Study guide
2.3 Joining Methods: Permitted and Prohibited Joints
ASSE 6010 Medical Gas Systems Installer Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: The Credential, Codes & Medical Gas Fundamentals
1.1 The ASSE 6010 Credential: Eligibility, Exam Format & Recertification 1.2 Codes, Referenced Standards & the Medical Gas Team 1.3 Medical Gases, Hazards & Permitted Uses 1.4 Risk Categories & Category 1, 2, and 3 Piped Systems 1.5 Key NFPA 99 Definitions & Terminology
2 Chapter 2: Piping Materials, Oxygen Cleanliness & Joining Methods
2.1 Tube Specifications for Medical Gas and Vacuum Piping 2.2 Oxygen-Clean Materials: Delivery, Handling & Recleaning 2.3 Joining Methods: Permitted and Prohibited Joints
3 Chapter 3: Brazing Medical Gas Piping
3.1 Joint Preparation, Fittings, Filler Metals & Flux 3.2 Nitrogen Purge: Setup, Control & Final Tie-In Exception 3.3 Heating, Filling & Inspecting Brazed Joints 3.4 Brazing Procedure & Brazer Qualification, Records and Continuity
4 Chapter 4: Installing the Distribution Piping
4.1 Pipe Sizing, Protection & Permitted Locations 4.2 Supports, Buried Piping, Flexible Connectors & System Interconnections
5 Chapter 5: Valves, Station Outlets, Alarms & Labeling
5.1 Valve Requirements: Source, Main Line, Riser, Service & In-Line Valves 5.2 Zone Valves & Zone Valve Box Assemblies 5.3 Station Outlets & Inlets, Manufactured Assemblies & Pressure Indicators 5.4 Warning Systems: Master, Area & Local Alarms 5.5 Labeling, Identification & Color Codes
6 Chapter 6: Central Supply Systems & Source Equipment
6.1 Central Supply Locations, Cylinder Manifolds, Line Controls & Relief Valves 6.2 Cryogenic Supplies, Reserves, EOSC, IBER & Oxygen Concentrators 6.3 Medical Air Compressor Systems 6.4 Medical-Surgical Vacuum, WAGD & Medical Support Gas Sources
7 Chapter 7: Testing, Verification & Documentation
7.1 Installer Tests I: Blowdown, Initial Pressure, Cross-Connection & Piping Purge 7.2 Installer Tests II: 24-Hour Standing Pressure & Vacuum Tests, Inspection & Witnessing 7.3 System Verification: The Verifier's Test Sequence 7.4 Tie-Ins, Breached Systems, Operational Flow & Gas Concentration Tests 7.5 Documentation, Records & System Turnover
2.3 Joining Methods: Permitted and Prohibited Joints
Key Takeaways Explain This Topic AI
Changes in direction in copper or stainless tube must use brazing, welding, memory metal fittings, axially swaged fittings, or threaded joints where threads are permitted; NFPA 99-2024 also recognizes CMT systems.
Threaded joints are limited to pressure and vacuum indicators, alarm devices, gas-specific demand check fittings, and source equipment on the source side of the source valve.
Memory metal and axially swaged fittings must be rated for at least 300 psi and 1000°F (538°C) and must be installed by qualified technicians per the manufacturer's instructions.
Flared and compression connections, other straight-thread connections including unions, pipe-crimp stops, and push-fit fittings are prohibited throughout medical gas and vacuum systems.
Only vacuum and WAGD copper piping may use mechanically formed, drilled, and extruded tee-branch connections, and those branches must then be brazed.
Last updated: October 2026
The Permitted Joining Methods
For positive-pressure patient gas systems, medical support gas systems, and vacuum systems built from hard-drawn seamless copper or stainless steel tube, NFPA 99 requires every turn, offset, and change in direction to be made with fittings or techniques that suit one of these methods:
Method Key NFPA 99 conditions
Brazing Socket joints with ASME B16.22 or B16.50 fittings, AWS A5.8 filler melting above 1000°F, continuous nitrogen NF purge, qualified procedure and brazers (Chapter 3)
Welding Gas tungsten arc welding (GTAW) autogenous orbital process; stainless tube may be welded by MIG, TIG, or other suitable techniques
Memory metal fittings Rated at least 1000°F (538°C) and 300 psi (2068 kPa); installed by qualified technicians per the manufacturer's instructions
Axially swaged (elastic preload) fittings Metal-to-metal seals, suitable for 300 psig, withstand 1000°F, permanent and nonseparable; installed by qualified technicians per the manufacturer's instructions
CMT systems NFPA 99-2024 recognizes corrugated medical tubing; turns are made by bending within the manufacturer's minimum bend radius or with permitted fittings; installed by ASSE 6010-qualified installers per the CMT manufacturer's instructions
Threaded Limited locations only (see below)
Why 1000°F? NFPA 99 requires brazing alloys to melt above 1000°F (538°C) so the piping keeps its integrity if a fire exposes it. Mechanical fittings must meet the same temperature to be treated as equivalent. The same thinking explains a catch-all clause. Listed or approved metallic gas tube fittings are permitted if, once made up, they form a permanent joint with the mechanical, thermal, and sealing integrity of a brazed joint.
Welding details worth memorizing
The GTAW autogenous orbital procedure and the welder qualification are both qualified to ASME BPVC Section IX . Welder qualification includes a bend test and a tensile test on each tube diameter .
Each welder qualifies to a welding procedure specification (WPS) for each tube diameter .
Orbital welds are purged during welding with a commercial mixture of 75% helium (plus or minus 5%) and 25% argon (plus or minus 5%) . The shield gas is the same mixture.
Test coupons are welded and inspected on the ID and OD by a qualified quality control inspector:
- at the start of work, every 4 hours after that, and at the end of the work period;
- after the machine sits idle for more than 30 minutes ;
whenever the operator, weld head, welding power supply, or gas source changes.
When the autogenous orbital process is used, joints are purged with inert gas inside and outside per the qualified welding procedure.
Threaded Connections: Only Where the Code Lists Them
Threaded fittings are limited to:
- Connections for pressure and vacuum indicators
- Alarm devices
- Gas-specific demand check fittings
- Source equipment on the source side of the source valve
Threads must be tapered pipe threads per ASME B1.20.1 . Joints must be made up with PTFE tape or another oxygen-service thread sealant , applied to the male threads only , and the sealant must not enter the pipe.
Special Fittings
Dielectric fittings are permitted only where the manufacturer of special medical equipment requires electrical isolation of the equipment from the distribution piping. They must be brass or copper with an approved dielectric, may be a union, and must be clean for oxygen when used on medical gases or medical support gases.
Extruded tee branches: vacuum and WAGD systems made of copper tubing may use mechanically formed, drilled, and extruded tee-branch connections formed per the tool manufacturer's instructions. The branch connection is then brazed . This exception does not exist for positive-pressure gas piping.
Metallic flexible joints for expansion, seismic protection, thermal expansion, or vibration control are covered in Section 4.2 of this guide.
Prohibited Joints
NFPA 99 prohibits all of the following throughout medical gas and vacuum distribution systems :
Prohibited joint Typical temptation on the job
Flared and compression-type connections , including at station outlets, inlets, alarm devices, and other components Using a compression nut to hook up an alarm sensor
Other straight-threaded connections, including unions Adding a union so a piece of equipment can be removed later
Pipe-crimping tools used to permanently stop flow Crimping and abandoning a dead leg instead of cutting and capping it
Push-fit fittings , removable or nonremovable Using a quick-assembly push connector for a repair
Tip
A common exam pattern describes a convenient shortcut, such as a union for future service or a crimp to retire a branch, and asks whether it is allowed. If it is not one of the listed permitted methods, it is prohibited. To abandon a line, cut it and close it with a brazed cap. For future connections, NFPA 99 requires downstream piping closed with a brazed cap that leaves tubing allowance for cutting and rebrazing.
Choosing a Method in Practice
New construction: brazing with BCuP filler under a nitrogen purge remains the default for copper.
Tie-ins near occupied patient areas: listed memory metal or axially swaged fittings eliminate open flame. They must meet the 300 psi and 1000°F ratings and be installed by technicians trained in that product.
Stainless systems: welding by qualified welders to ASME Section IX.
CMT: only where the adopted code edition and the design allow it, installed by ASSE 6010-qualified installers per the manufacturer's instructions.
Whatever the method, the finished joint still goes through the same installer pressure tests, standing tests, and verification. A non-brazed joint does not get a lighter test regime.