4.2 Combustion Chemistry, Flammability Limits & Ignition Temperatures
TSSA Gas Technician 3 G3
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Safety & Workplace Practices
1.1 Personal Protective Equipment (PPE) & Worksite Hazard Identification 1.2 WHMIS, GHS, Safety Data Sheets (SDS) & Chemical Safety 1.3 Electrical Safety, Lockout/Tagout (LOTO) & Confined Space Awareness
2 Chapter 2: Fasteners, Hand Tools & Power Tools
2.1 Hand Tools for Gas Piping and Mechanical Assembly 2.2 Power Tools, Threading Machines & Mechanical Fasteners
3 Chapter 3: Testing Instruments & Diagnostics
3.1 Pressure Measurement: U-Tube, Inclined & Digital Manometers 3.2 Electrical Multimeters, Combustion Analyzers & Electronic Leak Detectors
4 Chapter 4: Fuel Gas Properties & Combustion Principles
4.1 Chemical & Physical Properties of Natural Gas vs. Propane 4.2 Combustion Chemistry, Flammability Limits & Ignition Temperatures 4.3 Complete vs. Incomplete Combustion, Carbon Monoxide Hazards & Air Requirements
5 Chapter 5: Ontario Acts, Regulations & G.3 Scope of Authority
5.1 Technical Standards and Safety Act & O. Reg. 215/01 Certification 5.2 O. Reg. 211/01, O. Reg. 212/01 & TSSA Code Adoption Documents (CAD) 5.3 Unacceptable Conditions, Warning Notices & Red Tag Procedures
6 Chapter 6: CSA B149 Code Navigation & General Requirements
6.1 CSA B149.1 & CSA B149.2 Scope, Structure & Key Definitions 6.2 General Installation Rules: Instructions, Access, Clearances & Garages (Clause 4)
7 Chapter 7: Introduction to Electricity & Electrical Safety
7.1 Electrical Fundamentals: Ohm's Law, Power & Circuit Configurations 7.2 Line Voltage (120V) vs. Low Voltage (24V), Transformers & Circuit Protection 7.3 Basic Electrical Controls, Switches & Ladder Diagram Schematics
8 Chapter 8: Technical Manuals, Specifications & Architectural Drawings
8.1 Reading Appliance Rating Plates, Certified Manuals & Specifications 8.2 Architectural Blueprints, Mechanical Drawings & Piping Schematics
9 Chapter 9: Customer Relations, Professional Conduct & Documentation
9.1 Professional Communication, Ethics & Customer Service Standards 9.2 Work Orders, Service Documentation & Red Tag Communication
10 Chapter 10: Piping & Tubing Systems: Materials, Joining & Installation
10.1 Piping & Tubing Materials: Steel, Copper, CSST & Plastic 10.2 Pipe Joining Methods: Threading, Flaring, Brazing & Approved Sealants 10.3 Piping Installation: Supports, Hangers, Drip Legs, Dirt Pockets & Valves
11 Chapter 11: Gas Pipe Sizing, Pressure Testing & Purging Procedures
11.1 Gas Pipe & Tubing Sizing Fundamentals (Tables & Pressure Drop) 11.2 Pressure Testing, Leak Testing & the Ontario Test Tag (Clause 6.22) 11.3 Purging Procedures, Safety Protocols & Leak Detection (Clauses 6.23–6.24)
12 Chapter 12: Gas Appliances, Burners & Combustion Air Fundamentals
12.1 Appliance Classifications, Categories (I–IV), Approvals & Clearances 12.2 Atmospheric & Power Burners: Operation, Aeration & Flame Adjustment 12.3 Ignition Systems & Flame Safeguards: Standing Pilot, HSI, DSI, Thermocouples & Flame Rods 12.4 Combustion Air & Basic Venting Requirements (Clause 8)
4.2 Combustion Chemistry, Flammability Limits & Ignition Temperatures
Key Takeaways Explain This Topic AI
The fire tetrahedron requires four elements for self-sustaining combustion: fuel, oxygen, heat (ignition temperature), and an uninhibited chemical chain reaction supported by free radicals.
Balanced stoichiometric oxidation equations are CH 4 + 2 O 2 → CO 2 + 2 H 2 O + Heat \text{CH}_4 + 2\text{O}_2 \rightarrow \text{CO}_2 + 2\text{H}_2\text{O} + \text{Heat} CH 4 + 2 O 2 → CO 2 + 2 H 2 O + Heat for methane (1:2 fuel-to-oxygen ratio) and C 3 H 8 + 5 O 2 → 3 CO 2 + 4 H 2 O + Heat \text{C}_3\text{H}_8 + 5\text{O}_2 \rightarrow 3\text{CO}_2 + 4\text{H}_2\text{O} + \text{Heat} C 3 H 8 + 5 O 2 → 3 CO 2 + 4 H 2 O + Heat for propane (1:5 fuel-to-oxygen ratio).
Commercial heating values are nominal 1,000 BTU/cu ft 1{,}000\text{ BTU/cu ft} 1 , 000 BTU/cu ft ( 37.3 MJ/m 3 37.3\text{ MJ/m}^3 37.3 MJ/m 3 ) for natural gas and 2,500 BTU/cu ft 2{,}500\text{ BTU/cu ft} 2 , 500 BTU/cu ft ( 93.1 MJ/m 3 93.1\text{ MJ/m}^3 93.1 MJ/m 3 ) for propane; propane's higher energy density and pressure demand much smaller orifice drill sizes.
The flammability limits in air by volume are 4.0 % to 15.0 % 4.0\%\text{ to }15.0\% 4.0% to 15.0% for natural gas (ideal ≈ 9.5 % to 10.0 % \approx 9.5\%\text{ to }10.0\% ≈ 9.5% to 10.0% ) and 2.15 % to 9.6 % 2.15\%\text{ to }9.6\% 2.15% to 9.6% for propane (ideal ≈ 4.0 % to 4.2 % \approx 4.0\%\text{ to }4.2\% ≈ 4.0% to 4.2% ).
Auto-ignition temperatures are approximately 1,200 ∘ F 1{,}200^\circ\text{F} 1 , 20 0 ∘ F ( 649 ∘ C 649^\circ\text{C} 64 9 ∘ C ) for natural gas and 920 ∘ F to 1,020 ∘ F 920^\circ\text{F}\text{ to }1{,}020^\circ\text{F} 92 0 ∘ F to 1 , 02 0 ∘ F ( 493 ∘ C to 549 ∘ C 493^\circ\text{C}\text{ to }549^\circ\text{C} 49 3 ∘ C to 54 9 ∘ C ) for propane; stable burner operation requires port velocity to equal flame speed ( 1.2 ft/s 1.2\text{ ft/s} 1.2 ft/s for NG, 1.3 to 1.5 ft/s 1.3\text{ to }1.5\text{ ft/s} 1.3 to 1.5 ft/s for LP).
Last updated: October 2026
Combustion Chemistry, Flammability Limits & Ignition Temperatures
Combustion is a rapid, high-temperature, exothermic oxidation reaction between a fuel hydrocarbon and oxygen that converts chemical potential energy into sensible thermal energy. In Ontario's heating, ventilation, and air conditioning (HVAC) sector, gas technicians certified under Ontario Regulation 215/01 must master combustion thermodynamics to safely configure appliance burners, size gas orifices, adjust air shutters, and avoid explosive or toxic operating defects. This section analyzes the classical combustion triangle and modern fire tetrahedron, explores balanced chemical oxidation equations, evaluates heating values, and defines the operational boundaries of flammability limits, auto-ignition temperatures, and flame propagation speeds under the CSA B149.1 Installation Code.
Principles of Combustion: Triangle vs. Tetrahedron
Historically, combustion was conceptualized as the Fire Triangle , consisting of three essential components:
Fuel: A combustible hydrocarbon in vapor form (methane or propane).
Oxygen: The oxidizer, provided by atmospheric air (which contains ≈ 20.9 % \approx 20.9\% ≈ 20.9% oxygen by volume).
Heat: Sufficient thermal activation energy to elevate the air-fuel mixture to its auto-ignition temperature.
Removing any single leg of the triangle—such as shutting the gas valve, starving the burner of air, or chilling the flame below ignition temperature—extinguishes the fire.
Modern combustion science models combustion using the Fire Tetrahedron , adding a fourth indispensable factor: an Uninhibited Chemical Chain Reaction .
During active combustion, thermal energy dissociates hydrocarbon molecules into highly reactive intermediate free radicals, including atomic hydrogen ( H ∙ \text{H}^\bullet H ∙ ), atomic oxygen ( O ∙ \text{O}^\bullet O ∙ ), and hydroxyl radicals ( OH ∙ \text{OH}^\bullet OH ∙ ). These free radicals collide with adjacent fuel and oxygen molecules, initiating an exothermic chain of self-propagating sub-reactions. If chemical inhibitors (such as dry chemical potassium bicarbonate or halogenated agents) are introduced, they scavenge free radicals, breaking the chain reaction and instantly extinguishing the flame even when fuel, oxygen, and high temperatures remain present.
Balanced Chemical Combustion Equations
When hydrocarbon fuel gas reacts with exactly the theoretical amount of oxygen required with no fuel or oxygen left over, it undergoes stoichiometric (complete) combustion . All carbon atoms oxidize into carbon dioxide ( CO 2 \text{CO}_2 CO 2 ) and all hydrogen atoms convert to water vapor ( H 2 O \text{H}_2\text{O} H 2 O ):
Natural Gas (Methane) CH 4 + 2 O 2 → CO 2 + 2 H 2 O + Heat \text{CH}_4 + 2\text{O}_2 \rightarrow \text{CO}_2 + 2\text{H}_2\text{O} + \text{Heat} CH 4 + 2 O 2 → CO 2 + 2 H 2 O + Heat
Volumetric and molar stoichiometry:
1 volume 1\text{ volume} 1 volume (e.g., 1 cu ft 1\text{ cu ft} 1 cu ft ) of methane combines with 2 volumes 2\text{ volumes} 2 volumes ( 2 cu ft 2\text{ cu ft} 2 cu ft ) of pure oxygen.
The reaction yields 1 volume 1\text{ volume} 1 volume ( 1 cu ft 1\text{ cu ft} 1 cu ft ) of carbon dioxide and 2 volumes 2\text{ volumes} 2 volumes ( 2 cu ft 2\text{ cu ft} 2 cu ft ) of superheated water vapor.
Commercial Propane C 3 H 8 + 5 O 2 → 3 CO 2 + 4 H 2 O + Heat \text{C}_3\text{H}_8 + 5\text{O}_2 \rightarrow 3\text{CO}_2 + 4\text{H}_2\text{O} + \text{Heat} C 3 H 8 + 5 O 2 → 3 CO 2 + 4 H 2 O + Heat
Volumetric and molar stoichiometry:
1 volume 1\text{ volume} 1 volume ( 1 cu ft 1\text{ cu ft} 1 cu ft ) of propane vapor combines with 5 volumes 5\text{ volumes} 5 volumes ( 5 cu ft 5\text{ cu ft} 5 cu ft ) of pure oxygen.
The reaction yields 3 volumes 3\text{ volumes} 3 volumes ( 3 cu ft 3\text{ cu ft} 3 cu ft ) of carbon dioxide and 4 volumes 4\text{ volumes} 4 volumes ( 4 cu ft 4\text{ cu ft} 4 cu ft ) of water vapor.
Latent Heat & Condensing Appliance Dynamics
Notice that the combustion of fuel gas produces substantial volumes of water vapor: 2 cu ft 2\text{ cu ft} 2 cu ft of water vapor for every cu ft of methane, and 4 cu ft 4\text{ cu ft} 4 cu ft of water vapor for every cu ft of propane. Water vapor holds significant latent heat of vaporization (approximately 970 BTU per pound 970\text{ BTU per pound} 970 BTU per pound of water, or 2,257 kJ/kg 2{,}257\text{ kJ/kg} 2 , 257 kJ/kg ):
In mid-efficiency, non-condensing appliances (Category I, ≤ 80 % \le 80\% ≤ 80% AFUE), flue gas temperatures stay above the dew point ( > 275 ∘ F / 135 ∘ C >275^\circ\text{F} / 135^\circ\text{C} > 27 5 ∘ F /13 5 ∘ C ). The moisture escapes up the chimney as superheated steam, carrying away its latent heat.
In high-efficiency condensing furnaces and boilers (Category IV, 90 % to 98 % 90\%\text{ to }98\% 90% to 98% AFUE), an engineered secondary stainless steel heat exchanger extracts sensible heat from the flue gases, lowering their temperature below their dew point (approximately 130 ∘ F / 54 ∘ C 130^\circ\text{F} / 54^\circ\text{C} 13 0 ∘ F /5 4 ∘ C for natural gas ; 125 ∘ F / 52 ∘ C 125^\circ\text{F} / 52^\circ\text{C} 12 5 ∘ F /5 2 ∘ C for propane ). As the water vapor condenses into liquid, it releases its latent heat into the living space, capturing an additional 10 % to 11 % 10\%\text{ to }11\% 10% to 11% of thermal efficiency.
Because carbon dioxide dissolves into the condensate forming carbonic acid ( H 2 CO 3 \text{H}_2\text{CO}_3 H 2 CO 3 ) and trace sulfur creates sulfurous acids, furnace condensate is acidic ( pH 3.0 to 5.0 \text{pH } 3.0\text{ to }5.0 pH 3.0 to 5.0 ). It must be drained through acid-resistant piping (PVC, CPVC, or polypropylene) and passed through a neutralizer where the manufacturer or local rules require one.
Heating Values & Burner Orifice Sizing
The heating value of a fuel gas represents the quantity of thermal energy released during the complete combustion of a unit volume of gas. Heating values are categorized as:
Higher Heating Value (HHV) / Gross Heating Value: Assumes that all water vapor generated by combustion is condensed back to liquid state at 60 ∘ F 60^\circ\text{F} 6 0 ∘ F ( 15.6 ∘ C 15.6^\circ\text{C} 15. 6 ∘ C ), fully recovering latent heat.
Lower Heating Value (LHV) / Net Heating Value: Assumes that all water vapor remains in the vapor phase and exits through the flue gas, losing latent heat (typically 10 % 10\% 10% lower than HHV).
Commercial Heating Values
Natural Gas: Gross heating value is nominal 1,000 BTU per cubic foot 1{,}000\text{ BTU per cubic foot} 1 , 000 BTU per cubic foot ( 37.3 MJ/m 3 37.3\text{ MJ/m}^3 37.3 MJ/m 3 ). Depending on regional pipeline gas composition across Ontario utilities (such as Enbridge Gas), delivered gas varies between 950 and 1,050 BTU/cu ft 950\text{ and }1{,}050\text{ BTU/cu ft} 950 and 1 , 050 BTU/cu ft ( 35.4 to 39.1 MJ/m 3 35.4\text{ to }39.1\text{ MJ/m}^3 35.4 to 39.1 MJ/m 3 ). For utility billing and calculations, 1 m 3 ≈ 35.315 cu ft ≈ 37.3 MJ ≈ 10.35 kWh 1\text{ m}^3 \approx 35.315\text{ cu ft} \approx 37.3\text{ MJ} \approx 10.35\text{ kWh} 1 m 3 ≈ 35.315 cu ft ≈ 37.3 MJ ≈ 10.35 kWh .
Commercial Propane: Gross heating value is nominal 2,500 BTU per cubic foot 2{,}500\text{ BTU per cubic foot} 2 , 500 BTU per cubic foot of gas vapor ( 93.1 MJ/m 3 93.1\text{ MJ/m}^3 93.1 MJ/m 3 ). In liquid form, propane delivers approximately 21,560 BTU per pound 21{,}560\text{ BTU per pound} 21 , 560 BTU per pound ( 50.1 MJ/kg 50.1\text{ MJ/kg} 50.1 MJ/kg ) and 91,500 to 91,600 BTU per US gallon 91{,}500\text{ to }91{,}600\text{ BTU per US gallon} 91 , 500 to 91 , 600 BTU per US gallon ( 25.3 MJ/liter 25.3\text{ MJ/liter} 25.3 MJ/liter ).
Practical Orifice Sizing & Conversion Rules
Because propane delivers 2.5 times 2.5\text{ times} 2.5 times more thermal energy per cubic foot than natural gas ( 2,500 / 1,000 = 2.5 2{,}500 / 1{,}000 = 2.5 2 , 500/1 , 000 = 2.5 ), delivering an equivalent firing rate requires less than half the volume of propane gas: Flow Rate (CFH) = Input Rating (BTU/hr) Heating Value (BTU/cu ft) \text{Flow Rate (CFH)} = \frac{\text{Input Rating (BTU/hr)}}{\text{Heating Value (BTU/cu ft)}} Flow Rate (CFH) = Heating Value (BTU/cu ft) Input Rating (BTU/hr)
For a residential furnace rated at 100,000 BTU/hr 100{,}000\text{ BTU/hr} 100 , 000 BTU/hr : Natural Gas Firing Rate = 100,000 1,000 = 100 CFH \text{Natural Gas Firing Rate} = \frac{100{,}000}{1{,}000} = 100\text{ CFH} Natural Gas Firing Rate = 1 , 000 100 , 000 = 100 CFH Propane Firing Rate = 100,000 2,500 = 40 CFH \text{Propane Firing Rate} = \frac{100{,}000}{2{,}500} = 40\text{ CFH} Propane Firing Rate = 2 , 500 100 , 000 = 40 CFH
Furthermore, propane operates at a substantially higher manifold pressure ( 10.0 to 11.0 in. w.c. 10.0\text{ to }11.0\text{ in. w.c.} 10.0 to 11.0 in. w.c. ) than natural gas ( 3.5 in. w.c. 3.5\text{ in. w.c.} 3.5 in. w.c. ). Higher manifold pressure forces gas through an orifice at higher velocity. Consequently, for the same appliance BTU rating, a propane burner orifice must have a much smaller drill diameter (cross-sectional area) than a natural gas orifice:
Warning
Firing propane through natural gas orifices delivers roughly 2.5 2.5 2.5 times the rated heat input. This extreme overfiring produces violent flame rollout, heavy soot accumulation, deadly carbon monoxide generation, heat exchanger cracking, and house fires. Technicians must never convert an appliance between gas types without installing an approved manufacturer conversion kit containing certified orifices, gas valve regulator springs, and conversion rating decals.
Flammability Limits (Explosive Limits)
A fuel gas-air mixture will only ignite and sustain combustion when the concentration of gas falls between its lower and upper flammability limits (also termed explosive limits), expressed as the percentage of fuel gas by volume in air:
Lower Explosive Limit (LEL) / Lower Flammable Limit (LFL): The minimum volumetric concentration of gas in air that will propagate a flame when an ignition source is introduced. Below the LEL, the mixture is too lean to burn—there is insufficient fuel to release enough heat to ignite adjacent fuel molecules.
Upper Explosive Limit (UEL) / Upper Flammable Limit (UFL): The maximum volumetric concentration of gas in air that will support flame propagation. Above the UEL, the mixture is too rich to burn—there is insufficient oxygen to sustain oxidation.
Flammability Limits Comparison
Natural Gas:
LEL = 4.0 % \text{LEL} = 4.0\% LEL = 4.0% gas in air by volume.
UEL = 15.0 % \text{UEL} = 15.0\% UEL = 15.0% gas in air by volume.
Flammable Range Width: 11.0 % 11.0\% 11.0% ( 4.0 % to 15.0 % 4.0\%\text{ to }15.0\% 4.0% to 15.0% ).
Ideal Stoichiometric Mixture: ≈ 9.5 % to 10.0 % \approx 9.5\%\text{ to }10.0\% ≈ 9.5% to 10.0% .
Commercial Propane:
LEL = 2.15 % \text{LEL} = 2.15\% LEL = 2.15% gas in air by volume (practical trade benchmark 2.0 % 2.0\% 2.0% ).
UEL = 9.6 % \text{UEL} = 9.6\% UEL = 9.6% gas in air by volume.
Flammable Range Width: 7.45 % 7.45\% 7.45% ( 2.15 % to 9.6 % 2.15\%\text{ to }9.6\% 2.15% to 9.6% ).
Ideal Stoichiometric Mixture: ≈ 4.0 % to 4.2 % \approx 4.0\%\text{ to }4.2\% ≈ 4.0% to 4.2% .
Field Safety Implications of Flammability Limits
Although natural gas has a broader flammability window ( 11.0 % 11.0\% 11.0% vs 7.45 % 7.45\% 7.45% ), propane has a much lower lower flammability limit ( 2.15 % 2.15\% 2.15% vs 4.0 % 4.0\% 4.0% ). This means a small propane leak can elevate a confined space to an explosive condition much faster than a comparable volume of natural gas.
Important
An over-rich gas concentration ( > 15 % >15\% > 15% NG or > 9.6 % >9.6\% > 9.6% LP) is non-flammable only while sealed from the atmosphere. The moment fresh air enters—such as opening an access door, switching on a non-explosion-proof exhaust fan, or entering a building—the mixture is diluted directly through the explosive flammability window. Any mechanical or electrical spark during dilution triggers a catastrophic explosion.
Auto-Ignition Temperatures & Worksite Spark Sources
The auto-ignition temperature of a fuel gas is the minimum temperature to which a stoichiometric gas-air mixture must be heated to initiate self-sustaining combustion in the absence of an external spark or open flame:
Natural Gas: Auto-ignition temperature is approximately 1,200 ∘ F 1{,}200^\circ\text{F} 1 , 20 0 ∘ F ( 649 ∘ C 649^\circ\text{C} 64 9 ∘ C ) (standard textbook range 1,100 ∘ F to 1,300 ∘ F 1{,}100^\circ\text{F}\text{ to }1{,}300^\circ\text{F} 1 , 10 0 ∘ F to 1 , 30 0 ∘ F / 593 ∘ C to 704 ∘ C 593^\circ\text{C}\text{ to }704^\circ\text{C} 59 3 ∘ C to 70 4 ∘ C ).
Commercial Propane: Auto-ignition temperature is approximately 920 ∘ F to 1,020 ∘ F 920^\circ\text{F}\text{ to }1{,}020^\circ\text{F} 92 0 ∘ F to 1 , 02 0 ∘ F ( 493 ∘ C to 549 ∘ C 493^\circ\text{C}\text{ to }549^\circ\text{C} 49 3 ∘ C to 54 9 ∘ C ) .
Molecular Explanation for Ignition Temperatures
Methane's four carbon-hydrogen bonds are symmetrically balanced and exceptionally stable, requiring higher thermal activation energy ( 1,200 ∘ F 1{,}200^\circ\text{F} 1 , 20 0 ∘ F ) to initiate bond cleavage. In contrast, propane's three-carbon chain features weaker secondary carbon-hydrogen bonds and carbon-carbon bonds that dissociate at lower temperatures ( 920 ∘ F 920^\circ\text{F} 92 0 ∘ F ), giving propane a lower ignition temperature despite its higher molecular weight.
Common Worksite Ignition Temperatures
Every typical ignition source encountered on a construction or service jobsite far exceeds the ignition temperatures of both fuel gases:
Electric switch and relay contactor arcs: 2,000 ∘ F to 10,000 ∘ F 2{,}000^\circ\text{F}\text{ to }10{,}000^\circ\text{F} 2 , 00 0 ∘ F to 10 , 00 0 ∘ F ( 1,100 ∘ C to 5,500 ∘ C 1{,}100^\circ\text{C}\text{ to }5{,}500^\circ\text{C} 1 , 10 0 ∘ C to 5 , 50 0 ∘ C )
Open match or lighter flames: 1,500 ∘ F to 3,000 ∘ F 1{,}500^\circ\text{F}\text{ to }3{,}000^\circ\text{F} 1 , 50 0 ∘ F to 3 , 00 0 ∘ F ( 815 ∘ C to 1,650 ∘ C 815^\circ\text{C}\text{ to }1{,}650^\circ\text{C} 81 5 ∘ C to 1 , 65 0 ∘ C )
Hot Surface Igniters (HSI, silicon carbide/nitride): 1,800 ∘ F to 2,500 ∘ F 1{,}800^\circ\text{F}\text{ to }2{,}500^\circ\text{F} 1 , 80 0 ∘ F to 2 , 50 0 ∘ F ( 980 ∘ C to 1,370 ∘ C 980^\circ\text{C}\text{ to }1{,}370^\circ\text{C} 98 0 ∘ C to 1 , 37 0 ∘ C )
Static electricity discharge: up to 10,000 ∘ F 10{,}000^\circ\text{F} 10 , 00 0 ∘ F ( 5,500 ∘ C 5{,}500^\circ\text{C} 5 , 50 0 ∘ C )
Lit cigarette coal: 1,200 ∘ F to 1,400 ∘ F 1{,}200^\circ\text{F}\text{ to }1{,}400^\circ\text{F} 1 , 20 0 ∘ F to 1 , 40 0 ∘ F ( 650 ∘ C to 760 ∘ C 650^\circ\text{C}\text{ to }760^\circ\text{C} 65 0 ∘ C to 76 0 ∘ C )
Because any common spark will ignite a flammable gas-air mixture, technicians must de-energize and lock out electrical circuits before servicing gas-bearing components.
Flame Propagation Speeds & Burner Stability
Flame speed (burning velocity) is the speed at which a combustion wave travels through a quiescent stoichiometric gas-air mixture:
Natural Gas Laminar Flame Speed: Approximately 1.2 ft/s 1.2\text{ ft/s} 1.2 ft/s ( 0.37 m/s 0.37\text{ m/s} 0.37 m/s or ≈ 35 cm/s \approx 35\text{ cm/s} ≈ 35 cm/s ) .
Commercial Propane Laminar Flame Speed: Approximately 1.3 to 1.5 ft/s 1.3\text{ to }1.5\text{ ft/s} 1.3 to 1.5 ft/s ( 0.40 to 0.45 m/s 0.40\text{ to }0.45\text{ m/s} 0.40 to 0.45 m/s or ≈ 45 cm/s \approx 45\text{ cm/s} ≈ 45 cm/s ) .
Burner Port Aerodynamics: Velocity Balance
For a burner to maintain a stable, quiet flame seated firmly on the burner ports, the forward exit velocity of the air-gas mixture through the burner port openings ( V port V_{\text{port}} V port ) must precisely balance the backward flame propagation velocity ( V flame V_{\text{flame}} V flame ): V port = V flame V_{\text{port}} = V_{\text{flame}} V port = V flame
When this equilibrium is disrupted, two hazardous burner conditions occur:
Lifting Flame ( V port > V flame V_{\text{port}} > V_{\text{flame}} V port > V flame ): If the air-gas mixture exit velocity exceeds the flame propagation speed, the flame detaches from the burner port surface, hovering 1 / 4 to 1 / 2 inch 1/4\text{ to }1/2\text{ inch} 1/4 to 1/2 inch above the metal or blowing out completely. Symptoms include a loud roaring hiss, ragged flame cones, unburned gas odors, and delayed ignition rollouts. Causes include excessive manifold gas pressure, oversized burner orifices, excessive primary aeration, or excessive chimney draft.
Flashback ( V flame > V port V_{\text{flame}} > V_{\text{port}} V flame > V port ): If the flame propagation speed exceeds the mixture exit velocity, the flame travels backward through the burner port openings and burns inside the venturi mixing tube at the gas orifice spud. Symptoms include a loud popping sound followed by a continuous roaring or howling noise inside the burner body, yellow lazy flames issuing from air shutters, and smoke. Flashback causes rapid overheating and melting of brass orifices and burner castings, while generating lethal carbon monoxide. Causes include under-firing (low manifold pressure), partially clogged orifices, cracked or rusted-out burner heads with enlarged ports, or excessive primary air on low-fire stages.
Combustion Chemistry Parameters Comparison
- Parameter Natural Gas (Methane) Commercial Propane (HD-5)
- Chemical Formula CH 4 \text{CH}_4 CH 4 C 3 H 8 \text{C}_3\text{H}_8 C 3 H 8
Theoretical Oxygen per Cu Ft Gas 2.0 cu ft O 2 2.0\text{ cu ft }\text{O}_2 2.0 cu ft O 2 5.0 cu ft O 2 5.0\text{ cu ft }\text{O}_2 5.0 cu ft O 2
Gross Heating Value ≈ 1,000 BTU/cu ft \approx 1{,}000\text{ BTU/cu ft} ≈ 1 , 000 BTU/cu ft ( 37.3 MJ/m 3 37.3\text{ MJ/m}^3 37.3 MJ/m 3 ) ≈ 2,500 BTU/cu ft \approx 2{,}500\text{ BTU/cu ft} ≈ 2 , 500 BTU/cu ft ( 93.1 MJ/m 3 93.1\text{ MJ/m}^3 93.1 MJ/m 3 )
- Lower Explosive Limit (LEL) 4.0 % 4.0\% 4.0% gas in air 2.15 % 2.15\% 2.15% gas in air
- Upper Explosive Limit (UEL) 15.0 % 15.0\% 15.0% gas in air 9.6 % 9.6\% 9.6% gas in air
Ideal Stoichiometric Gas-Air Ratio ≈ 9.5 % to 10.0 % \approx 9.5\%\text{ to }10.0\% ≈ 9.5% to 10.0% gas in air ≈ 4.0 % to 4.2 % \approx 4.0\%\text{ to }4.2\% ≈ 4.0% to 4.2% gas in air
Auto-Ignition Temperature ≈ 1,200 ∘ F \approx 1{,}200^\circ\text{F} ≈ 1 , 20 0 ∘ F ( 649 ∘ C 649^\circ\text{C} 64 9 ∘ C ) ≈ 920 ∘ F to 1,020 ∘ F \approx 920^\circ\text{F}\text{ to }1{,}020^\circ\text{F} ≈ 92 0 ∘ F to 1 , 02 0 ∘ F ( 493 ∘ C to 549 ∘ C 493^\circ\text{C}\text{ to }549^\circ\text{C} 49 3 ∘ C to 54 9 ∘ C )
Laminar Flame Speed ≈ 1.2 ft/s \approx 1.2\text{ ft/s} ≈ 1.2 ft/s ( 0.37 m/s 0.37\text{ m/s} 0.37 m/s ) ≈ 1.3 to 1.5 ft/s \approx 1.3\text{ to }1.5\text{ ft/s} ≈ 1.3 to 1.5 ft/s ( 0.40 to 0.45 m/s 0.40\text{ to }0.45\text{ m/s} 0.40 to 0.45 m/s )
Standard Manifold Pressure 3.5 in. w.c. 3.5\text{ in. w.c.} 3.5 in. w.c. ( 0.87 kPa 0.87\text{ kPa} 0.87 kPa ) 10.0 to 11.0 in. w.c. 10.0\text{ to }11.0\text{ in. w.c.} 10.0 to 11.0 in. w.c. ( 2.49 to 2.74 kPa 2.49\text{ to }2.74\text{ kPa} 2.49 to 2.74 kPa )