Study guide

Thermodynamics of Steam & Steam Tables

SOPEEC 4th Class Power Engineer Part 4A — Free Study Guide 2026 Exam

Track your progress as you read

Finished sections get a check mark.

1 Examination and Mechanics Foundations

Examination, Certification and Study Method Applied Mathematics & Units of Measurement Moments, Free-Body Diagrams and Equilibrium Scalars, Graphical Vectors and Force Components

2 Motion, Energy and Plant Drives

Simple Machines and Mechanical Advantage Kinematics and Linear Motion Work, Pressure, Power and Mechanical Energy Dry Friction, Sliding Loads and Friction Power Stress, Strain, Material Behaviour and Safety Factors Belts, Gears, Couplings and Transmitted Power

3 Heat, Thermodynamic Laws and Steam

Heat, Temperature, and Thermal Expansion Thermodynamic Laws and Ideal Gas Calculations Conduction, Convection and Radiation Heat Exchanger Construction, Balances and Operation Thermodynamics of Steam & Steam Tables

4 Chemistry of Plant Fluids

Chemical Principles for Power Engineers

5 Legislation, Canadian Standards and ASME Codes

Jurisdictional Acts, Regulations and Plant Responsibilities Canadian Standards, Registration and Refrigerant Safety ASME Construction, Materials, Examination and Welding Codes

6 Plant Safety and Fire Protection

Plant Hazard Assessment, Worker Rights and PPE Safety Programs, Permits, Isolation and Confined Spaces WHMIS, SDSs and Dangerous-Material Handling Fire Prevention, Detection, Fixed Systems and Emergency Plans Fire Classes, Extinguishing Agents and Portable Response

7 Environment and Plant Emissions

Plant Environmental Impacts, Approvals and Monitoring Gaseous Emissions, Controls and Plant Noise Liquid and Solid Wastes, Containment and Spill Response

8 Materials, Welding and Examination

Ferrous and Nonferrous Materials, Alloys and Heat Treatment Welding Processes, Discontinuities and Hydrogen Control Material Tests and Weld Examination Methods

9 Piping, Valves and Drainage

Piping Dimensions, Materials, Joints, Expansion and Supports Industrial Valves, Non-Return Devices and Reducing Stations Steam Traps, Drainage, Separators and Water Hammer

10 Electrical Principles and Plant Power

Electrical Quantities, DC Circuits, Power and Energy AC Waveforms, Reactance and Power Factor Magnetic Circuits, Electromagnets and Induction Electrical Meter Designs, Connections and Interpretation AC and DC Motors, Generators and Three-Phase Connections Transformer Ratios, Losses, Cooling and Ratings Electrical Distribution, Protection and Station DC Systems

11 Process Measurements and Control Systems

Pressure Sensors, Transmitters and Impulse Connections Mechanical Thermometers, RTDs and Thermocouples Direct and Inferential Liquid-Level Measurement Flow, Humidity and Composition Instruments Control-System Purpose, Feedback and Controller Modes Transmitters, Recorders, Signals and Final Control Elements Boiler Programming, Flame Supervision and Functional Tests Electronic Signal Conditioning, Logic and Digital Controllers Relays, Contactors, Starter Circuits and Electrical Interlocks

12 Sketches, Diagrams and Operating Communication

Equipment Sketches and Plant Line Tracing Plant Diagrams, P&IDs and Instrument Tags Radios, Alarms, Records and Shift Handover

13 Boiler Development and Construction

Boiler Development, Components and Configurations Firetube Designs, Gas Passes, Stays and Bracing Watertube Circulation, Drums and Heat-Recovery Surfaces Resistance-Element and Electrode Boilers Sectional, Coil, Finned-Tube and Condensing Heating Boilers Power and Heating Boiler Code Scopes and Protective Functions

14 Combustion, Fuel, Draft, Feedwater, Blowdown and Cleaning

Combustion Conditions, Air Supply and Flue-Gas Analysis Gas, Liquid and Solid Boiler Fuel Systems Natural, Forced, Induced and Balanced Draft Open and Pressurized Feedwater Systems Continuous and Bottom Blowdown, Discharge and Balances Fireside Deposits, Sootblowers and Offline Cleaning

Thermodynamics of Steam & Steam Tables

Key Takeaways Explain This Topic AI

Steam generation at constant pressure transitions through five distinct thermodynamic states: subcooled liquid, saturated liquid, wet steam, dry saturated steam, and superheated steam.

Saturation temperature (T_sat) is uniquely governed by saturation pressure (P_sat); as boiler pressure increases, saturation boiling temperature rises while latent heat of vaporization (h_fg) decreases.

Steam tables publish specific volume, enthalpy, and entropy using standard subscripts: f (saturated liquid), g (dry saturated vapor), and fg (phase change latent property).

Wet steam enthalpy and volume are calculated via dryness fraction (x): h_x = h_f + x·h_fg and v_x ≈ x·v_g, where x represents the vapor mass fraction.

Superheated steam is above saturation temperature at its pressure; it can improve cycle performance and reduce turbine moisture.

Last updated: October 2026

Water and steam serve as the premier thermal working fluid in commercial power generation, industrial process heating, and district energy plants. Water is non-toxic, inexpensive, chemically stable, and possesses an extraordinary latent heat capacity ( 2257 kJ/kg 2257\text{ kJ/kg} 2257 kJ/kg at atmospheric pressure). To operate, control, and test steam boilers safely and efficiently, the 4th Class Power Engineer must master the thermodynamic phases of steam generation, understand steam table nomenclature, and perform accurate enthalpy balances.

1. Thermodynamic Phases of Steam Generation

Consider 1 kg 1\text{ kg} 1 kg of liquid water at 20 ∘ C 20^\circ\text{C} 2 0 ∘ C contained in a cylinder beneath a weighted piston that maintains a constant operating pressure of 1000 kPa 1000\text{ kPa} 1000 kPa ( 1.0 MPa 1.0\text{ MPa} 1.0 MPa ). As thermal energy is continuously added from an external heat source, the substance progresses through five distinct thermodynamic regimes: PROGRESSION OF STEAM GENERATION

  • 1. Subcooled Liquid : T < T_sat (Sensible heat raises water temperature)
  • 2. Saturated Liquid : T = T_sat, x = 0 (Boiling threshold; zero vapor present)
  • 3. Wet Saturated Steam : T = T_sat, 0 < x < 1 (Two-phase boiling mixture; absorbing h_fg)
  • 4. Dry Saturated Steam : T = T_sat, x = 1.0 (100% dry vapor; last water droplet gone)
  • 5. Superheated Steam : T > T_sat (Sensible heat added to vapor; gas behavior)

Subcooled (Compressed) Liquid: The liquid temperature is below the saturation boiling temperature corresponding to the system pressure ( T < T sat T < T_{\text{sat}} T < T sat ​ ). Any heat added is sensible heat , causing a direct temperature rise without vapor formation.

Saturated Liquid: The water reaches the exact boiling temperature for 1000 kPa 1000\text{ kPa} 1000 kPa ( T sat ≈ 179.89 ∘ C T_{\text{sat}} \approx 179.89^\circ\text{C} T sat ​ ≈ 179.8 9 ∘ C ). The liquid contains the saturated-liquid enthalpy at that pressure ( h f h_f h f ​ ). The addition of any further heat causes immediate vaporization without any increase in temperature. The dryness fraction is x = 0 x = 0 x = 0 .

Wet Saturated Steam: A two-phase equilibrium mixture of boiling water droplets and saturated vapor. The temperature remains locked at T sat = 179.89 ∘ C T_{\text{sat}} = 179.89^\circ\text{C} T sat ​ = 179.8 9 ∘ C while the mixture absorbs latent heat of vaporization ( h f g h_{fg} h f g ​ ). The dryness fraction ranges between 0 < x < 1.0 0 < x < 1.0 0 < x < 1.0 .

Dry Saturated Steam: The exact instant the final droplet of moisture vaporizes into steam at T sat T_{\text{sat}} T sat ​ ( x = 1.0 x = 1.0 x = 1.0 ). The steam contains 100 % 100\% 100% vapor by mass. Any removal of heat causes immediate condensation back into liquid; any addition of heat causes superheating.

Superheated Steam: Steam heated to a temperature above its saturation boiling point ( T sup > T sat T_{\text{sup}} > T_{\text{sat}} T sup ​ > T sat ​ ) at the prevailing pressure. Superheated steam contains zero moisture droplets and behaves increasingly like an ideal gas. It can lose thermal energy in piping without condensing until its temperature drops back to T sat T_{\text{sat}} T sat ​ .

2. Saturation Pressure and Saturation Temperature

Boiling cannot initiate until the liquid water's internal vapor pressure equals the surrounding external pressure. Consequently, saturation temperature ( T sat T_{\text{sat}} T sat ​ ) is directly linked to saturation pressure ( P sat P_{\text{sat}} P sat ​ ) :

Saturation Pressure P P P (Absolute) Saturation Temperature T sat T_{\text{sat}} T sat ​ ( ∘ C ^\circ\text{C} ∘ C ) Latent Heat h f g h_{fg} h f g ​ ( kJ/kg \text{kJ/kg} kJ/kg ) Specific Volume of Vapor v g v_g v g ​ ( m 3 / kg \text{m}^3/\text{kg} m 3 / kg )

101.325 kPa 101.325\text{ kPa} 101.325 kPa (Atmospheric) 100.00 100.00 100.00 2257.0 2257.0 2257.0 1.6730 1.6730 1.6730

500 kPa 500\text{ kPa} 500 kPa ( 0.5 MPa 0.5\text{ MPa} 0.5 MPa ) 151.84 151.84 151.84 2107.9 2107.9 2107.9 0.3748 0.3748 0.3748

1000 kPa 1000\text{ kPa} 1000 kPa ( 1.0 MPa 1.0\text{ MPa} 1.0 MPa ) 179.89 179.89 179.89 2014.4 2014.4 2014.4 0.1943 0.1943 0.1943

2000 kPa 2000\text{ kPa} 2000 kPa ( 2.0 MPa 2.0\text{ MPa} 2.0 MPa ) 212.38 212.38 212.38 1889.8 1889.8 1889.8 0.0996 0.0996 0.0996

5000 kPa 5000\text{ kPa} 5000 kPa ( 5.0 MPa 5.0\text{ MPa} 5.0 MPa ) 263.94 263.94 263.94 1639.7 1639.7 1639.7 0.0394 0.0394 0.0394

10000 kPa 10000\text{ kPa} 10000 kPa ( 10.0 MPa 10.0\text{ MPa} 10.0 MPa ) 311.00 311.00 311.00 1317.6 1317.6 1317.6 0.0180 0.0180 0.0180

22064 kPa 22064\text{ kPa} 22064 kPa (Critical Point) 373.95 373.95 373.95 0.0 0.0 0.0 0.00311 0.00311 0.00311 ( v f = v g v_f = v_g v f ​ = v g ​ )

Critical Point Dynamics

Notice two crucial thermodynamic trends as boiler pressure increases:

Boiling temperature ( T sat T_{\text{sat}} T sat ​ ) increases: The required water saturation temperature increases; furnace temperature and firing conditions are separate design variables.

Latent heat of vaporization ( h f g h_{fg} h f g ​ ) decreases: At higher pressures, water molecules are packed closer together under heavy compression, requiring less additional energy to transition into vapor. At the critical point ( 22.064 MPa 22.064\text{ MPa} 22.064 MPa and 373.95 ∘ C 373.95^\circ\text{C} 373.9 5 ∘ C ), liquid and vapour become indistinguishable; there is no separate boiling interface or latent heat at the critical point.

3. Steam Table Architecture & Nomenclature

Thermodynamic steam tables (such as ASME Steam Tables) compile empirical measurements of water and steam properties across three primary tables:

Table 1: Saturation Properties by Temperature (indexed by T sat T_{\text{sat}} T sat ​ in ∘ C ^\circ\text{C} ∘ C )

Table 2: Saturation Properties by Pressure (indexed by P sat P_{\text{sat}} P sat ​ in kPa \text{kPa} kPa or MPa \text{MPa} MPa )

  • Table 3: Superheated Steam Properties (indexed by both pressure and temperature)
  • Property Subscript Notation

Standard international power engineering notation uses distinct subscripts:

v f v_f v f ​ — Specific Volume of Saturated Liquid ( [ m 3 / kg ] [\text{m}^3/\text{kg}] [ m 3 / kg ] ): The volume occupied by 1 kg 1\text{ kg} 1 kg of liquid water at saturation temperature (typically 0.00100 m 3 / kg 0.00100\text{ m}^3/\text{kg} 0.00100 m 3 / kg to 0.00125 m 3 / kg 0.00125\text{ m}^3/\text{kg} 0.00125 m 3 / kg ).

v g v_g v g ​ — Specific Volume of Dry Saturated Vapor ( [ m 3 / kg ] [\text{m}^3/\text{kg}] [ m 3 / kg ] ): The volume occupied by 1 kg 1\text{ kg} 1 kg of pure dry steam vapor. At atmospheric pressure, v g = 1.673 m 3 / kg v_g = 1.673\text{ m}^3/\text{kg} v g ​ = 1.673 m 3 / kg , meaning water expands by over 1600 1600 1600 times upon boiling!

v f g v_{fg} v f g ​ — Volume Change of Evaporation: v f g = v g − v f v_{fg} = v_g - v_f v f g ​ = v g ​ − v f ​ .

h f h_f h f ​ — Specific Enthalpy of Saturated Liquid ( [ kJ / kg ] [\text{kJ}/\text{kg}] [ kJ / kg ] ): The sensible heat required to raise 1 kg 1\text{ kg} 1 kg of water from the reference point ( 0.01 ∘ C 0.01^\circ\text{C} 0.0 1 ∘ C triple point, where saturated-liquid internal energy and entropy are assigned zero by the conventional reference) to T sat T_{\text{sat}} T sat ​ .

h f g h_{fg} h f g ​ — Latent Heat of Evaporation ( [ kJ / kg ] [\text{kJ}/\text{kg}] [ kJ / kg ] ): The heat energy required to evaporate 1 kg 1\text{ kg} 1 kg of saturated water into dry saturated steam at constant pressure.

h g h_g h g ​ — Specific Enthalpy of Dry Saturated Steam ( [ kJ / kg ] [\text{kJ}/\text{kg}] [ kJ / kg ] ): Total heat content of dry saturated vapor: h g = h f + h f g h_g = h_f + h_{fg} h g ​ = h f ​ + h f g ​

s f , s f g , s g s_f, s_{fg}, s_g s f ​ , s f g ​ , s g ​ — Specific Entropy ( [ kJ / ( kg ⋅ K ) ] [\text{kJ}/(\text{kg}\cdot\text{K})] [ kJ / ( kg ⋅ K )] ): Thermodynamic measure of molecular disorder used for turbine isentropic expansion calculations.

u f , u g u_f, u_g u f ​ , u g ​ — Specific Internal Energy ( [ kJ / kg ] [\text{kJ}/\text{kg}] [ kJ / kg ] ): Derived from enthalpy by subtracting flow work: u = h − P v u = h - P v u = h − P v .

4. Wet Steam Calculations: Dryness Fraction and Quality

In industrial boiler drums, steam generation is turbulent, and bubbles bursting at the water line carry entrained liquid droplets into the steam space. Steam-separation equipment is intended to minimize carryover; a saturated outlet may contain moisture and its quality must be assessed.

Dryness Fraction (Steam Quality, x x x )

The dryness fraction ( x x x ) is the proportion of dry steam vapor by mass in a wet steam mixture: x = m vapor m total = m vapor m vapor + m liquid x = \frac{m_{\text{vapor}}}{m_{\text{total}}} = \frac{m_{\text{vapor}}}{m_{\text{vapor}} + m_{\text{liquid}}} x = m total ​ m vapor ​ ​ = m vapor ​ + m liquid ​ m vapor ​ ​

  • Saturated liquid: x = 0 x = 0 x = 0
  • Dry saturated steam: x = 1.0 x = 1.0 x = 1.0

Wet steam: 0 < x < 1.0 0 < x < 1.0 0 < x < 1.0 (e.g., x = 0.95 x = 0.95 x = 0.95 indicates 95 % 95\% 95% dry vapor and 5 % 5\% 5% entrained moisture by mass).

Wetness Fraction / Moisture Content ( y y y ): y = 1 − x y = 1 - x y = 1 − x .

Thermodynamic Properties of Wet Steam

Because only the vapor portion has absorbed the latent heat of vaporization, the enthalpy of wet steam ( h x h_x h x ​ ) is calculated as: h x = h f + x h f g [ kJ / kg ] h_x = h_f + x h_{fg} \quad [\text{kJ}/\text{kg}] h x ​ = h f ​ + x h f g ​ [ kJ / kg ]

The specific volume of wet steam ( v x v_x v x ​ ) is: v x = ( 1 − x ) v f + x v g v_x = (1 - x) v_f + x v_g v x ​ = ( 1 − x ) v f ​ + x v g ​

Because v f v_f v f ​ is negligible compared to v g v_g v g ​ at low and medium operating pressures, power engineers simplify this on examinations to: v x ≈ x v g [ m 3 / kg ] v_x \approx x v_g \quad [\text{m}^3/\text{kg}] v x ​ ≈ x v g ​ [ m 3 / kg ]

5. Superheated Steam and the Degree of Superheat

Superheated steam is steam that has absorbed sensible heat beyond dry saturated vapor at the prevailing pressure, elevating its temperature above T sat T_{\text{sat}} T sat ​ .

Degree of Superheat

The degree of superheat is the temperature rise above saturation temperature: Degree of Superheat = T sup − T sat \text{Degree of Superheat} = T_{\text{sup}} - T_{\text{sat}} Degree of Superheat = T sup ​ − T sat ​

Example: If a steam boiler operates at 2000 kPa 2000\text{ kPa} 2000 kPa ( T sat = 212.38 ∘ C T_{\text{sat}} = 212.38^\circ\text{C} T sat ​ = 212.3 8 ∘ C ) and the superheater outlet temperature is 350 ∘ C 350^\circ\text{C} 35 0 ∘ C : Degree of Superheat = 350 ∘ C − 212.38 ∘ C = 137.62 ∘ C \text{Degree of Superheat} = 350^\circ\text{C} - 212.38^\circ\text{C} = 137.62^\circ\text{C} Degree of Superheat = 35 0 ∘ C − 212.3 8 ∘ C = 137.6 2 ∘ C

Enthalpy of Superheated Steam ( h sup h_{\text{sup}} h sup ​ )

Standard Method: Look up directly in Table 3 (Superheated Steam Tables) by locating the intersection of operating pressure and steam temperature.

Approximation Formula: If superheated steam tables are unavailable, enthalpy can be estimated using the mean specific heat of superheated steam ( c p c_p c p ​ ): h sup = h g + c p ( T sup − T sat ) h_{\text{sup}} = h_g + c_p (T_{\text{sup}} - T_{\text{sat}}) h sup ​ = h g ​ + c p ​ ( T sup ​ − T sat ​ )

(Where c p c_p c p ​ typically averages 2.1 2.1 2.1 to 2.5 kJ/(kg ⋅ ∘ C) 2.5\text{ kJ/(kg}\cdot^\circ\text{C)} 2.5 kJ/(kg ⋅ ∘ C) ) .

Why Power Plants Superheat Steam

Reduces Moisture Erosion: When saturated steam expands through turbine blades, work extraction causes partial condensation. High-velocity liquid droplets impact turbine blades at supersonic speeds, causing severe pitting, erosion, and catastrophic failure. Superheating reduces exhaust moisture but does not guarantee dry steam throughout expansion.

Maximizes Thermodynamic Cycle Efficiency: According to the Carnot and Rankine principles, increasing the peak cycle temperature of heat addition directly boosts thermodynamic efficiency (the Carnot expression gives a reversible reservoir-temperature limit, not the actual Rankine-cycle efficiency).

Reduces Pipe Condensation: Superheated steam can lose some sensible energy before reaching saturation and forming condensate, reducing steam trap loading and water hammer hazards.

6. Steam Table Reading & Linear Interpolation

When a measured plant pressure or temperature falls between published rows in a steam table, engineers use linear interpolation : y = y 1 + ( x − x 1 x 2 − x 1 ) ( y 2 − y 1 ) y = y_1 + \left(\frac{x - x_1}{x_2 - x_1}\right)(y_2 - y_1) y = y 1 ​ + ( x 2 ​ − x 1 ​ x − x 1 ​ ​ ) ( y 2 ​ − y 1 ​ )

Where:

x x x = given intermediate value (e.g., pressure of 1450 kPa 1450\text{ kPa} 1450 kPa )

x 1 , x 2 x_1, x_2 x 1 ​ , x 2 ​ = adjacent tabular values in the steam table ( 1400 kPa 1400\text{ kPa} 1400 kPa and 1500 kPa 1500\text{ kPa} 1500 kPa )

  • y 1 , y 2 y_1, y_2 y 1 ​ , y 2 ​ = known tabular properties at x 1 x_1 x 1 ​ and x 2 x_2 x 2 ​
  • y y y = desired property value
  • 7. Boiler Heat Duty and Feedwater Balance

The total thermal heat duty (power output, Q ˙ \dot{Q} Q ˙ ​ ) required to generate steam from incoming boiler feedwater is: Q ˙ = m ˙ s ( h steam − h feedwater ) \dot{Q} = \dot{m}_s (h_{\text{steam}} - h_{\text{feedwater}}) Q ˙ ​ = m ˙ s ​ ( h steam ​ − h feedwater ​ )

Where:

Q ˙ \dot{Q} Q ˙ ​ = boiler thermal heat duty in kilowatts ( kW = kJ/s \text{kW} = \text{kJ/s} kW = kJ/s ) or megawatts ( MW \text{MW} MW )

m ˙ s \dot{m}_s m ˙ s ​ = steam generation mass flow rate in kg/s \text{kg/s} kg/s (if given in kg/h \text{kg/h} kg/h , divide by 3600 s/h 3600\text{ s/h} 3600 s/h )

h steam h_{\text{steam}} h steam ​ = enthalpy of steam leaving boiler ( h x h_x h x ​ , h g h_g h g ​ , or h sup h_{\text{sup}} h sup ​ in kJ/kg \text{kJ/kg} kJ/kg )

h feedwater h_{\text{feedwater}} h feedwater ​ = enthalpy of feedwater entering boiler (approx. equal to liquid enthalpy h f h_f h f ​ at feedwater temperature T fw T_{\text{fw}} T fw ​ , or c w × T fw = 4.187 × T fw c_w \times T_{\text{fw}} = 4.187 \times T_{\text{fw}} c w ​ × T fw ​ = 4.187 × T fw ​ )

  • 8. Worked Engineering Calculations
  • Example 1: Wet Steam Enthalpy and Volume Calculation

Problem: A firetube boiler produces saturated steam at an absolute pressure of 1500 kPa 1500\text{ kPa} 1500 kPa . A suitable quality measurement gives a dryness fraction of x = 0.95 x = 0.95 x = 0.95 . Using the following steam table data for 1500 kPa 1500\text{ kPa} 1500 kPa :

  • T sat = 198.30 ∘ C T_{\text{sat}} = 198.30^\circ\text{C} T sat ​ = 198.3 0 ∘ C
  • v f = 0.0011539 m 3 / kg v_f = 0.0011539\text{ m}^3/\text{kg} v f ​ = 0.0011539 m 3 / kg
  • v g = 0.1317023 m 3 / kg v_g = 0.1317023\text{ m}^3/\text{kg} v g ​ = 0.1317023 m 3 / kg
  • h f = 844.72 kJ/kg h_f = 844.72\text{ kJ/kg} h f ​ = 844.72 kJ/kg
  • h f g = 1946.29 kJ/kg h_{fg} = 1946.29\text{ kJ/kg} h f g ​ = 1946.29 kJ/kg
  • h g = 2791.01 kJ/kg h_g = 2791.01\text{ kJ/kg} h g ​ = 2791.01 kJ/kg

Determine:

The specific enthalpy of the wet steam ( h x h_x h x ​ ).

The specific volume of the wet steam ( v x v_x v x ​ ).

The heat required to completely dry 1 kg 1\text{ kg} 1 kg of this wet steam.

Step-by-Step Solution:

Specific enthalpy of wet steam ( h x h_x h x ​ ): h x = h f + x h f g = 844.72 kJ/kg + ( 0.95 ) × ( 1946.29 kJ/kg ) h_x = h_f + x h_{fg} = 844.72\text{ kJ/kg} + (0.95) \times (1946.29\text{ kJ/kg}) h x ​ = h f ​ + x h f g ​ = 844.72 kJ/kg + ( 0.95 ) × ( 1946.29 kJ/kg ) h x = 844.72 + 1848.9755 = 2693.70 kJ/kg h_x = 844.72 + 1848.9755 = 2693.70\text{ kJ/kg} h x ​ = 844.72 + 1848.9755 = 2693.70 kJ/kg

Specific volume of wet steam ( v x v_x v x ​ ): v x = ( 1 − 0.95 ) ( 0.0011539 ) + 0.95 ( 0.1317023 ) = 0.1251749 m 3 / kg v_x = (1-0.95)(0.0011539) + 0.95(0.1317023) = 0.1251749\text{ m}^3/\text{kg} v x ​ = ( 1 − 0.95 ) ( 0.0011539 ) + 0.95 ( 0.1317023 ) = 0.1251749 m 3 / kg

Heat required to dry 1 kg 1\text{ kg} 1 kg of wet steam into dry saturated steam: q dry = h g − h x = 2791.01 kJ/kg − 2693.70 kJ/kg = 97.31 kJ/kg q_{\text{dry}} = h_g - h_x = 2791.01\text{ kJ/kg} - 2693.70\text{ kJ/kg} = 97.31\text{ kJ/kg} q dry ​ = h g ​ − h x ​ = 2791.01 kJ/kg − 2693.70 kJ/kg = 97.31 kJ/kg

(Or equivalently: q dry = ( 1 − x ) h f g = ( 0.05 ) × 1946.29 kJ/kg = 97.31 kJ/kg q_{\text{dry}} = (1 - x) h_{fg} = (0.05) \times 1946.29\text{ kJ/kg} = 97.31\text{ kJ/kg} q dry ​ = ( 1 − x ) h f g ​ = ( 0.05 ) × 1946.29 kJ/kg = 97.31 kJ/kg ) .

Example 2: Boiler Thermal Heat Duty Calculation

Problem: An industrial boiler generates 15 , 000 kg/h 15,000\text{ kg/h} 15 , 000 kg/h of superheated steam at 3000 kPa 3000\text{ kPa} 3000 kPa absolute and 325 ∘ C 325^\circ\text{C} 32 5 ∘ C . Feedwater enters the boiler economizer at 85 ∘ C 85^\circ\text{C} 8 5 ∘ C .

Steam Table Extract:

At 3000 kPa 3000\text{ kPa} 3000 kPa saturated: T sat = 233.86 ∘ C T_{\text{sat}} = 233.86^\circ\text{C} T sat ​ = 233.8 6 ∘ C

Using rounded IAPWS-IF97 properties, take outlet enthalpy as h sup = 3056.37 kJ/kg h_{\text{sup}} = 3056.37\text{ kJ/kg} h sup ​ = 3056.37 kJ/kg ; use the actual approved table and its rounding in an examination.

Approximate feedwater enthalpy using saturated liquid at 85 ∘ C 85^\circ\text{C} 8 5 ∘ C (neglecting the compressed-liquid pressure correction): h f = 355.95 kJ/kg h_f = 355.95\text{ kJ/kg} h f ​ = 355.95 kJ/kg

Determine:

The degree of superheat.

The heat absorbed per kilogram of steam produced.

The boiler thermal duty in kilowatts ( kW \text{kW} kW ) and megawatts ( MW \text{MW} MW ).

Step-by-Step Solution:

Degree of superheat: Δ T sup = T sup − T sat = 325.0 ∘ C − 233.86 ∘ C = 91.14 ∘ C \Delta T_{\text{sup}} = T_{\text{sup}} - T_{\text{sat}} = 325.0^\circ\text{C} - 233.86^\circ\text{C} = 91.14^\circ\text{C} Δ T sup ​ = T sup ​ − T sat ​ = 325. 0 ∘ C − 233.8 6 ∘ C = 91.1 4 ∘ C

Heat absorbed per kilogram of steam: Δ h = h sup − h feedwater = 3056.37 kJ/kg − 355.95 kJ/kg = 2700.42 kJ/kg \Delta h = h_{\text{sup}} - h_{\text{feedwater}} = 3056.37\text{ kJ/kg} - 355.95\text{ kJ/kg} = 2700.42\text{ kJ/kg} Δ h = h sup ​ − h feedwater ​ = 3056.37 kJ/kg − 355.95 kJ/kg = 2700.42 kJ/kg

Steam mass flow rate in kg/s \text{kg/s} kg/s : m ˙ s = 15 , 000 kg/h 3600 s/h = 4.1667 kg/s \dot{m}_s = \frac{15,000\text{ kg/h}}{3600\text{ s/h}} = 4.1667\text{ kg/s} m ˙ s ​ = 3600 s/h 15 , 000 kg/h ​ = 4.1667 kg/s

Boiler thermal heat duty: Q ˙ = m ˙ s × Δ h = ( 4.1667 kg/s ) × ( 2700.42 kJ/kg ) = 11251.8 kW \dot{Q} = \dot{m}_s \times \Delta h = (4.1667\text{ kg/s}) \times (2700.42\text{ kJ/kg}) = 11251.8\text{ kW} Q ˙ ​ = m ˙ s ​ × Δ h = ( 4.1667 kg/s ) × ( 2700.42 kJ/kg ) = 11251.8 kW Q ˙ = 11251.8 kW 1000 kW/MW = 11.25 MW \dot{Q} = \frac{11251.8\text{ kW}}{1000\text{ kW/MW}} = 11.25\text{ MW} Q ˙ ​ = 1000 kW/MW 11251.8 kW ​ = 11.25 MW

Result: The boiler delivers a continuous thermal duty of 11 , 253 kW 11,253\text{ kW} 11 , 253 kW ( 11.25 MW 11.25\text{ MW} 11.25 MW ).

Source notes

Official scope and technical references checked 2026-10-17: Reference 1 ; Reference 2 . Archived DOE handbooks are used for physical principles, not current Canadian legal requirements.

Property formulation: IAPWS-IF97 . Numerical teaching values above use rounded IF97 properties; the specified examination reference and supplied values govern examination arithmetic.