

Non-testable and limited devices you still must name

The 5110 tester’s world is centered on testable assemblies with shutoff valves and test cocks. Programs still require you to recognize devices that are not annually gauge-tested the same way:

1001 AVB — atmospheric vacuum breaker; no field test cocks like an RP/DC/PVB assembly; correct application is about installation height, no continuous pressure, and no downstream shutoffs (per code/product rules).

1011 / 1052 hose-connection devices — protect hose outlets; replaceable devices, not the four practical assemblies.

1024 dual check — non-testable dual check (often residential or appliance isolation). Not the same as 1015 double check assembly .

If a question shows “dual check without test cocks” and offers 1015, reject it. 1015 implies a testable assembly configuration.

How listings, marks, and local approval interact

A device standard number on a data plate is not a blank check for every installation:

Listed to the correct standard for the intended protection (for example RP for the hazard that requires RP).

Approved by the local purveyor / AHJ — many utilities maintain approved-assembly lists by manufacturer and model.

Installed per manufacturer instructions and code — orientation, elevation, clearances, freeze protection, RP drainage.

Tested by a qualified tester using a recognized procedure and a calibrated gauge .

  • Failing any layer can take an assembly out of compliance even if the casting still says “ASSE 1013.”
  • Drill patterns for number-swap distractors
  • Stem clue Correct number Common wrong option
  • Relief valve + zone of reduced pressure 1013 1015, 1020
  • Two checks, no relief, testable assembly 1015 1024, 1013
  • Air inlet + check, backsiphonage, not SVB 1020 1056, 1001
  • Spill-resistant vacuum breaker 1056 1020, 1011
  • Fire line detector with RP main 1047 1048, 1013 alone
  • Fire line detector with DC main 1048 1047, 1015 alone
  • Atmospheric vacuum breaker (non-testable) 1001 1020
  • Non-testable dual check 1024 1015
  • Person who tests assemblies 5110 1013
  • Study method that survives exam pressure

Do not memorize a paragraph. Memorize the table columns : number → name → testable yes/no → one distinguishing feature (relief, dual checks only, air inlet, detector meter, atmospheric only). Say them aloud in both directions: “1013 is RP” and “RP is 1013.” Then practice stems that bury the assembly type in a scenario (“high hazard chemical feed with potential backpressure”) and force you to choose the product standard that matches the required assembly type—not the personnel credential.

When Chapter 11.3 discusses USC 10th criteria, those numbers (2.0 psid relief, 5.0 psid check #1, and so on) are field-test acceptance criteria , not alternative names for the product standards. Keep shelves separate: 10xx = product , 51xx = people , manual criteria = how you pass/fail a test .