8.3 Capacitors (Start & Run), Potential Relays & Motor Starting Circuits
Arizona HVAC Contractor License ROC R-39R/C-39/CR-39
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Arizona ROC Licensing & Legal Framework
1.1 Arizona ROC Authority & License Classifications 1.2 Application Requirements, Qualifying Party Duties & Experience Standards 1.3 Contractor Bonds, Financial Requirements & Residential Recovery Fund 1.4 Arizona Prompt Pay Act, Contracting Requirements & Mechanic's Liens 1.5 ROC Workmanship Standards, Complaint Investigation, Citations & Disciplinary Procedures
2 Chapter 2: Thermodynamics & The Vapor Compression Refrigeration Cycle
2.1 Thermodynamic Fundamentals, Heat Transfer & Pressure-Temperature Relationships 2.2 The Four Primary Cycle Components: Compressors, Condensers, Metering Devices & Evaporators 2.3 Superheat & Subcooling: Measurement, Calculation & Diagnostic Interpretation 2.4 Pressure-Enthalpy (P-h) Diagrams & System Operating Analysis 2.5 Refrigerant Characteristics, Oil Miscibility & ASHRAE Safety Classifications
3 Chapter 3: Refrigerant Management, EPA Section 608 & Environmental Compliance
3.1 EPA Clean Air Act Section 608 Regulations, Certifications & Venting Prohibitions 3.2 Recovery, Recycling & Reclaim Standards, Evacuation Levels & Deep Vacuum Procedures 3.3 Leak Detection Methods & Mandatory Repair Trigger Rates 3.4 Low-GWP Refrigerants & A2L Transition Safety Requirements 3.5 System Evacuation, Triple Evacuation Method, Vacuum Decay Testing & Moisture Removal
4 Chapter 4: Heating Systems: Gas Furnaces, Electric Heat & Combustion Safety
4.1 Fuel Gas Combustion Chemistry, Gas Burners & Orifice Sizing 4.2 Gas Furnace Components, Ignition Systems & Flame Rectification 4.3 Furnace Safety Controls & Troubleshooting Sequences 4.4 Gas Venting Categories (I-IV), Vent Sizing & Combustion Air Calculations 4.5 Electric Furnaces & Duct Heaters: Sizing, Sequencers, Thermal Cutoffs & Wiring
5 Chapter 5: Heat Pump Systems & Defrost Operation
5.1 Heat Pump Operating Principles & Reversing Valve Operation 5.2 Thermal Expansion Valves (TXVs), Electronic Expansion Valves (EEVs) & Bi-flow Metering 5.3 Defrost Systems: Time-Temperature vs. Demand Defrost Cycles & Sensor Operation 5.4 Heat Pump Balance Point Analysis, Supplemental Strip Heat Staging & Emergency Heat 5.5 Inverter-Driven Variable Capacity Systems & Desert Heat Pump Performance
6 Chapter 6: Air Distribution, Duct Design & Airflow Dynamics
6.1 Airflow Fundamentals: CFM Requirements, Velocity, Static Pressure & TESP 6.2 ACCA Manual D Duct Sizing: Equal Friction Method & Friction Rate Calculations 6.3 Duct Construction, Materials & SMACNA Support Standards 6.4 Duct Sealing (UL 181 Standards, Mastic, Tapes), Attic Insulation & Leakage Testing 6.5 Air System Balancing, Diagnostic Instruments & Grille/Register Selection
7 Chapter 7: Psychrometrics & Desert Climate HVAC Load Sizing
7.1 The Psychrometric Chart: Dry-Bulb, Wet-Bulb, Relative Humidity, Enthalpy & Dew Point 7.2 Psychrometric Air Conditioning Processes: Cooling, Heating, Humidification & Dehumidification 7.3 ACCA Manual J Residential Load Calculations: Heat Gain, Heat Loss, U-Values & SHGC 7.4 Arizona Desert Climate Design Considerations: Sensible Heat Ratios & Manual S Sizing 7.5 Evaporative Cooling Systems (Direct & Indirect Swamp Coolers): Principles & Maintenance
8 Chapter 8: HVAC Electrical Systems, Motors & Control Circuits
8.1 Electrical Fundamentals for HVAC: Ohm's Law, Power Formula & Single/Three-Phase Power 8.2 24VAC Control Circuits, Step-Down Transformers, Relays & Contactors 8.3 Capacitors (Start & Run), Potential Relays & Motor Starting Circuits 8.4 HVAC Motors: PSC, ECM & Three-Phase Motors 8.5 NEC Article 440 Compliance: MCA, MOCP & Disconnect Switch Rules
9 Chapter 9: Hydronics, Boilers, Chilled Water & Commercial Systems
9.1 Hydronic Heating Systems: Low-Pressure Hot Water & Steam Boilers 9.2 Hydronic Specialties: Air Separators, Expansion Tanks, Circulator Pumps & Zone Valves 9.3 Water Piping Systems, Sizing, Flow Rates & Relief Valves 9.4 Commercial Chilled Water Systems: Air-Cooled & Water-Cooled Chillers 9.5 Cooling Towers, Condenser Water Loops & Legionella Water Treatment
10 Chapter 10: Codes, Piping Systems, Safety & OSHA Standards
10.1 International Mechanical Code (IMC) & International Fuel Gas Code (IFGC) Compliance 10.2 Refrigerant Copper Piping: ACR Tubing, Brazing with Nitrogen Purge & Trapping 10.3 Fuel Gas Piping Installation: Materials, Sizing Tables & Pressure Testing 10.4 OSHA Safety Standards: Fall Protection, Scaffolding, Ladders & HazCom 10.5 OSHA Heat Illness Prevention for Arizona Outdoor Work, LOTO & Arc Flash Safety
8.3 Capacitors (Start & Run), Potential Relays & Motor Starting Circuits
Key Takeaways Explain This Topic AI
Capacitors store electrostatic energy and create a 90° leading phase shift in auxiliary start windings, providing the rotating magnetic stator field necessary to produce starting torque in single-phase motors.
Run capacitors are continuous-duty, oil-filled metal components (1.5–80 μ F \mu\text{F} μ F , 370–440 VAC); Start capacitors are intermittent-duty, dry electrolytic plastic components (50–600 μ F \mu\text{F} μ F , 250–330 VAC) equipped with a 15k–20k Ω \Omega Ω bleed resistor.
Under-load capacitance can be verified while operating using the formula: μ F = ( Start Winding Amperes × 2652 ) / Capacitor Measured Voltage \mu\text{F} = (\text{Start Winding Amperes} \times 2652) / \text{Capacitor Measured Voltage} μ F = ( Start Winding Amperes × 2652 ) / Capacitor Measured Voltage ; allowable tolerance is ± 6 % \pm 6\% ± 6% to ± 10 % \pm 10\% ± 10% .
Potential starting relays operate on Counter-Electromotive Force (CEMF / Back-EMF) generated across the compressor start winding, using normally closed (NC) contacts 1–2 in series with the start capacitor.
When the motor accelerates to 75%–80% of synchronous speed, start winding CEMF reaches the relay's Pick-up Voltage (300–450 VAC), energizing the high-resistance coil (terminals 2–5) and opening contacts 1–2 to drop the start capacitor out of the circuit.
Last updated: August 2026
8.3 Capacitors (Start & Run), Potential Relays & Motor Starting Circuits
Single-phase alternating current supply produces a pulsating, stationary magnetic field across a motor stator rather than a naturally rotating field. Consequently, a single-phase AC induction motor has zero net starting torque at standstill and cannot rotate on its own without auxiliary phase-splitting assistance.
To overcome this physical limitation, single-phase HVAC compressors and fan motors utilize Run Capacitors , Start Capacitors , and Potential Starting Relays . An Arizona HVAC contractor must thoroughly understand capacitor sizing, active under-load testing, and Counter-Electromotive Force (CEMF) relay dynamics to ensure reliable compressor starting under extreme desert head pressures.
1. Capacitor Operating Principles & Phase Displacement
A capacitor consists of two conductive aluminum foil plates separated by an insulating dielectric material (polypropylene film bathed in dielectric oil for run capacitors, or an etched aluminum oxide electrolytic paste for start capacitors). CAPACITOR PHASE SHIFT DYNAMICS
- RUN WINDING CURRENT (I_run) START WINDING CURRENT (I_start)
- (High Inductance -> Lags Voltage) (Series Capacitor -> Leads Voltage)
- │ ▲
- │ /
- │ / Phase Displacement
- │ / Angle: up to 90°
- │ / (Creates Rotating
- ▼ / Magnetic Field!)
- ──────────────────────────────────────────────────► VOLTAGE (V_line)
- The 90 ∘ 90^\circ 9 0 ∘ Phase Angle Shift
When an alternating voltage is applied across a capacitor, the capacitor continuously charges and discharges. The alternating current through the capacitor leads the applied voltage by 90 ∘ 90^\circ 9 0 ∘ electrical degrees ( I C I_C I C leads V C V_C V C by 90 ∘ 90^\circ 9 0 ∘ ).
The motor's Main (Run) Winding has high inductance and low resistance, causing current to lag applied line voltage by approximately 45 ∘ to 60 ∘ 45^\circ\text{ to }60^\circ 4 5 ∘ to 6 0 ∘ .
The motor's Auxiliary (Start) Winding is connected in series with a capacitor, causing start winding current to lead line voltage by 30 ∘ to 45 ∘ 30^\circ\text{ to }45^\circ 3 0 ∘ to 4 5 ∘ .
The resulting net current phase displacement between the two windings approaches 90 ∘ 90^\circ 9 0 ∘ . This simulated two-phase condition produces a true Rotating Magnetic Field (RMF) across the stator, inducing rotor currents that generate powerful starting torque.
2. Run Capacitors vs. Start Capacitors: Comparative Analysis
Run and start capacitors fulfill completely different engineering roles inside an HVAC electrical circuit and cannot be interchanged. RUN CAPACITOR VS. START CAPACITOR
- ┌───────────────────────────┬─────────────────────────────────────────────────┐
- │ SPECIFICATION / FEATURE │ RUN CAPACITOR │ START CAPACITOR │
- ├───────────────────────────┼────────────────────────┼────────────────────────┤
- │ Operating Duty Cycle │ Continuous Duty (100%) │ Intermittent (< 3 sec) │
- │ Physical Construction │ Oil-Filled Metal Can │ Dry Plastic / Bakelite │
- │ Dielectric Material │ Metallized Polyprop. │ Aluminum Oxide Paste │
- │ Capacitance Range │ 1.5 μF to 80 μF │ 50 μF to 600+ μF │
- │ Voltage Rating (VAC) │ 370 VAC or 440 VAC │ 250 VAC to 330 VAC │
- │ Internal Safety Feature │ Pressure Interrupter │ None (Vents/Explodes) │
- │ Bleed Resistor Fitted? │ No │ Yes (15kΩ - 20kΩ, 2W) │
- └───────────────────────────┴────────────────────────┴────────────────────────┘
- 1. Run Capacitors (Continuous Duty) & Dual Round/Oval Cans
Role: Remains permanently in series with the auxiliary start winding throughout the entire operating cycle of the motor. It optimizes running torque, lowers motor running current (FLA/RLA), and corrects the motor's operating Power Factor to 0.92 – 0.96 0.92\text{--}0.96 0.92 – 0.96 .
Dual Capacitor Construction: Most residential outdoor condensing units combine two independent run capacitors into a single three-terminal metal canister:
C (Common): Connected to incoming Line 2 power from the contactor.
HERM (Hermetic Compressor): Connected to the compressor Start ( S ) terminal (typically 35 μ F to 70 μ F 35\ \mu\text{F}\text{ to }70\ \mu\text{F} 35 μ F to 70 μ F ).
FAN (Condenser Fan Motor): Connected to the condenser fan Start terminal (typically 5 μ F to 10 μ F 5\ \mu\text{F}\text{ to }10\ \mu\text{F} 5 μ F to 10 μ F ).
Internal Pressure Sensitive Interrupter (PSI): If internal electrical arcing vaporizes dielectric oil, internal pressure expands the convex top dome of the metal can, physically tearing internal ribbon connections to disconnect the capacitor safely before the case ruptures.
2. Start Capacitors (Intermittent Duty) & Bleed Resistors
Role: Provides massive microfarad capacitance ( 50 μ F to 600 + μ F 50\ \mu\text{F}\text{ to }600+\ \mu\text{F} 50 μ F to 600 + μ F ) for an instant ( < 1 second < 1\text{ second} < 1 second ) during compressor startup, boosting starting torque up to 300 % to 400 % 300\%\text{ to }400\% 300% to 400% of full-load torque . Essential when starting against un-equalized TXV refrigerant pressures.
Duty Limit: Designed for a maximum of 20 starts per hour, with each start lasting no longer than 3 seconds . If a defective starting relay sticks closed, a start capacitor will overheat, boil its internal paste, and vent catastrophically within 10 to 15 seconds.
Bleed Resistor: A 15 , 000 Ω to 20 , 000 Ω 15,000\ \Omega\text{ to }20,000\ \Omega 15 , 000 Ω to 20 , 000 Ω ( 15 k– 20 k Ω 15\text{k}\text{--}20\text{k}\ \Omega 15 k – 20 k Ω ), 2-Watt carbon resistor must be soldered across the start capacitor terminals. It safely discharges residual DC voltage between cycles, preventing contact arcing and welding across potential relay contacts.
3. Capacitance Testing & The Active Under-Load Formula
Capacitors degrade over time as extreme desert heat dries out dielectric fluid or breaks down internal foil layers. Capacitance must be verified during routine maintenance and troubleshooting.
1. Bench / Passive Capacitance Test
Disconnect power, discharge capacitor terminals with a 20kΩ resistor, and isolate the terminals.
Set a digital multimeter to Capacitance ( μ F \mu\text{F} μ F ) .
Manufacturer Tolerance: A capacitor must measure within ± 6 % to ± 10 % \pm 6\%\text{ to }\pm 10\% ± 6% to ± 10% of its stamped nameplate rating (e.g., a 45 μ F ± 6 % 45\ \mu\text{F} \pm 6\% 45 μ F ± 6% capacitor must read between 42.3 μ F 42.3\ \mu\text{F} 42.3 μ F and 47.7 μ F 47.7\ \mu\text{F} 47.7 μ F ). Any reading outside this window requires immediate replacement.
2. Active Under-Load Capacitance Test Formula
Bench testing with a 9V multimeter battery does not reveal capacitor dielectric breakdown occurring under full 240 V 240\text{V} 240 V operating load. The most rigorous diagnostic test measures current and voltage while the motor is actively running: μ F = Start Winding Amperes × 2652 Capacitor Measured Voltage (VAC) \mu\text{F} = \frac{\text{Start Winding Amperes} \times 2652}{\text{Capacitor Measured Voltage (VAC)}} μ F = Capacitor Measured Voltage (VAC) Start Winding Amperes × 2652
Where:
Start Winding Amperes \text{Start Winding Amperes} Start Winding Amperes = Current measured with a True-RMS clamp meter on the auxiliary start winding wire.
Capacitor Measured Voltage \text{Capacitor Measured Voltage} Capacitor Measured Voltage = Voltage measured directly across the capacitor terminals ( C to HERM or C to FAN ) while operating.
2652 2652 2652 = Constant derived from standard 60 Hz 60\text{ Hz} 60 Hz AC line frequency: X C = V C I start = 1 2 π f C ⟹ C = I start 2 π ( 60 ) V C = I start 376.99 × V C × 10 6 = I start × 2652 V C X_C = \frac{V_C}{I_{\text{start}}} = \frac{1}{2\pi f C} \implies C = \frac{I_{\text{start}}}{2\pi (60) V_C} = \frac{I_{\text{start}}}{376.99 \times V_C} \times 10^6 = \frac{I_{\text{start}} \times 2652}{V_C} X C = I start V C = 2 π f C 1 ⟹ C = 2 π ( 60 ) V C I start = 376.99 × V C I start × 1 0 6 = V C I start × 2652
Worked Example: Under-Load Capacitance Calculation
Problem: A technician diagnoses a running 4-ton compressor with a stamped 50 μ F 50\ \mu\text{F} 50 μ F run capacitor. While the compressor runs under full cooling load:
Measured Start Winding Current ( I start I_{\text{start}} I start ) = 6.2 Amperes 6.2\text{ Amperes} 6.2 Amperes
Measured Voltage Across Capacitor Terminals ( V C V_C V C ) = 360 VAC 360\text{ VAC} 360 VAC
Calculate actual running microfarads and determine if the capacitor meets ± 6 % \pm 6\% ± 6% tolerance. Actual μ F = 6.2 A × 2652 360 V = 16 , 442.4 360 = 45.67 μ F \text{Actual } \mu\text{F} = \frac{6.2\text{ A} \times 2652}{360\text{ V}} = \frac{16,442.4}{360} = \mathbf{45.67\ \mu\text{F}} Actual μ F = 360 V 6.2 A × 2652 = 360 16 , 442.4 = 45.67 μ F
Tolerance Check: Deviation = ( 45.67 − 50.0 50.0 ) × 100 = − 4.33 50.0 × 100 = − 8.66 % \text{Deviation} = \left(\frac{45.67 - 50.0}{50.0}\right) \times 100 = \frac{-4.33}{50.0} \times 100 = -8.66\% Deviation = ( 50.0 45.67 − 50.0 ) × 100 = 50.0 − 4.33 × 100 = − 8.66%
Diagnostic Conclusion: The capacitor has drifted − 8.66 % -8.66\% − 8.66% , exceeding the allowable ± 6 % \pm 6\% ± 6% manufacturer tolerance. The capacitor is degraded and must be replaced to prevent compressor motor overheating.
Loading diagram... Potential Starting Relay (Hard Start Kit) Wiring Schematic & Terminal Layout
4. Potential Starting Relays: Counter-EMF Operating Mechanics
The Potential Starting Relay (PSR) is the industry-standard starting device for high-efficiency single-phase air conditioning and heat pump compressors equipped with thermal expansion valves (TXVs). POTENTIAL RELAY OPERATING CYCLE
- 1. STANDSTILL (0% RPM) 2. ACCELERATION (0-75% RPM) 3. RUNNING (75-100% RPM)
- ┌──────────────────────┐ ┌──────────────────────┐ ┌──────────────────────┐
- │ CEMF = 0 Volts │ │ CEMF Rising Across S │ │ CEMF Reaches Pickup │
- │ Contacts 1-2 CLOSED │ ──► │ Start Cap in Parallel│ ──► │ (300V - 450V) │
- │ Full Inrush Torque │ │ High Acceleration │ │ Coil Energizes │
- │ Applied (300-400%) │ │ Torque Delivered │ │ Contacts 1-2 SNAP OPEN│
- └──────────────────────┘ └──────────────────────┘ └──────────────────────┘
- Counter-Electromotive Force (CEMF / Back-EMF)
As the compressor rotor spins inside the stator, the auxiliary start winding behaves like an electrical generator. The spinning magnetic field cuts across the fine start winding turns, inducing a Counter-Electromotive Force (CEMF / Back-EMF) voltage across the start winding.
CEMF is directly proportional to rotor rotational speed ( R P M RPM RPM ).
Because the start winding has significantly more wire turns than the run winding, generated CEMF voltage exceeds line voltage, frequently reaching 300 VAC to 450 + VAC 300\text{ VAC to }450+\text{ VAC} 300 VAC to 450 + VAC on a nominal 240 V 240\text{V} 240 V system at full operational speed!
Potential Relay Terminal Numbering & Internal Connections
Industry-standard potential relays utilize a universal three-terminal layout ( 1, 2, and 5 ):
Terminal 1: One side of the heavy-duty Normally Closed (NC) contacts ; wired in series with the start capacitor.
Terminal 2: The junction of the NC contacts and the high-resistance continuous voltage-sensing coil; wired directly to the compressor Start ( S ) terminal.
Terminal 5: The opposite end of the high-resistance sensing coil; wired to incoming Line 2 power (Compressor R / Run terminal).
Critical Operating Voltage Ratings
Pick-Up Voltage ( V pickup V_{\text{pickup}} V pickup ): The precise CEMF voltage required across the sensing coil (Terminals 2–5) to generate sufficient electromagnetic force to overcome spring tension and snap contacts 1–2 OPEN , taking the start capacitor out of the circuit. Occurs when the motor reaches 75 % to 80 % 75\%\text{ to }80\% 75% to 80% of synchronous speed (within ≈ 0.5 seconds \approx 0.5\text{ seconds} ≈ 0.5 seconds ).
Hold-In Voltage: The minimum CEMF voltage required to keep the coil energized and contacts 1–2 held open while the motor runs. Always lower than pick-up voltage.
Drop-Out Voltage: When the compressor shuts off and the rotor decelerates, CEMF collapses. When CEMF drops below the drop-out rating, internal spring tension drops the armature, re-closing contacts 1–2 so the start capacitor is ready for the next starting cycle.
Caution
Diagnostic Trap: Potential Relay vs. Current Relay: Potential relays have Normally Closed (NC) contacts and a high-resistance (high-turn) continuous voltage coil that senses CEMF across terminals 2 and 5.
Current starting relays (used on small fractional HP domestic refrigeration) have Normally Open (NO) contacts and a low-resistance (few turns of heavy wire) current coil wired in series with the main run winding that senses high starting inrush amperage.
Never confuse these devices—installing a potential relay incorrectly will burn out start capacitors or prevent motor starting.