7.1 The Psychrometric Chart: Dry-Bulb, Wet-Bulb, Relative Humidity, Enthalpy & Dew Point

Arizona HVAC Contractor License ROC R-39R/C-39/CR-39

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Arizona ROC Licensing & Legal Framework

1.1 Arizona ROC Authority & License Classifications 1.2 Application Requirements, Qualifying Party Duties & Experience Standards 1.3 Contractor Bonds, Financial Requirements & Residential Recovery Fund 1.4 Arizona Prompt Pay Act, Contracting Requirements & Mechanic's Liens 1.5 ROC Workmanship Standards, Complaint Investigation, Citations & Disciplinary Procedures

2 Chapter 2: Thermodynamics & The Vapor Compression Refrigeration Cycle

2.1 Thermodynamic Fundamentals, Heat Transfer & Pressure-Temperature Relationships 2.2 The Four Primary Cycle Components: Compressors, Condensers, Metering Devices & Evaporators 2.3 Superheat & Subcooling: Measurement, Calculation & Diagnostic Interpretation 2.4 Pressure-Enthalpy (P-h) Diagrams & System Operating Analysis 2.5 Refrigerant Characteristics, Oil Miscibility & ASHRAE Safety Classifications

3 Chapter 3: Refrigerant Management, EPA Section 608 & Environmental Compliance

3.1 EPA Clean Air Act Section 608 Regulations, Certifications & Venting Prohibitions 3.2 Recovery, Recycling & Reclaim Standards, Evacuation Levels & Deep Vacuum Procedures 3.3 Leak Detection Methods & Mandatory Repair Trigger Rates 3.4 Low-GWP Refrigerants & A2L Transition Safety Requirements 3.5 System Evacuation, Triple Evacuation Method, Vacuum Decay Testing & Moisture Removal

4 Chapter 4: Heating Systems: Gas Furnaces, Electric Heat & Combustion Safety

4.1 Fuel Gas Combustion Chemistry, Gas Burners & Orifice Sizing 4.2 Gas Furnace Components, Ignition Systems & Flame Rectification 4.3 Furnace Safety Controls & Troubleshooting Sequences 4.4 Gas Venting Categories (I-IV), Vent Sizing & Combustion Air Calculations 4.5 Electric Furnaces & Duct Heaters: Sizing, Sequencers, Thermal Cutoffs & Wiring

5 Chapter 5: Heat Pump Systems & Defrost Operation

5.1 Heat Pump Operating Principles & Reversing Valve Operation 5.2 Thermal Expansion Valves (TXVs), Electronic Expansion Valves (EEVs) & Bi-flow Metering 5.3 Defrost Systems: Time-Temperature vs. Demand Defrost Cycles & Sensor Operation 5.4 Heat Pump Balance Point Analysis, Supplemental Strip Heat Staging & Emergency Heat 5.5 Inverter-Driven Variable Capacity Systems & Desert Heat Pump Performance

6 Chapter 6: Air Distribution, Duct Design & Airflow Dynamics

6.1 Airflow Fundamentals: CFM Requirements, Velocity, Static Pressure & TESP 6.2 ACCA Manual D Duct Sizing: Equal Friction Method & Friction Rate Calculations 6.3 Duct Construction, Materials & SMACNA Support Standards 6.4 Duct Sealing (UL 181 Standards, Mastic, Tapes), Attic Insulation & Leakage Testing 6.5 Air System Balancing, Diagnostic Instruments & Grille/Register Selection

7 Chapter 7: Psychrometrics & Desert Climate HVAC Load Sizing

7.1 The Psychrometric Chart: Dry-Bulb, Wet-Bulb, Relative Humidity, Enthalpy & Dew Point 7.2 Psychrometric Air Conditioning Processes: Cooling, Heating, Humidification & Dehumidification 7.3 ACCA Manual J Residential Load Calculations: Heat Gain, Heat Loss, U-Values & SHGC 7.4 Arizona Desert Climate Design Considerations: Sensible Heat Ratios & Manual S Sizing 7.5 Evaporative Cooling Systems (Direct & Indirect Swamp Coolers): Principles & Maintenance

8 Chapter 8: HVAC Electrical Systems, Motors & Control Circuits

8.1 Electrical Fundamentals for HVAC: Ohm's Law, Power Formula & Single/Three-Phase Power 8.2 24VAC Control Circuits, Step-Down Transformers, Relays & Contactors 8.3 Capacitors (Start & Run), Potential Relays & Motor Starting Circuits 8.4 HVAC Motors: PSC, ECM & Three-Phase Motors 8.5 NEC Article 440 Compliance: MCA, MOCP & Disconnect Switch Rules

9 Chapter 9: Hydronics, Boilers, Chilled Water & Commercial Systems

9.1 Hydronic Heating Systems: Low-Pressure Hot Water & Steam Boilers 9.2 Hydronic Specialties: Air Separators, Expansion Tanks, Circulator Pumps & Zone Valves 9.3 Water Piping Systems, Sizing, Flow Rates & Relief Valves 9.4 Commercial Chilled Water Systems: Air-Cooled & Water-Cooled Chillers 9.5 Cooling Towers, Condenser Water Loops & Legionella Water Treatment

10 Chapter 10: Codes, Piping Systems, Safety & OSHA Standards

10.1 International Mechanical Code (IMC) & International Fuel Gas Code (IFGC) Compliance 10.2 Refrigerant Copper Piping: ACR Tubing, Brazing with Nitrogen Purge & Trapping 10.3 Fuel Gas Piping Installation: Materials, Sizing Tables & Pressure Testing 10.4 OSHA Safety Standards: Fall Protection, Scaffolding, Ladders & HazCom 10.5 OSHA Heat Illness Prevention for Arizona Outdoor Work, LOTO & Arc Flash Safety

7.1 The Psychrometric Chart: Dry-Bulb, Wet-Bulb, Relative Humidity, Enthalpy & Dew Point

Key Takeaways Explain This Topic AI

The psychrometric chart graphically correlates seven fundamental thermodynamic properties of moist air at standard sea-level atmospheric pressure (29.921 in. Hg / 14.696 psia); establishing any two independent properties completely fixes the thermodynamic state point.

Dry-bulb temperature (T_DB) measures sensible thermal kinetic energy along the horizontal axis, while humidity ratio (W, grains of moisture per pound of dry air, where 7,000 grains = 1 lb H2O) is read along the vertical right-hand scale.

Wet-bulb depression (T_DB - T_WB) measured by a sling psychrometer reflects the evaporative potential and moisture deficit of ambient air; when relative humidity reaches 100% saturation, dry-bulb, wet-bulb, and dew-point temperatures are identical.

The 3 fundamental HVAC air formulas derived from standard air density (0.075 lb/cu ft) and air specific heat (0.24 BTU/lb·°F) govern all equipment load calculations: Q_sensible = 1.08 × CFM × ΔT_DB, Q_latent = 0.68 × CFM × ΔW_grains, and Q_total = 4.5 × CFM × Δh_BTU/lb.

The Sensible Heat Ratio (SHR = Q_s / Q_t) defines the physical slope of the cooling/heating process line on the psychrometric chart and determines the proportion of sensible vs. latent cooling required.

Last updated: August 2026

7.1 The Psychrometric Chart: Dry-Bulb, Wet-Bulb, Relative Humidity, Enthalpy & Dew Point

Psychrometrics is the branch of thermodynamic engineering that studies the physical and thermal properties of moist air—a binary mixture of dry atmospheric gas and water vapor. In air conditioning and refrigeration design, air is both the convective transport medium and the thermal heat sink.

Every comfort cooling, heating, dehumidification, and evaporative cooling process involves thermodynamic transformations that can be precisely mapped, analyzed, and quantified using the Psychrometric Chart . For HVAC contractors in Arizona's low-humidity desert climate, mastering psychrometric properties is essential for sizing equipment, calculating air-side capacities, diagnosing airflow deficiencies, and preventing catastrophic coil freezing or capacity derating.

1. Standard Atmospheric Baseline & Chart Geometry

The standard psychrometric chart developed by the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) is constructed for a standard sea-level barometric pressure of 29.921 in. Hg (14.696 psia / 101.325 kPa) .

Under these standard conditions, air exhibits a standard density of:

ρ_air = 0.075 lb/cu ft (Specific volume v = 1 / ρ = 13.33 cu ft/lb dry air at 70°F) PSYCHROMETRIC CHART GEOMETRY & COORDINATE AXES

  • Enthalpy Scale (h)
  • [BTU/lb dry air] Saturation Curve (100% Relative Humidity)
  • / /
  • / /
  • / / Constant Wet-Bulb (T_wb)
  • ┌───────────────────────────┐ & Enthalpy (h) Lines (Diagonal)
  • │ │ /
  • │ │ / Relative Humidity Curves (% RH)
  • │ │ / /
  • │ │ / / Constant Specific Volume (v)
  • │ │ / / [cu ft / lb] (Steep Diagonal)
  • │ │ / / /
  • │ │/ / / Humidity Ratio Scale (W)
  • └───────────────────────────┴───┴─────┴──► [Grains of moisture / lb]
  • 30°F 50°F 70°F 90°F 110°F (Right-Hand Vertical Axis)
  • ◄──────── Dry-Bulb Temperature (T_db) ────────►
  • (Horizontal Bottom Axis)
  • The State Point Rule

According to Gibbs' Phase Rule for a two-component, single-phase mixture, establishing any two independent psychrometric properties (e.g., dry-bulb temperature and wet-bulb temperature, or dry-bulb temperature and relative humidity) definitively fixes the thermodynamic state point . Once this state point is plotted, all remaining five properties can be read directly from the intersecting coordinate lines.

2. The Seven Fundamental Psychrometric Properties

Psychrometric Property Symbol & Unit Chart Line Orientation Thermodynamic Definition & Physical Meaning

Dry-Bulb Temperature T_DB (°F) Vertical lines running from bottom axis The ambient air temperature measured by an unshielded, dry thermometer unaffected by moisture or thermal radiation. Represents sensible thermal energy.

Wet-Bulb Temperature T_WB (°F) Diagonal lines sloping downward to the right The lowest temperature attainable by adiabatic evaporative cooling of a wetted surface exposed to high-velocity airflow (> 900 FPM).

Dew-Point Temperature T_DP (°F) Horizontal lines extending left to saturation curve The saturation temperature at which water vapor in the air begins to condense into liquid droplets at constant pressure and moisture content.

Relative Humidity % RH (Percentage, %) Curved lines arching upward from left to right The ratio of the actual partial vapor pressure of water (p_w) to the saturation vapor pressure (p_ws) at the same dry-bulb temperature.

Humidity Ratio (Specific Humidity) W (Grains/lb or lb/lb) Horizontal lines extending to the right vertical scale The absolute mass of water vapor per unit mass of bone-dry air. Expressed in grains of moisture per pound of dry air (7,000 grains = 1.0 lb H2O).

Specific Enthalpy h (BTU/lb dry air) Diagonal lines extending outward to enthalpy scale The total thermal energy content of moist air per pound of dry air, incorporating both sensible heat of the air and latent heat of the water vapor (h = h_sensible + h_latent).

Specific Volume v (cu ft/lb dry air) Steep diagonal lines sloping downward right The reciprocal of air density (ρ = 1/v); represents the volume in cubic feet occupied by one pound of dry air plus its associated vapor.

Loading diagram... Psychrometric Coordinate Line Orientations

3. Sling Psychrometer Mechanics & Wet-Bulb Depression

A sling psychrometer consists of two matched mercury or spirit-filled thermometers mounted side-by-side on a swiveling frame: a dry-bulb thermometer that measures ambient air temperature, and a wet-bulb thermometer enclosed in a wetted, clean cotton wick. SLING PSYCHROMETER THERMODYNAMICS

  • Dry Thermometer Wetted Wick Thermometer
  • ┌─────────────────┐ ┌─────────────────┐
  • │ Reads: T_db │ │ Reads: T_wb │
  • │ (Sensible Temp) │ │ (Evaporative) │
  • └────────┬────────┘ └────────┬────────┘
  • │ │
  • ▼ ▼
  • 80°F Ambient Air 60°F Depressed Temp
  • │ │
  • └───────────────────┬─────────────────────┘
  • │
  • ▼
  • Wet-Bulb Depression = T_db - T_wb
  • 80°F - 60°F = 20°F Depression
  • (Indicates very dry, low-humidity air)
  • Wet-Bulb Depression Mechanics

Aspiration & Evaporation: When whirled through the air at an airspeed of at least 900 FPM (10 to 15 ft/s) , water evaporates from the wetted wick into the passing air stream.

Latent Heat Extraction: Evaporation requires latent heat of vaporization (h_fg ≈ 1,061 BTU/lb at room temperature), which is extracted directly from the thermometer bulb, causing its temperature to drop below the ambient dry-bulb temperature.

Wet-Bulb Depression Definition: The mathematical difference between the dry-bulb and wet-bulb temperatures is defined as the Wet-Bulb Depression :

Wet-Bulb Depression = T_DB - T_WB

Saturation Dynamics:

In bone-dry desert air (0% RH), water evaporates rapidly, yielding a large wet-bulb depression (25°F to 35°F).

In fully saturated air (100% RH), no net evaporation can occur (p_w = p_ws), meaning the wet-bulb depression is zero . At 100% RH:

T_DB = T_WB = T_DP

Note

Diagnostic Protocol: Always use distilled or deionized water on the psychrometer wick. Mineral salts present in tap water deposit on the wick fibers upon evaporation, creating an insulating crust that retards moisture transfer and causes falsely high wet-bulb readings.

4. Derivations of the Three Fundamental HVAC Air Formulas

In forced-air HVAC systems, calculating the capacity of heating coils, cooling coils, and heat pumps requires converting volumetric airflow (measured in Cubic Feet per Minute, CFM) and thermodynamic property changes into heat transfer rates (measured in BTU/hr).

All three universal HVAC air equations originate from the fundamental mass flow rate equation for air under standard atmospheric density:

  • m_dot_air = CFM × (60 min/hr) × ρ_air = CFM × 60 × 0.075 lb/cu ft = 4.5 × CFM [lb dry air / hr]
  • 1. Sensible Heat Equation (Q_s)

Sensible heat exchange changes the dry-bulb temperature of the air without altering its absolute moisture content (W remains constant):

Q_s = m_dot_air × c_p × ΔT_DB

Where c_p is the specific heat capacity of dry air (0.24 BTU / (lb·°F)):

  • Q_s = (4.5 × CFM) × 0.24 × ΔT_DB
  • Q_s = 1.08 × CFM × ΔT_DB [BTU/hr]
  • Constant 1.08 = 60 min/hr × 0.075 lb/cu ft × 0.24 BTU/lb·°F
  • ΔT_DB = |T_DB,entering - T_DB,leaving| (°F)
  • 2. Latent Heat Equation (Q_l)

Latent heat exchange changes the moisture content of the air through evaporation or condensation without changing the dry-bulb temperature:

Q_l = m_dot_air × h_fg × ΔW_lb

Where:

  • h_fg = Latent heat of vaporization of water at room temperature (≈ 1,061 BTU/lb)
  • ΔW_grains = Moisture change in grains of water per pound of dry air
  • Conversion factor: 1.0 lb H2O = 7,000 grains
  • Q_l = (4.5 × CFM) × 1,061 BTU/lb × (ΔW_grains / 7,000 grains/lb)
  • Q_l = ((4.5 × 1,061) / 7,000) × CFM × ΔW_grains = 0.682 × CFM × ΔW_grains
  • Q_l = 0.68 × CFM × ΔW_grains [BTU/hr]
  • Constant 0.68 = (60 × 0.075 × 1,061) / 7,000
  • ΔW_grains = |W_entering - W_leaving| (grains/lb dry air)
  • 3. Total Heat Equation (Q_t)

Total heat exchange accounts for the combined sensible and latent thermal energy transferred across the heat exchanger using specific enthalpy (h in BTU/lb dry air):

  • Q_t = m_dot_air × Δh
  • Q_t = (4.5 × CFM) × Δh
  • Q_t = 4.5 × CFM × Δh [BTU/hr]
  • Constant 4.5 = 60 min/hr × 0.075 lb/cu ft
  • Δh = |h_entering - h_leaving| (BTU/lb dry air)
  • Thermodynamic balance verification: Q_t = Q_s + Q_l
  • 4. Sensible Heat Ratio (SHR)

The Sensible Heat Ratio (SHR) represents the fraction of total cooling capacity devoted exclusively to lowering sensible dry-bulb temperature:

SHR = Q_s / Q_t = Q_s / (Q_s + Q_l) SENSIBLE HEAT RATIOS BY REGION

  • Humid Southeast / Coastal (SHR ≈ 0.65 - 0.75) Arizona Desert (SHR ≈ 0.85 - 0.95+)
  • ┌───────────────────┬──────────────────┐ ┌───────────────────────────────┬───────┐
  • │ Sensible (70%) │ Latent (30%) │ │ Sensible (90%) │Lat(10)│
  • └───────────────────┴──────────────────┘ └───────────────────────────────┴───────┘
  • 5. Comprehensive Worked Engineering Calculation
  • Field Scenario

A technician performs a commissioning test on a nominal 3-ton (36,000 BTU/hr) split-system air conditioner in a Phoenix home. Airflow is verified at 1,200 CFM. Psychrometric measurements across the evaporator coil yield the following properties:

Entering Return Air Conditions:

  • T_DB,entering = 80.0°F
  • T_WB,entering = 67.0°F
  • Psychrometric chart lookup: Enthalpy h_entering = 31.6 BTU/lb, Moisture W_entering = 78.0 grains/lb

Leaving Supply Air Conditions:

  • T_DB,leaving = 57.0°F
  • T_WB,leaving = 55.0°F
  • Psychrometric chart lookup: Enthalpy h_leaving = 23.2 BTU/lb, Moisture W_leaving = 61.0 grains/lb
  • Step-by-Step Mathematical Solution

Calculate Sensible Heat Removal (Q_s):

  • ΔT_DB = 80.0°F - 57.0°F = 23.0°F
  • Q_s = 1.08 × 1,200 CFM × 23.0°F = 1.08 × 27,600 = 29,808 BTU/hr

Calculate Latent Heat Removal (Q_l):

  • ΔW = 78.0 gr/lb - 61.0 gr/lb = 17.0 grains/lb
  • Q_l = 0.68 × 1,200 CFM × 17.0 gr/lb = 0.68 × 20,400 = 13,872 BTU/hr

Calculate Total Heat Removal using Enthalpy (Q_t):

  • Δh = 31.6 BTU/lb - 23.2 BTU/lb = 8.4 BTU/lb
  • Q_t = 4.5 × 1,200 CFM × 8.4 BTU/lb = 4.5 × 10,080 = 45,360 BTU/hr

Verify Energy Summation & Calculate System SHR:

Q_s+l = Q_s + Q_l = 29,808 + 13,872 = 43,680 BTU/hr

(Note: Minor variance between Q_t via enthalpy and Q_s+Q_l is due to standard rounding of the 1.08, 0.68, and 4.5 constants and chart interpolation).

  • SHR = Q_s / Q_t = 29,808 BTU/hr / 43,680 BTU/hr = 0.682 (68.2% Sensible)
  • 6. High-Altitude and Density Deration

Warning

Arizona Exam Trap — Altitude Air Density Adjustments: Standard constants (1.08, 0.68, 4.5) assume sea-level air density (ρ = 0.075 lb/cu ft). In Northern Arizona (e.g., Flagstaff at elevation 7,000 ft, barometric pressure ≈ 23.0 in. Hg, density ρ ≈ 0.060 lb/cu ft), air is 20% less dense.

The sensible constant drops from 1.08 to 0.86 (60 × 0.060 × 0.24 = 0.864).

The total constant drops from 4.50 to 3.60 (60 × 0.060 = 3.60).

Failure to derate density constants in high-elevation Arizona designs leads to calculated capacities being overpredicted by 20%.