6.2 The CT Disinfection Concept & Basin Hydraulics

Arizona Water/Wastewater Operator Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Arizona Regulatory Framework & ADEQ Certification

1.1 ADEQ Operator Certification Rules & Grade Structure 1.2 Facility Classification & Operator in Direct Responsible Charge (ODRC) 1.3 Arizona Aquifer Protection Permit (APP) Program & BADCT 1.4 AZPDES Surface Water Discharges & Arizona Reclaimed Water Standards 1.5 The WPI Need-to-Know Criteria: What Is Actually on Your Exam

2 Chapter 2: Federal Drinking Water & Clean Water Act Compliance

2.1 Safe Drinking Water Act (SDWA) Primary & Secondary MCLs 2.2 Surface Water Treatment Rules & Revised Total Coliform Rule (RTCR) 2.3 Stage 1 & Stage 2 Disinfectants/Disinfection Byproducts Rules (D/DBPR)

3 Chapter 3: Source Water Assessment, Wells & Watershed Protection

3.1 Groundwater Sources, Well Components & Water Level Measurement 3.2 Surface Water Sources, Intakes & Reservoir Management 3.3 Watershed Management, Contamination Sources & Public Education 3.4 Pretreatment: Aeration, Presedimentation & Algae Control

4 Chapter 4: Source Water Quality, Coagulation & Flocculation

4.1 Arizona Source Water Quality & Arid Climate Challenges 4.2 Coagulation Chemistry, Coagulants & Jar Testing 4.3 Flocculation Basin Design & Process Control 4.4 Sedimentation Basins, Clarifiers & Solids Contact Units

5 Chapter 5: Filtration Systems & Advanced Separation

5.1 Granular Media Filtration Principles & Media Types 5.2 Filter Backwash Operations, Ripening & Filter-to-Waste 5.3 Membrane Filtration & Reverse Osmosis Desalination 5.4 Ion Exchange Softening, Arsenic Removal & GAC Adsorption

6 Chapter 6: Drinking Water Disinfection & Chemical Oxidation

6.1 Chlorine Chemistry & Break-Point Chlorination 6.2 The CT Disinfection Concept & Basin Hydraulics 6.3 Alternative Disinfectants: Chloramines, Ozone, UV & Chlorine Dioxide

7 Chapter 7: Specialized Drinking Water Treatment & Chemical Conditioning

7.1 Iron & Manganese Removal 7.2 Fluoridation: Chemicals, Dosage & Safety 7.3 Corrosion Control, Saturation Indices & the Lead and Copper Rule 7.4 Water Treatment Plant Residuals Handling & Disposal

8 Chapter 8: Water Treatment Plant Equipment Operation & Maintenance

8.1 Raw Water Intake, Screening & Pumping Equipment 8.2 Chemical Feed Equipment, Storage & Metering 8.3 Instrumentation, Online Analyzers, SCADA & Calibration 8.4 Valves, Motors, Auxiliary Systems & Maintenance Programs

9 Chapter 9: Wastewater Preliminary, Primary & Biological Treatment Principles

9.1 Wastewater Characteristics & Preliminary Treatment 9.2 Primary Clarification Design & Settling Mechanics 9.3 Biological Treatment Kinetics & Microbiology

10 Chapter 10: Activated Sludge Processes & Nutrient Removal

10.1 Activated Sludge Configurations & Operational Mass Balance 10.2 Process Control Parameters, Settleability & Troubleshooting 10.3 Biological Nutrient Removal: Nitrification, Denitrification & Phosphorus Removal

11 Chapter 11: Fixed-Film, Lagoon & Advanced Secondary Processes

11.1 Trickling Filters & Attached Growth Fundamentals 11.2 Rotating Biological Contactors & Hybrid Processes 11.3 Stabilization Ponds & Lagoon Systems 11.4 Membrane Bioreactors

12 Chapter 12: Tertiary Treatment, Wastewater Disinfection & Effluent Management

12.1 Tertiary Filtration & Advanced Effluent Polishing 12.2 Wastewater Chlorination & Dechlorination 12.3 Ultraviolet & Ozone Disinfection of Wastewater 12.4 Effluent Disposal, Reclaimed Water Reuse & Permit Compliance

13 Chapter 13: Residuals Management & Sludge Processing

13.1 Sludge Thickening & Digestion Processes 13.2 Sludge Dewatering Technologies & Drying Beds 13.3 EPA Part 503 Biosolids Rules & Arizona Beneficial Use

14 Chapter 14: Wastewater Plant Equipment Operation & Maintenance

14.1 Preliminary & Primary Treatment Equipment 14.2 Aeration Systems, Blowers, Diffusers & Dissolved Oxygen Control 14.3 Wastewater Pumps, Mixers & Chemical Dosing Equipment 14.4 Electrical Systems, Online Analyzers & Auxiliary Power

15 Chapter 15: Water Distribution Infrastructure & Hydraulic Management

15.1 Water Main Materials, Fittings & Appurtenances 15.2 Water Storage, Pressure Management & Water Age 15.3 Cross-Connection Control & Backflow Prevention 15.4 Main Maintenance, Unidirectional Flushing & Leak Detection 15.5 Distribution Hydraulics, Head Loss & C-Factor 15.6 System Mapping, GIS, Plans & Distribution SCADA

16 Chapter 16: Water Main Installation, Repair & Disinfection

16.1 Main & Service Line Installation, Tapping & Thrust Restraint 16.2 New Construction Inspection, Pressure Testing & Utility Locating 16.3 Disinfection of Mains, Storage Facilities & Repaired Components 16.4 Booster Stations, Meters & Storage Facility Inspection

17 Chapter 17: Distribution Water Quality Management & Field Testing

17.1 Distribution Chemical Feed, Dosage Adjustment & Booster Chlorination 17.2 Distribution Sampling Programs & Field Analyses 17.3 Chemical Transport, Storage & Handling in Distribution Operations 17.4 Interpreting Water Quality Data, Complaints & Nitrification Control

18 Chapter 18: Wastewater Collection Systems & Lift Stations

18.1 Gravity Sewer Design, Piping Materials & Manholes 18.2 Inflow & Infiltration (I&I) Assessment & Pipeline Rehabilitation 18.3 Wastewater Lift Stations, Pump Types & Force Mains 18.4 Hydrogen Sulfide Corrosion, Odor Control & Line Cleaning 18.5 Excavation, Heavy Equipment & Surface Restoration

19 Chapter 19: Collection System Cleaning, Inspection & Rehabilitation

19.1 Hydraulic Cleaning, Rodding & Blockage Removal 19.2 CCTV Inspection, Condition Assessment & FOG Control 19.3 Trenchless Rehabilitation: CIPP, Pipe Bursting & Lining 19.4 SSO Response, Flow Monitoring & Capacity Assurance

20 Chapter 20: Laboratory Testing, Quality Control & Monitoring

20.1 Drinking Water Analytical Methods & Compliance Testing 20.2 Wastewater Laboratory Analytics & Process Control Tests 20.3 Sampling Protocols, Chain of Custody & Laboratory QA/QC 20.4 Emerging Contaminants, PFAS & Advanced Analytical Methods

21 Chapter 21: Utility Safety Programs & Emergency Preparedness

21.1 Lockout/Tagout, Electrical Safety & Arc Flash 21.2 Personal Protective Equipment, Fall Protection & Bloodborne Pathogens 21.3 Traffic Control & Work Zone Safety 21.4 Emergency Response Planning & Disaster Recovery 21.5 Heat Illness Prevention, Respiratory Protection & Hearing Conservation

22 Chapter 22: Security, Administration & Utility Management

22.1 Facility Security, Vulnerability Assessment & Cybersecurity 22.2 Recordkeeping, Standard Operating Procedures & Regulatory Reporting 22.3 Budgets, Procurement, Cost Analysis & Capital Improvement Planning 22.4 Asset Management, Energy Optimization & Water Loss Control 22.5 Supervision, Training, Customer Service & Public Communication

23 Chapter 23: Applied Operator Mathematics, Pumping Hydraulics & Utility Safety

23.1 Chemical Feed Calculations & Dosage Problem Solving 23.2 Geometric Volumes, Hydraulic Loading & Detention Time Math 23.3 Pumping Mechanics, System Head & Horsepower Calculations 23.4 Plant Safety: Confined Spaces, Chemical Hazards & OSHA Standards 23.5 Unit Conversions & Using the Supplied Formula/Conversion Table 23.6 Percent Removal, Process Efficiency & Solution Blending

6.2 The CT Disinfection Concept & Basin Hydraulics

Key Takeaways Explain This Topic AI

Under the Safe Drinking Water Act Surface Water Treatment Rules, disinfection efficacy is quantified using the CT calculation: disinfectant residual concentration (C in mg/L) multiplied by effective contact time (T₁₀ in minutes).

The Surface Water Treatment Rule mandates minimum total removal and inactivation standards of 3-log (99.9%) for Giardia lamblia cysts and 4-log (99.99%) for enteric viruses across the overall treatment train.

Conventional surface water filtration plants receive credit for 2.5-log Giardia and 2.0-log virus removal, requiring chemical disinfection to achieve the remaining 0.5-log Giardia and 2.0-log virus inactivation.

Effective contact time (T₁₀) represents the duration for 10% of the water volume to pass through a contact basin and is calculated by multiplying theoretical hydraulic detention time by the basin's hydraulic baffling factor (ranging from 0.1 for unbaffled basins to 1.0 for perfect plug flow).

Disinfection kinetics are acutely sensitive to water temperature and pH: colder water and higher pH values significantly decrease pathogen inactivation rates, requiring substantially higher CT values to achieve compliance.

Last updated: September 2026

6.2 The CT Disinfection Concept & Basin Hydraulics

Under the federal Safe Drinking Water Act (SDWA) Surface Water Treatment Rule (SWTR), Interim Enhanced Surface Water Treatment Rule (IESWTR), and Long Term 1 and 2 Enhanced Surface Water Treatment Rules (LT1/LT2ESWTR), all public water systems utilizing surface water or Groundwater Under the Direct Influence of Surface Water (GWUDI) must ensure continuous, verified destruction of microbial pathogens. In Arizona, where utilities treat surface water from the Colorado River via the Central Arizona Project (CAP), the Salt and Verde River watersheds, and mountain impoundments, regulatory compliance centers on the CT Disinfection Concept codified under Arizona Administrative Code (A.A.C.) R18-4-301.

Regulatory Basis & Pathogen Log-Inactivation Standards

The SWTR establishes legally enforceable health performance standards based on log-reduction benchmarks. Log-reduction measures the mathematical reduction of viable pathogens on a logarithmic scale: Log Reduction = log ⁡ 10 ( N 0 N ) \text{Log Reduction} = \log_{10}\left(\frac{N_0}{N}\right) Log Reduction = lo g 10 ​ ( N N 0 ​ ​ ) Percent Inactivation = ( 1 − 1 10 Log Reduction ) × 100 % \text{Percent Inactivation} = \left(1 - \frac{1}{10^{\text{Log Reduction}}}\right) \times 100\% Percent Inactivation = ( 1 − 1 0 Log Reduction 1 ​ ) × 100%

1-log Inactivation: 90.0% reduction ( N / N 0 = 0.10 N/N_0 = 0.10 N / N 0 ​ = 0.10 ).

2-log Inactivation: 99.0% reduction ( N / N 0 = 0.01 N/N_0 = 0.01 N / N 0 ​ = 0.01 ).

3-log Inactivation: 99.9% reduction ( N / N 0 = 0.001 N/N_0 = 0.001 N / N 0 ​ = 0.001 ).

4-log Inactivation: 99.99% reduction ( N / N 0 = 0.0001 N/N_0 = 0.0001 N / N 0 ​ = 0.0001 ).

Minimum Multi-Barrier Compliance Targets

The EPA mandates that all surface water treatment systems deliver at least:

3-log (99.9%) reduction of Giardia lamblia cysts: Giardia is a flagellated protozoan parasite whose thick outer cyst wall resists environmental stress and mild chemical exposure, causing severe human gastrointestinal illness (giardiasis).

4-log (99.99%) reduction of enteric viruses: Enteric viruses (rotaviruses, noroviruses, enteroviruses, Hepatitis A) are minuscule infectious virions transmitted via fecal contamination.

Cryptosporidium oocyst protection: Highly chlorine-resistant protozoan oocysts regulated under LT2ESWTR through physical filtration removal credits (2.0 to 3.0-log) and, where source water Bin classification dictates, advanced disinfection (UV irradiation, ozone, or chlorine dioxide).

Treatment Credits: Physical Filtration vs. Chemical Inactivation

The regulatory framework recognizes that water treatment is a sequential, multi-barrier process. Facilities receive predetermined physical removal credits for properly operated coagulation, sedimentation, and granular media filtration systems that meet stringent filtered effluent turbidity limits ( ≤ 0.30 \le 0.30 ≤ 0.30 NTU in 95% of monthly measurements):

Treatment Process Configuration Giardia Cyst Physical Removal Credit Enteric Virus Physical Removal Credit Required Disinfection Inactivation (Giardia) Required Disinfection Inactivation (Viruses)

Conventional Filtration (Coagulation, Flocculation, Sedimentation, Filtration) 2.5-log (99.7%) 2.0-log (99.0%) 0.5-log (68.4%) 2.0-log (99.0%)

Direct Filtration (Coagulation, Flocculation, Filtration; No Sedimentation) 2.0-log (99.0%) 1.0-log (90.0%) 1.0-log (90.0%) 3.0-log (99.9%)

  • Slow Sand Filtration 2.0-log (99.0%) 2.0-log (99.0%) 1.0-log (90.0%) 2.0-log (99.0%)
  • Diatomaceous Earth Filtration 2.0-log (99.0%) 1.0-log (90.0%) 1.0-log (90.0%) 3.0-log (99.9%)

For conventional surface water treatment plants in Arizona, the chemical disinfection process must achieve at least 0.5-log Giardia inactivation and 2.0-log virus inactivation every single operating day.

Kinetic Formulation of the CT Concept

Disinfection kinetics follow the classic Chick-Watson Law , which states that the rate of microbial inactivation is directly proportional to the disinfectant concentration ( C C C ) raised to a coefficient of dilution ( n ≈ 1.0 n \approx 1.0 n ≈ 1.0 ) multiplied by the contact exposure time ( T T T ): ln ⁡ ( N N 0 ) = − k ⋅ C n ⋅ T \ln\left(\frac{N}{N_0}\right) = -k \cdot C^n \cdot T ln ( N 0 ​ N ​ ) = − k ⋅ C n ⋅ T

Under EPA drinking water regulations, this relationship is simplified into the CT Value : C T calc = C × T 10 CT_{\text{calc}} = C \times T_{10} C T calc ​ = C × T 10 ​

C C C = Disinfectant Residual Concentration (mg/L): The measured free or combined chlorine residual in milligrams per liter taken at or before the exit point of the contact basin or pipeline segment.

T 10 T_{10} T 10 ​ = Effective Contact Time (minutes): The minimum contact time (in minutes) that 90% of the water volume remains in the basin under peak hourly flow conditions.

The Inactivation Ratio (IR)

To demonstrate compliance, an operator compares the calculated operational CT ( C T calc CT_{\text{calc}} C T calc ​ ) against the regulatory benchmark value ( C T req CT_{\text{req}} C T req ​ ) published in EPA compliance tables for the specific pathogen, temperature, pH, and residual concentration: Inactivation Ratio (IR) = C T calc C T req \text{Inactivation Ratio (IR)} = \frac{CT_{\text{calc}}}{CT_{\text{req}}} Inactivation Ratio (IR) = C T req ​ C T calc ​ ​ Daily Log Inactivation Achieved = Required Log Target × IR \text{Daily Log Inactivation Achieved} = \text{Required Log Target} \times \text{IR} Daily Log Inactivation Achieved = Required Log Target × IR

If IR ≥ 1.0 \text{IR} \ge 1.0 IR ≥ 1.0 , the disinfection segment meets or exceeds regulatory compliance.

If IR < 1.0 \text{IR} < 1.0 IR < 1.0 , the facility has under-disinfected and is in violation of the treatment technique requirement unless downstream contact basins provide additive credit.

When water flows through multiple disinfection segments in series (e.g., rapid mix basin → \rightarrow → sedimentation basin → \rightarrow → clearwell → \rightarrow → transmission pipeline), the system calculates total compliance by summing individual inactivation ratios: Total Daily Inactivation Ratio = ∑ IR i = IR 1 + IR 2 + IR 3 + ⋯ ≥ 1.0 \text{Total Daily Inactivation Ratio} = \sum \text{IR}_i = \text{IR}_1 + \text{IR}_2 + \text{IR}_3 + \dots \ge 1.0 Total Daily Inactivation Ratio = ∑ IR i ​ = IR 1 ​ + IR 2 ​ + IR 3 ​ + ⋯ ≥ 1.0

Basin Hydraulics: Short-Circuiting & Baffling Classifications

In a hypothetical, ideal hydraulic system, water moves through a contact chamber in a uniform, flat velocity profile known as plug flow , where every parcel of water resides in the basin for the exact same duration.

Theoretical Hydraulic Detention Time ( T d T_d T d ​ )

Theoretical detention time reflects idealized hydraulic retention based purely on geometric basin volume and flow rate: T d = Basin Volume (gallons) Flow Rate (gallons per minute, gpm) T_d = \frac{\text{Basin Volume (gallons)}}{\text{Flow Rate (gallons per minute, gpm)}} T d ​ = Flow Rate (gallons per minute, gpm) Basin Volume (gallons) ​ T d = Volume (gal) Flow (MGD) × 1 , 000 , 000 / 1 , 440 T_d = \frac{\text{Volume (gal)}}{\text{Flow (MGD)} \times 1,000,000 / 1,440} T d ​ = Flow (MGD) × 1 , 000 , 000/1 , 440 Volume (gal) ​

The Problem of Short-Circuiting

In actual clearwells and contact tanks, plug flow never exists naturally. Internal dead zones, stagnation pockets, density currents caused by temperature or salinity differentials, wind-induced surface circulation, and high-velocity inlet jetting cause a substantial portion of the incoming water to bypass the bulk volume and travel directly to the effluent weir in a fraction of T d T_d T d ​ . This phenomenon is called short-circuiting .

If an operator relied on theoretical detention time ( T d T_d T d ​ ) for CT calculations, short-circuiting water would be severely under-disinfected, allowing viable Giardia cysts and viruses to pass directly into the distribution system.

Defining T 10 T_{10} T 10 ​

To protect public health against short-circuiting, the EPA mandates that contact time be evaluated using T 10 T_{10} T 10 ​ :

Note

T 10 T_{10} T 10 ​ Definition : The time required for 10% of a chemical tracer (or water volume) entering a basin to exit at the discharge point. In other words, 90% of the water molecules remain inside the basin for a time equal to or greater than T 10 T_{10} T 10 ​ .

EPA Baffling Factors ( B F BF BF )

Where empirical tracer studies have not yet been conducted, regulatory agencies permit estimating T 10 T_{10} T 10 ​ by applying an empirical Baffling Factor ( B F BF BF ) to the theoretical detention time: T 10 = T d × Baffling Factor (BF) T_{10} = T_d \times \text{Baffling Factor (BF)} T 10 ​ = T d ​ × Baffling Factor (BF)

Baffling Condition Baffling Factor ( B F BF BF ) Physical Basin Layout & Internal Flow Characteristics

Unbaffled / Poor 0.1 None. Single inlet and outlet points with no internal flow direction walls. Severe short-circuiting, large stagnant circulation zones, high-velocity jetting. Typical of open circular storage tanks or basic rectangular basins.

Poor 0.3 Single intra-basin baffle, perforated inlet wall without diffuser vanes, or wide rectangular basin with unguided flow. Moderate short-circuiting.

Average 0.5 Intermediate baffling. Submerged baffle walls, multi-pass baffling with some dead space, or baffled inlet and outlet structures.

Superior 0.7 Advanced serpentine (labyrinth) baffling with multi-pass directional channels (length-to-width ratio ≥ 10 : 1 \ge 10:1 ≥ 10 : 1 ). Slotted diffusion inlet walls that eliminate jetting. Dead space is minimal ( < 10 % <10\% < 10% ).

Perfect Plug Flow 1.0 Extremely long pipelines, concentric pipe contactors, or serpentine tubular reactors (length-to-width ratio ≥ 50 : 1 \ge 50:1 ≥ 50 : 1 ). Zero short-circuiting; all fluid parcels have identical residence time.

Empirical Determination of T 10 T_{10} T 10 ​ via Chemical Tracer Studies

Under ADEQ engineering review guidelines, large municipal utilities verify basin baffling factors by performing on-site chemical tracer testing rather than relying on assumed default factors.

Tracer Testing Methodology

Tracer Selection: A non-reactive, conservative chemical tracer is dosed into the basin inlet. Approved tracers include fluoride ion ( F − F^- F − ) dosed via hydrofluorosilicic acid (carefully monitored to avoid exceeding the 4.0 mg/L primary MCL), sodium chloride ( N a C l NaCl N a Cl ) monitored via continuous electrical conductivity, or lithium chloride ( L i C l LiCl L i Cl ).

Step-Dose Injection vs. Slug (Pulse) Injection:

Step-Dose Method: Tracer is injected continuously at a steady concentration ( C 0 C_0 C 0 ​ ). The effluent concentration ( C C C ) is recorded at regular intervals until it matches C 0 C_0 C 0 ​ . A breakthrough curve of C / C 0 C/C_0 C / C 0 ​ versus time is plotted. The time at which C / C 0 = 0.10 C/C_0 = 0.10 C / C 0 ​ = 0.10 (10% breakthrough) is the empirical T 10 T_{10} T 10 ​ .

Pulse (Slug) Method: A single discrete mass of tracer is injected instantaneously at the inlet. Effluent concentration is monitored until the entire tracer cloud discharges. The concentration curve is integrated to generate a cumulative residence time distribution; the time where 10% of the total mass has discharged represents T 10 T_{10} T 10 ​ .

The Peak Hourly Flow Mandate: Federal and ADEQ rules dictate that tracer studies must be evaluated under the peak hourly flow rate ( Q peak Q_{\text{peak}} Q peak ​ ) of the operating day. Using average daily flow ( Q avg Q_{\text{avg}} Q avg ​ ) is strictly prohibited for compliance determination because peak flows generate the highest velocities and shortest retention times, representing the facility's period of greatest microbial vulnerability.

Loading diagram... Clearwell Baffling Architecture, Short-Circuiting, and T₁₀ Tracer Breakthrough

Environmental Drivers: Water Temperature and pH

Pathogen inactivation kinetics are profoundly influenced by two environmental parameters: water temperature and water pH .

Water Temperature Impact

Chemical reaction rates decrease significantly as temperature drops, following the Arrhenius principle (reaction velocity decreases by roughly 50% for every 10°C drop in temperature). Cold water slows down the rate at which chlorine molecules cross pathogen cell membranes and disrupts metabolic enzyme inactivation. Consequently, colder water requires dramatically higher CT values to achieve an identical log-inactivation.

Water pH Impact

As detailed in Section 6.1, higher water pH shifts the chemical equilibrium away from hypochlorous acid ( H O C l HOCl H OCl ) toward the hypochlorite ion ( O C l − OCl^- OC l − ). Because O C l − OCl^- OC l − is 80 to 100 times less germicidal than H O C l HOCl H OCl , higher water pH drastically increases the required CT value for free chlorine.

EPA CT Table Reference Values for Giardia Inactivation

The following data excerpted from EPA compliance tables illustrates the dramatic impact of temperature and pH on the required CT for 0.5-log Giardia lamblia inactivation using free chlorine at a residual concentration of 1.0 mg/L :

Water pH Required CT at 0.5°C (33°F) Required CT at 10.0°C (50°F) Required CT at 20.0°C (68°F) Required CT at 25.0°C (77°F)

  • pH 6.5 35 mg·min/L 17 mg·min/L 9 mg·min/L 6 mg·min/L
  • pH 7.0 42 mg·min/L 21 mg·min/L 11 mg·min/L 7 mg·min/L
  • pH 7.5 50 mg·min/L 25 mg·min/L 13 mg·min/L 8 mg·min/L
  • pH 8.0 61 mg·min/L 30 mg·min/L 15 mg·min/L 10 mg·min/L
  • pH 8.5 73 mg·min/L 37 mg·min/L 19 mg·min/L 12 mg·min/L

Warning

Seasonal Operational Shift in Arizona : During northern Arizona winters (e.g., Flagstaff, Show Low, Verde Valley) or winter runoff events, surface water temperatures drop below 5°C to 10°C. If raw water pH remains elevated (~8.0), the required CT more than quadruples compared to summer operations. Operators must proactively boost chlorine dosage or lower filtration throughput to ensure T 10 T_{10} T 10 ​ contact time remains sufficient.

Step-by-Step Operator Compliance Math Example

Problem Statement: A conventional water treatment plant in central Arizona treats surface water at a peak hourly flow rate of 8.64 MGD . Finished water passes through an on-site rectangular clearwell with a total storage volume of 450,000 gallons . The clearwell is equipped with serpentine multi-pass baffle walls classified as superior baffling ( B F = 0.7 BF = 0.7 BF = 0.7 ) .

Water quality monitoring at the clearwell discharge records:

  • Water Temperature: 10°C
  • Water pH: 7.5
  • Effluent Free Chlorine Residual ( C C C ): 1.2 mg/L
  • EPA CT Table Requirement for 0.5-log Giardia (at 10°C, pH 7.5, C = 1.2 C = 1.2 C = 1.2 mg/L): 26 mg·min/L
  • EPA CT Table Requirement for 2.0-log Enteric Viruses (at 10°C, pH 7.5): 6 mg·min/L

Calculation Steps:

Convert Peak Flow to Gallons Per Minute (gpm): Q = 8.64 MGD × 1 , 000 , 000 gal/MG 1 , 440 min/day = 6 , 000 gpm Q = \frac{8.64 \text{ MGD} \times 1,000,000 \text{ gal/MG}}{1,440 \text{ min/day}} = 6,000 \text{ gpm} Q = 1 , 440 min/day 8.64 MGD × 1 , 000 , 000 gal/MG ​ = 6 , 000 gpm

Calculate Theoretical Detention Time ( T d T_d T d ​ ): T d = Volume Q = 450 , 000 gal 6 , 000 gpm = 75.0 minutes T_d = \frac{\text{Volume}}{Q} = \frac{450,000 \text{ gal}}{6,000 \text{ gpm}} = 75.0 \text{ minutes} T d ​ = Q Volume ​ = 6 , 000 gpm 450 , 000 gal ​ = 75.0 minutes

Calculate Effective Contact Time ( T 10 T_{10} T 10 ​ ): T 10 = T d × Baffling Factor = 75.0 min × 0.7 = 52.5 minutes T_{10} = T_d \times \text{Baffling Factor} = 75.0 \text{ min} \times 0.7 = 52.5 \text{ minutes} T 10 ​ = T d ​ × Baffling Factor = 75.0 min × 0.7 = 52.5 minutes

Calculate Operational C T calc CT_{\text{calc}} C T calc ​ : C T calc = C × T 10 = 1.2 mg/L × 52.5 min = 63.0 mg ⋅ min/L CT_{\text{calc}} = C \times T_{10} = 1.2 \text{ mg/L} \times 52.5 \text{ min} = 63.0 \text{ mg}\cdot\text{min/L} C T calc ​ = C × T 10 ​ = 1.2 mg/L × 52.5 min = 63.0 mg ⋅ min/L

Evaluate Inactivation Ratios (IR): IR Giardia = C T calc C T req = 63.0 mg ⋅ min/L 26.0 mg ⋅ min/L = 2.42 \text{IR}_{\text{Giardia}} = \frac{CT_{\text{calc}}}{CT_{\text{req}}} = \frac{63.0 \text{ mg}\cdot\text{min/L}}{26.0 \text{ mg}\cdot\text{min/L}} = \mathbf{2.42} IR Giardia ​ = C T req ​ C T calc ​ ​ = 26.0 mg ⋅ min/L 63.0 mg ⋅ min/L ​ = 2.42 IR Virus = C T calc C T req = 63.0 mg ⋅ min/L 6.0 mg ⋅ min/L = 10.50 \text{IR}_{\text{Virus}} = \frac{CT_{\text{calc}}}{CT_{\text{req}}} = \frac{63.0 \text{ mg}\cdot\text{min/L}}{6.0 \text{ mg}\cdot\text{min/L}} = \mathbf{10.50} IR Virus ​ = C T req ​ C T calc ​ ​ = 6.0 mg ⋅ min/L 63.0 mg ⋅ min/L ​ = 10.50

Conclusion: Because both Inactivation Ratios exceed 1.0 ( IR Giardia = 2.42 ≥ 1.0 \text{IR}_{\text{Giardia}} = 2.42 \ge 1.0 IR Giardia ​ = 2.42 ≥ 1.0 and IR Virus = 10.50 ≥ 1.0 \text{IR}_{\text{Virus}} = 10.50 \ge 1.0 IR Virus ​ = 10.50 ≥ 1.0 ), the disinfection process fully satisfies ADEQ and federal SWTR requirements.