7.2 Psychrometric Air Conditioning Processes: Cooling, Heating, Humidification & Dehumidification

Arizona HVAC Contractor License ROC R-39R/C-39/CR-39

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Arizona ROC Licensing & Legal Framework

1.1 Arizona ROC Authority & License Classifications 1.2 Application Requirements, Qualifying Party Duties & Experience Standards 1.3 Contractor Bonds, Financial Requirements & Residential Recovery Fund 1.4 Arizona Prompt Pay Act, Contracting Requirements & Mechanic's Liens 1.5 ROC Workmanship Standards, Complaint Investigation, Citations & Disciplinary Procedures

2 Chapter 2: Thermodynamics & The Vapor Compression Refrigeration Cycle

2.1 Thermodynamic Fundamentals, Heat Transfer & Pressure-Temperature Relationships 2.2 The Four Primary Cycle Components: Compressors, Condensers, Metering Devices & Evaporators 2.3 Superheat & Subcooling: Measurement, Calculation & Diagnostic Interpretation 2.4 Pressure-Enthalpy (P-h) Diagrams & System Operating Analysis 2.5 Refrigerant Characteristics, Oil Miscibility & ASHRAE Safety Classifications

3 Chapter 3: Refrigerant Management, EPA Section 608 & Environmental Compliance

3.1 EPA Clean Air Act Section 608 Regulations, Certifications & Venting Prohibitions 3.2 Recovery, Recycling & Reclaim Standards, Evacuation Levels & Deep Vacuum Procedures 3.3 Leak Detection Methods & Mandatory Repair Trigger Rates 3.4 Low-GWP Refrigerants & A2L Transition Safety Requirements 3.5 System Evacuation, Triple Evacuation Method, Vacuum Decay Testing & Moisture Removal

4 Chapter 4: Heating Systems: Gas Furnaces, Electric Heat & Combustion Safety

4.1 Fuel Gas Combustion Chemistry, Gas Burners & Orifice Sizing 4.2 Gas Furnace Components, Ignition Systems & Flame Rectification 4.3 Furnace Safety Controls & Troubleshooting Sequences 4.4 Gas Venting Categories (I-IV), Vent Sizing & Combustion Air Calculations 4.5 Electric Furnaces & Duct Heaters: Sizing, Sequencers, Thermal Cutoffs & Wiring

5 Chapter 5: Heat Pump Systems & Defrost Operation

5.1 Heat Pump Operating Principles & Reversing Valve Operation 5.2 Thermal Expansion Valves (TXVs), Electronic Expansion Valves (EEVs) & Bi-flow Metering 5.3 Defrost Systems: Time-Temperature vs. Demand Defrost Cycles & Sensor Operation 5.4 Heat Pump Balance Point Analysis, Supplemental Strip Heat Staging & Emergency Heat 5.5 Inverter-Driven Variable Capacity Systems & Desert Heat Pump Performance

6 Chapter 6: Air Distribution, Duct Design & Airflow Dynamics

6.1 Airflow Fundamentals: CFM Requirements, Velocity, Static Pressure & TESP 6.2 ACCA Manual D Duct Sizing: Equal Friction Method & Friction Rate Calculations 6.3 Duct Construction, Materials & SMACNA Support Standards 6.4 Duct Sealing (UL 181 Standards, Mastic, Tapes), Attic Insulation & Leakage Testing 6.5 Air System Balancing, Diagnostic Instruments & Grille/Register Selection

7 Chapter 7: Psychrometrics & Desert Climate HVAC Load Sizing

7.1 The Psychrometric Chart: Dry-Bulb, Wet-Bulb, Relative Humidity, Enthalpy & Dew Point 7.2 Psychrometric Air Conditioning Processes: Cooling, Heating, Humidification & Dehumidification 7.3 ACCA Manual J Residential Load Calculations: Heat Gain, Heat Loss, U-Values & SHGC 7.4 Arizona Desert Climate Design Considerations: Sensible Heat Ratios & Manual S Sizing 7.5 Evaporative Cooling Systems (Direct & Indirect Swamp Coolers): Principles & Maintenance

8 Chapter 8: HVAC Electrical Systems, Motors & Control Circuits

8.1 Electrical Fundamentals for HVAC: Ohm's Law, Power Formula & Single/Three-Phase Power 8.2 24VAC Control Circuits, Step-Down Transformers, Relays & Contactors 8.3 Capacitors (Start & Run), Potential Relays & Motor Starting Circuits 8.4 HVAC Motors: PSC, ECM & Three-Phase Motors 8.5 NEC Article 440 Compliance: MCA, MOCP & Disconnect Switch Rules

9 Chapter 9: Hydronics, Boilers, Chilled Water & Commercial Systems

9.1 Hydronic Heating Systems: Low-Pressure Hot Water & Steam Boilers 9.2 Hydronic Specialties: Air Separators, Expansion Tanks, Circulator Pumps & Zone Valves 9.3 Water Piping Systems, Sizing, Flow Rates & Relief Valves 9.4 Commercial Chilled Water Systems: Air-Cooled & Water-Cooled Chillers 9.5 Cooling Towers, Condenser Water Loops & Legionella Water Treatment

10 Chapter 10: Codes, Piping Systems, Safety & OSHA Standards

10.1 International Mechanical Code (IMC) & International Fuel Gas Code (IFGC) Compliance 10.2 Refrigerant Copper Piping: ACR Tubing, Brazing with Nitrogen Purge & Trapping 10.3 Fuel Gas Piping Installation: Materials, Sizing Tables & Pressure Testing 10.4 OSHA Safety Standards: Fall Protection, Scaffolding, Ladders & HazCom 10.5 OSHA Heat Illness Prevention for Arizona Outdoor Work, LOTO & Arc Flash Safety

7.2 Psychrometric Air Conditioning Processes: Cooling, Heating, Humidification & Dehumidification

Key Takeaways Explain This Topic AI

The four cardinal thermodynamic directions on the psychrometric chart are sensible heating (due east/right), sensible cooling (due west/left), humidification (due north/up), and dehumidification (due south/down).

Cooling and dehumidification proceeds along a diagonal path down and to the left directed toward the Apparatus Dew Point (ADP), which represents the effective coil surface saturation temperature.

Coil Bypass Factor (BF = [T_leaving - ADP] / [T_entering - ADP]) quantifies the percentage of air passing through a coil without contacting fin surfaces; Contact Factor (CF = 1 - BF) defines coil thermal effectiveness.

Adiabatic humidification (direct evaporative cooling) follows a line of constant wet-bulb temperature and constant enthalpy upward and to the left, converting sensible heat into latent heat with zero net total heat transfer (Q_t = 0).

Mixed air calculations use mass-weighted conservation of energy: Mixed Air Temperature (MAT) = (RAT × %RA) + (OAT × %OA), with identical weighted relationships governing mixed air enthalpy (h_m) and humidity ratio (W_m).

Last updated: August 2026

7.2 Psychrometric Air Conditioning Processes: Cooling, Heating, Humidification & Dehumidification

Thermodynamic air conditioning processes represent continuous physical changes in air temperature, moisture content, and energy as air traverses fans, heating exchangers, DX evaporator coils, humidifiers, and mixing plenums.

Mapping these processes on the psychrometric chart allows HVAC engineers and contractors to visualize conditioning pathways, evaluate coil performance, calculate moisture removal rates, and size multi-zone ventilation systems.

1. The Cardinal Psychrometric Conditioning Vectors

Every environmental conditioning process is a directional vector on the psychrometric chart composed of sensible (horizontal) and latent (vertical) components: CARDINAL PSYCHROMETRIC VECTORS

  • Humidification Only
  • (Constant T_db) ▲ [North]
  • │
  • Evaporative Cooling │ Chemical Dehumidification
  • (Adiabatic, Constant h/T_wb) │ (Sensible Heat Addition)
  • ▲ │ ▲
  • \ │ /
  • ◄──────────────────────┼──────────────────────►
  • Sensible Cooling │ Sensible Heating
  • (Constant W) [West] │ (Constant W) [East]
  • │
  • │
  • ▼ [South]
  • Dehumidification Only
  • (Constant T_db)
  • Thermodynamic Vector Summary Table

Process Vector Chart Direction Dry-Bulb (T_DB) Humidity Ratio (W) Relative Humidity (% RH) Enthalpy (h)

Sensible Heating (Electric strip, gas furnace) Due East (Right) Increases (ΔT > 0) Constant (ΔW = 0) Decreases Increases

Sensible Cooling (Dry coil, above T_DP) Due West (Left) Decreases (ΔT < 0) Constant (ΔW = 0) Increases Decreases

Pure Humidification (Steam injection) Due North (Up) Constant (ΔT = 0) Increases (ΔW > 0) Increases Increases

Pure Dehumidification (Solid desiccant wheel) Due South (Down) Constant (ΔT = 0) Decreases (ΔW < 0) Decreases Decreases

Cooling & Dehumidifying (DX cooling coil) Southwest (Down-Left) Decreases Decreases Increases (approaches 100%) Decreases

Adiabatic Evaporative Cooling (Swamp cooler) Northwest (Up-Left) Decreases Increases Increases Constant (Δh = 0)

Loading diagram... Thermodynamic Process Pathways on the Psychrometric Chart

2. Cooling and Dehumidification & Apparatus Dew Point (ADP)

When air enters a direct-expansion (DX) evaporator coil or chilled water coil, moisture removal (dehumidification) occurs if and only if the coil surface temperature is below the entering air's dew-point temperature (T_coil surface < T_DP,entering). COOLING & DEHUMIDIFICATION PROCESS CURVE

  • Saturation Curve (100% RH)
  • ┌───────────────────────────────────────────────┐
  • │ │
  • │ [Apparatus Dew Point - ADP] │
  • │ (50°F, 100% RH) │
  • │ * │
  • │ \ │
  • │ \ Leaving Air Point │
  • │ * (55°F DB / 53°F WB) │
  • │ \ │
  • │ \ │
  • │ * Entering Air Point │
  • │ (80°F DB / 67°F WB) │
  • └───────────────────────────────────────────────┘
  • Apparatus Dew Point (ADP)

The Apparatus Dew Point (ADP) is the effective coil surface temperature. It is graphically determined by extending the straight process line connecting the entering air state point and the leaving air state point until it intersects the 100% RH saturation curve.

Coil Bypass Factor (BF) and Contact Factor (CF)

In real-world HVAC equipment, not all air entering the coil comes into direct physical contact with the cold fins and tubes. A portion of the air stream passes through unobstructed open spaces between fins without undergoing heat transfer:

Bypass Factor (BF): The fraction of total airflow that completely bypasses the cooling surfaces unchanged.

Contact Factor (CF): The fraction of total airflow that makes perfect thermodynamic contact with the coil surfaces (CF = 1.0 - BF).

Mathematical Formulation of Bypass Factor:

BF = (T_DB,leaving - ADP) / (T_DB,entering - ADP) = (W_leaving - W_ADP) / (W_entering - W_ADP) = (h_leaving - h_ADP) / (h_entering - h_ADP)

Rearranging to solve for the leaving air dry-bulb temperature:

T_DB,leaving = ADP + BF × (T_DB,entering - ADP)

Typical Equipment Bypass Factors:

  • Residential DX split-system evaporator coils: BF = 0.10 to 0.20 (10% to 20% bypass)
  • Commercial multi-row chilled water coils (6 to 8 rows): BF = 0.03 to 0.08 (3% to 8% bypass)
  • Worked Example: Leaving Air Temperature Calculation

Problem: Return air enters a residential cooling coil at 80.0°F dry-bulb. The coil operates at an Apparatus Dew Point (ADP) of 48.0°F with an engineered Bypass Factor (BF) of 0.15. What is the leaving supply air dry-bulb temperature?

Apply the bypass equation:

T_DB,leaving = 48.0°F + [0.15 × (80.0°F - 48.0°F)]

Calculate temperature difference across coil potential:

80.0°F - 48.0°F = 32.0°F

Solve:

T_DB,leaving = 48.0°F + (0.15 × 32.0°F) = 48.0°F + 4.8°F = 52.8°F

Result: The leaving air dry-bulb temperature is 52.8°F .

3. Adiabatic Evaporative Cooling (Constant Wet-Bulb Process)

Adiabatic evaporative cooling is the thermodynamic process where liquid water evaporates into an unsaturated air stream with zero external heat added or removed (Q_total = 0). ADIABATIC SATURATION THERMODYNAMICS

  • Dry Air Stream ──► [Wetted Media Pad] ──► Cool, Humid Air
  • High Dry-Bulb • Low Dry-Bulb
  • Low Moisture (Grains) • High Moisture (Grains)
  • Constant Enthalpy (h) ◄────────────────► • Constant Enthalpy (h)
  • Thermodynamic Mechanism

As air passes through saturated media pads, sensible heat from the dry air is absorbed to supply the latent heat of vaporization (h_fg ≈ 1,061 BTU/lb) needed to evaporate the liquid water into vapor.

Sensible dry-bulb temperature drops significantly, while humidity ratio (W) increases proportionally.

Because no heat enters or leaves the system boundary, the total energy content is conserved: Enthalpy (h) and Wet-Bulb Temperature (T_WB) remain constant throughout the entire direct evaporative process.

The process line slopes upward and to the left along the constant wet-bulb coordinate line toward the saturation curve.

4. Mixed Air Calculations (Return Air + Outdoor Air)

Commercial packaged rooftop units (RTUs) and residential systems equipped with mechanical fresh air ventilation mix two distinct air streams prior to entering the conditioning coil: Return Air (RA) from the conditioned space and Outdoor Air (OA) for code-mandated ventilation (ASHRAE 62.1/62.2). AIR STREAM MIXING PLENUM SCHEMATIC

  • Outdoor Air (OA) ──────┐
  • (e.g., 105°F, 20% CFM) │
  • ├──► [MIXING PLENUM] ──► Mixed Air to Coil (MAT)
  • Return Air (RA) ──────┘
  • (e.g., 75°F, 80% CFM)
  • Mass and Energy Balance Formulas

Because mass and energy are strictly conserved, the thermodynamic properties of the Mixed Air (MA) stream are calculated as the volumetric-weighted averages of the constituent streams:

  • MAT = (RAT × %RA) + (OAT × %OA)
  • MAT = RAT + [(CFM_OA / CFM_Total) × (OAT - RAT)]
  • Enthalpy: h_mixed = (h_RA × %RA) + (h_OA × %OA)
  • Humidity: W_mixed = (W_RA × %RA) + (W_OA × %OA)
  • Comprehensive Mixed Air Worked Example

Scenario: A light commercial RTU serving a retail space in Scottsdale, Arizona circulates a total volumetric airflow of 4,000 CFM . The economizer minimum ventilation damper introduces 15% Outdoor Air (600 CFM), while the remaining 85% (3,400 CFM) is Return Air.

Given Psychrometric Conditions:

  • Outdoor Air (OA): 105.0°F DB, Enthalpy h_OA = 36.0 BTU/lb, Moisture W_OA = 85.0 gr/lb
  • Return Air (RA): 75.0°F DB, Enthalpy h_RA = 28.0 BTU/lb, Moisture W_RA = 60.0 gr/lb

Calculations:

Mixed Air Temperature (MAT):

MAT = (75.0°F × 0.85) + (105.0°F × 0.15) = 63.75°F + 15.75°F = 79.5°F

Mixed Air Enthalpy (h_mixed):

h_mixed = (28.0 BTU/lb × 0.85) + (36.0 BTU/lb × 0.15) = 23.8 + 5.4 = 29.2 BTU/lb

Mixed Air Humidity Ratio (W_mixed):

W_mixed = (60.0 gr/lb × 0.85) + (85.0 gr/lb × 0.15) = 51.0 + 12.75 = 63.75 gr/lb

Important

Diagnostic Standard: The mixed air temperature entering the cooling coil in this desert application is 79.5°F rather than the room temperature of 75.0°F. When performing capacity calculations or verifying coil delta-T, technicians must always measure entering dry-bulb downstream of the mixing box (entering coil face) rather than at a room return grille.