7.4 Discrimination & Selectivity

Queensland Electrical Licence Capstone Assessment Exam

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Capstone Overview

1.1 Current Capstone Exam Facts 1.2 Capstone Written & Practical Format 1.3 Queensland ESO Licence Pathway

2 AS/NZS 3000 Fundamentals

2.1 Scope & Fundamental Principles 2.2 Nominal Voltages & System Classifications 2.3 Conductor Identification & Colour Coding 2.4 Protection Against Electric Shock

3 Isolation, Switching & Special Locations

3.1 Isolation & Switching 3.2 Special Locations (Bathrooms, Pools & More) 3.3 Installation Defects & Rectification

4 Cable Selection Basics (AS/NZS 3008)

4.1 Current-Carrying Capacity & Installation Methods 4.2 Reference Temperatures & Insulation Types 4.3 Grouping & Thermal Derating Factors 4.4 Cable Short-Circuit Capacity

5 Voltage Drop & Selection Order

5.1 Voltage Drop (mV/A·m) & the 5% Limit 5.2 Order of Cable-Selection Checks 5.3 Worked Cable Selection Examples

6 Maximum Demand Calculations

6.1 Diversity & Appendix C Overview 6.2 Domestic Table C1 Demand Factors 6.3 Commercial Demand & Mains/Main-Switch Sizing

7 Circuit Protection Coordination

7.1 Overload & Short-Circuit Protection 7.2 The Ib ≤ In ≤ Iz Coordination Rule 7.3 Circuit-Breaker Curves & Breaking Capacity 7.4 Discrimination & Selectivity

8 RCDs, Division of Circuits & SELV/PELV

8.1 RCD Types & 30 mA Additional Protection 8.2 Division of Circuits 8.3 SELV & PELV Systems

9 Earthing & the MEN System

9.1 MEN System Principles & Fault Return Path 9.2 The MEN Link at the Main Switchboard 9.3 Main Earthing Conductor Sizing (Table 5.1) 9.4 Equipotential Bonding

10 Electrodes, Adiabatic & Prospective Fault Current

10.1 Earth Electrodes & Arrangements 10.2 The Adiabatic Equation for Protective Conductors 10.3 Prospective Fault Current

11 Earth-Fault-Loop Impedance & Disconnection

11.1 Earth-Fault-Loop Impedance (Zs = Ze + R1 + R2) 11.2 Disconnection Times (0.4 s & 5 s) 11.3 Breaking Capacity Coordination with PFC

12 Consumer Mains & Submains

12.1 Point of Supply Definitions 12.2 Consumer Mains Sizing & Installation 12.3 Submains Definitions & Sizing 12.4 Neutral & Earth Separation Downstream

13 QLD Electrical Safety Legislation

13.1 Electrical Safety Act 2002 & the ESO 13.2 Licensing Classes & Worker Duties 13.3 Certificates of Testing & Compliance 13.4 Construction Sites (AS/NZS 3012)

14 Safe Work & Critical Theory

14.1 Safe Isolation & Lock-Out/Tag-Out 14.2 Energised Electrical Work Controls 14.3 Effects of Electric Current (Critical EPC Theory)

15 Testing & Verification

15.1 AS/NZS 3000 Section 8 Test Sequence 15.2 Earth Continuity & Polarity 15.3 Insulation Resistance (1 MΩ at 500 V DC) 15.4 RCD Testing & Loop-Impedance Verification 15.5 AS/NZS 3017 Verification, Reporting & Documentation

16 DC, AC & Three-Phase Circuit Theory

16.1 DC Circuits, Ohm’s Law & Power 16.2 AC Generation, RMS Values & Phase 16.3 Three-Phase Systems & Phase Sequence

17 Motors, Transformers & Switchboards

17.1 Motor Selection, Enclosures & Starting Methods 17.2 Motor Overload & Short-Circuit Protection 17.3 Transformer Key Safety Issues 17.4 Switchboard Location, Arrangement & Form Types

18 Wiring Systems, Aerials & Hazardous Areas

18.1 Cable Installation & Termination Requirements 18.2 Final Subcircuits Into Switchboards 18.3 Aerial Conductors & Underground Wiring 18.4 Hazardous Areas & Classified Zones

19 Drawings, Commissioning & Fault Rectification

19.1 Reading, Sketching & Interpreting Electrical Diagrams 19.2 Commissioning & Decommissioning 19.3 Diagnosing & Rectifying Faults

20 Workplace Safety, Rescue & High Voltage

20.1 Statutory WHS Duties, Supervision & Duty of Care 20.2 Asbestos, Silica & Hazardous Gases 20.3 Workplace Safety Checks & Hazard Control 20.4 Rescue From Live Electrical Conductors 20.5 Electric Shock First Aid & CPR 20.6 High Voltage Dangers & Distribution Systems

7.4 Discrimination & Selectivity

Key Takeaways Explain This Topic AI

Discrimination (selectivity) means only the protective device nearest the fault opens, leaving upstream devices closed so healthy circuits stay energised

Current discrimination and time discrimination are the two classic strategies; device curves and ratings must be compared, not assumed

Total discrimination aims to hold for all fault levels up to a stated limit; partial discrimination holds only up to a lower fault current

Backup/cascade arrangements that force the upstream device to share clearing can improve breaking capacity at the expense of selectivity

A downstream fault that also trips the main breaker is a selectivity failure — a frequent the capstone scenario question

Last updated: August 2026

Discrimination & Selectivity

Quick Answer: Discrimination (also called selectivity ) means that for a fault on a downstream circuit, only the nearest protective device opens . Upstream breakers or fuses remain closed so the rest of the installation stays on. Achieved by coordinating ratings and time–current curves (and manufacturer selectivity tables). Backup protection that deliberately involves the upstream device can defeat selectivity.

Why Selectivity Matters on Real Jobs

Imagine a Queensland commercial board: main MCCB feeding several subcircuits, each with an MCB. A nail through a cable on one lighting circuit should trip that MCB. If the main MCCB also opens, every tenant loses power, refrigerated stock warms, and fault-finding becomes theatre. That outcome is a loss of discrimination .

AS/NZS 3000 and good practice encourage arrangements where protective devices are selective so that faults are cleared as close to the defect as practicable. The capstone unit uses this language in scenario questions: identify which device should operate, and why both operating is undesirable.

  • Term Meaning
  • Downstream device Closer to the load / fault
  • Upstream device Closer to the supply / main switch
  • Discrimination / selectivity Only the downstream device clears for faults in its zone
  • Loss of discrimination Upstream also opens (or opens instead) for a downstream-zone fault
  • Current Discrimination

Current discrimination uses different continuous ratings and curve shapes so that, for fault currents in a given range, the downstream device’s operating characteristic lies to the left of (operates before) the upstream device.

Simple fuse example taught in trade courses: a minor downstream overload melts a small fuse while a much larger upstream fuse’s element barely heats. For high fault currents, both fuse I²t values must still be checked — at extreme levels, discrimination can fail if the upstream fuse’s pre-arcing energy is exceeded.

Breaker example: a 20 A Type C final-circuit MCB downstream of a 63 A MCCB with a suitably set short-time delay may discriminate for many fault levels if manufacturer tables say so. Equal ratings stacked without study often do not discriminate on heavy faults — both magnetic trips may race.

Strategy How it works Limitation

Current discrimination Downstream device more sensitive / lower rating clears first for moderate faults May fail at very high fault currents where both devices enter instantaneous region

Time discrimination Upstream device deliberately delayed (short-time delay on MCCB) so downstream clears first Increases fault energy upstream must withstand; settings must respect cable withstand

Energy / I²t selectivity Compare let-through and pre-arcing energies (especially fuse–fuse) Requires manufacturer data

Time Discrimination

Time discrimination introduces intentional delay on the upstream device’s short-circuit response (common on MCCBs with adjustable short-time delay). The downstream MCB’s instantaneous trip clears first; the upstream device only opens if the fault persists (for example if the downstream device fails or the fault is on the bus between them).

Rules of thumb for assessment reasoning:

Delay improves selectivity but increases the I²t the installation must withstand while waiting.

Cable short-circuit withstand (Chapter 4) and device ratings must still survive that delay.

Instantaneous trips on both devices with no delay and similar magnetic thresholds often collide on bolted faults.

Total Versus Partial Discrimination

Manufacturer literature and exam wording distinguish:

Total discrimination (full selectivity): for all fault currents up to a stated maximum (often up to the downstream breaking capacity or a published limit), only the downstream device operates.

Partial discrimination: selectivity holds only up to a certain fault current; above that level, both devices may operate.

A design that is “selective for overloads but not for bolted faults at the board” is partial . That may still be acceptable if documented and risk-assessed, but candidates must not claim total discrimination without evidence.

Discrimination Versus Backup Protection

Section 7.3 introduced backup / cascade protection: an upstream device helps the downstream device clear a fault beyond the downstream Icu. That help often means the upstream device also operates or shares energy limitation. Result:

Breaking capacity problem may be solved.

Selectivity for that high-level fault may be sacrificed .

Goal Typical tool Side effect

Selectivity Coordinated curves, ratings, delays, manufacturer selectivity tables May require higher downstream Icu or careful settings

Backup breaking capacity Proven cascade pairs Upstream may trip — loss of discrimination on heavy faults

Competent design states which goal was prioritised. Waving “the main fuse backs it up” without admitting the selectivity cost is incomplete thinking.

Series Device Themes on Final Circuits

Domestic and small commercial boards often have:

Service protection / main switch arrangement upstream.

Submain protection midstream (if any).

Final-circuit MCBs or fuses downstream.

For a fault on a final circuit, ideal sequence: final-circuit device opens only . If the fault is on the submain bus, the submain device should open while the service protection remains closed if discrimination is achieved. Map the fault location to the device zone before answering which breaker “should” trip.

Reading Selectivity Questions Under Exam Pressure

Locate the fault (final circuit, submain, main tails).

Name the device that protects that zone.

Ask whether upstream devices are meant to stay closed.

If both tripped in a scenario stem, call it loss of discrimination and suggest causes: identical instantaneous settings, inadequate rating ratio, missing time delay, or cascade behaviour.

Common Exam Traps

Believing two MCBs of the same In and same curve will always discriminate because one is “downstream.” On a bolted fault both may trip.

Confusing RCD discrimination (S-type time-delayed RCDs upstream of general 30 mA devices) with overcurrent discrimination — related idea, different technology; do not mix residual-current and overcurrent answers blindly.

Claiming total discrimination from instinct without curve or manufacturer support.

Fixing nuisance main-breaker trips by upsizing the main In without checking whether downstream devices and Iz still coordinate — you may mask a selectivity or earth-fault problem.

Pulling Chapter 7 Together

Check Question

Overload vs fault Which physical event? Thermal or fast clear?

Ib ≤ In ≤ Iz Continuous coordination after derating?

Curve B/C/D Inrush versus magnetic sensitivity?

Icu/Ics Can it interrupt prospective fault current (or validated backup)?

Discrimination Will only the nearest device open?

A capstone-ready answer names the check you are performing. “Put in a bigger breaker” without walking this table is how candidates fail coordination items.

Closing Study Habits for Queensland Licence Work

Sketch the board hierarchy on every scenario question.

Write Ib, In, Iz beside every cable decision.

State curve type when motors or transformers appear.

Compare fault level to Icu before celebrating a neat CCC result.

Say “selectivity” aloud when describing which device should trip.

Master those habits and Chapter 7 stops being a list of symbols — it becomes the way you defend a safe Australian installation under AS/NZS 3000.

Loading diagram... Selectivity: downstream clears, upstream stays closed