5.2 Zone Valves & Zone Valve Box Assemblies

ASSE 6010 Medical Gas Systems Installer Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: The Credential, Codes & Medical Gas Fundamentals

1.1 The ASSE 6010 Credential: Eligibility, Exam Format & Recertification 1.2 Codes, Referenced Standards & the Medical Gas Team 1.3 Medical Gases, Hazards & Permitted Uses 1.4 Risk Categories & Category 1, 2, and 3 Piped Systems 1.5 Key NFPA 99 Definitions & Terminology

2 Chapter 2: Piping Materials, Oxygen Cleanliness & Joining Methods

2.1 Tube Specifications for Medical Gas and Vacuum Piping 2.2 Oxygen-Clean Materials: Delivery, Handling & Recleaning 2.3 Joining Methods: Permitted and Prohibited Joints

3 Chapter 3: Brazing Medical Gas Piping

3.1 Joint Preparation, Fittings, Filler Metals & Flux 3.2 Nitrogen Purge: Setup, Control & Final Tie-In Exception 3.3 Heating, Filling & Inspecting Brazed Joints 3.4 Brazing Procedure & Brazer Qualification, Records and Continuity

4 Chapter 4: Installing the Distribution Piping

4.1 Pipe Sizing, Protection & Permitted Locations 4.2 Supports, Buried Piping, Flexible Connectors & System Interconnections

5 Chapter 5: Valves, Station Outlets, Alarms & Labeling

5.1 Valve Requirements: Source, Main Line, Riser, Service & In-Line Valves 5.2 Zone Valves & Zone Valve Box Assemblies 5.3 Station Outlets & Inlets, Manufactured Assemblies & Pressure Indicators 5.4 Warning Systems: Master, Area & Local Alarms 5.5 Labeling, Identification & Color Codes

6 Chapter 6: Central Supply Systems & Source Equipment

6.1 Central Supply Locations, Cylinder Manifolds, Line Controls & Relief Valves 6.2 Cryogenic Supplies, Reserves, EOSC, IBER & Oxygen Concentrators 6.3 Medical Air Compressor Systems 6.4 Medical-Surgical Vacuum, WAGD & Medical Support Gas Sources

7 Chapter 7: Testing, Verification & Documentation

7.1 Installer Tests I: Blowdown, Initial Pressure, Cross-Connection & Piping Purge 7.2 Installer Tests II: 24-Hour Standing Pressure & Vacuum Tests, Inspection & Witnessing 7.3 System Verification: The Verifier's Test Sequence 7.4 Tie-Ins, Breached Systems, Operational Flow & Gas Concentration Tests 7.5 Documentation, Records & System Turnover

5.2 Zone Valves & Zone Valve Box Assemblies

Key Takeaways Explain This Topic AI

All station outlets and inlets must be supplied through a zone valve that has a wall between it and the outlets it controls, is operable from a standing position, and is visible and accessible at all times.

A zone valve may not be hidden behind normally open or closed doors, placed in the room it controls, or placed in rooms or closets that can be closed or locked.

Each Category 1 space needs a zone valve in each gas and vacuum line; in anesthetizing locations the zone valves go immediately outside each room.

Piping on the patient side of a zone valve may serve outlets only on the same story, and closing one zone must not affect any other zone.

Zone valves are installed in valve boxes with removable covers, with a pressure or vacuum indicator on the outlet side of each zone valve.

Last updated: October 2026

The Purpose of a Zone Valve

A zone valve controls the gas or vacuum to one area. In a fire, a leak, or an outlet failure, clinical staff, not just the maintenance department, may need to shut it off within seconds. Every location rule below exists so the valve can be found, reached, and operated by the right person at the right moment.

Placement Rules for Every Zone Valve

All station outlets and inlets must be supplied through a zone valve , placed as follows:

Must Must not

Have a wall between the valve and the outlets it controls Be installed in the room with the outlets it controls

Be readily operable from a standing position Be hidden from plain view , such as behind a normally open or normally closed door

Be visible and accessible at all times Be installed in rooms, areas, or closets that can be closed or locked

These rules work together. The wall keeps a person who is closing the valve out of the fire or gas release, while a visible, unlocked, standing-height valve means nobody needs a key or a ladder.

Category 1 Spaces and Anesthetizing Locations

A zone valve in each medical gas and vacuum line is required for each Category 1 space :

In patient care spaces that are not anesthetizing locations , the zone valves go immediately outside the area or zone being controlled.

In anesthetizing locations , they go immediately outside each room .

A suite of six operating rooms therefore gets a zone valve box outside each OR, not one box for the whole suite. An ICU may be zoned as an area, with its zone valve box immediately outside the unit, typically at the entrance staff use.

Arrangement on the Patient Side

Piping on the patient side of a zone valve must be arranged so that:

Shutting off one zone does not affect the supply to any other zone or to the rest of the system.

The zone serves outlets and inlets only on the same story .

All gas delivery columns, hose reels, ceiling tracks, control panels, pendants, booms , and other special installations are on the patient side of the zone valve .

Zone Valve Box Assemblies

Requirement Detail

Enclosure Zone valves go in valve boxes with removable covers large enough to allow manual operation of the valves

Securing in special areas In areas such as psychiatric or pediatric units , zone valves may be secured with AHJ approval to prevent inappropriate access

Flammable gases Valves for nonflammable medical gases may not share a zone valve box with valves for flammable gases

Indicator A pressure or vacuum indicator goes on the station outlet/inlet side of each zone valve

Security exemption Zone valve box valves are the one group exempt from the general valve-securing rule (they must stay operable by staff)

Labeling: zone valve box assemblies are labeled with the rooms, areas, or spaces they control, for example "ZONE VALVES FOR THE (GAS) SERVING (ROOMS)." The label must be visible from outside through the cover or replicated on the outside , but never fixed to the removable cover . A label on the cover can be lost or put back on the wrong box after service.

Alarm Sensors Near Zone Valves

Area alarm sensors (Section 5.4) are installed relative to zone valve boxes:

For Category 1 spaces other than anesthetizing locations , sensors go on the patient or use side of each zone valve box assembly.

For anesthetizing locations where moderate sedation, deep sedation, or general anesthesia is given, sensors may go on either the source side or the patient side of each room's zone valve box.

Installation and Testing Notes

Zone valves arrive with copper tube extensions and purge ports on both sides. Braze to the extensions under nitrogen purge, following the valve manufacturer's instructions on heat and valve position.

During the verifier's valve test , each zone valve is closed to confirm it controls only the outlets listed on its label. A zone that also shuts off an outlet in the next room is a piping or labeling error that must be fixed before the system goes into service.

Keep the area in front of zone valve boxes clear. Equipment parked in front of a box makes it "not accessible at all times."

Scenario Check

A design places the zone valve box for an ICU inside the unit's clean supply room, which has a self-closing, keypad-locked door. This fails twice: the box is in a room that can be locked, and it is not visible at all times. Moving it to the corridor wall just outside the unit entrance, at standing height, with nothing obstructing it, meets the rules.