11.1 Gas Pipe & Tubing Sizing Fundamentals (Tables & Pressure Drop)
TSSA Gas Technician 3 G3
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Safety & Workplace Practices
1.1 Personal Protective Equipment (PPE) & Worksite Hazard Identification 1.2 WHMIS, GHS, Safety Data Sheets (SDS) & Chemical Safety 1.3 Electrical Safety, Lockout/Tagout (LOTO) & Confined Space Awareness
2 Chapter 2: Fasteners, Hand Tools & Power Tools
2.1 Hand Tools for Gas Piping and Mechanical Assembly 2.2 Power Tools, Threading Machines & Mechanical Fasteners
3 Chapter 3: Testing Instruments & Diagnostics
3.1 Pressure Measurement: U-Tube, Inclined & Digital Manometers 3.2 Electrical Multimeters, Combustion Analyzers & Electronic Leak Detectors
4 Chapter 4: Fuel Gas Properties & Combustion Principles
4.1 Chemical & Physical Properties of Natural Gas vs. Propane 4.2 Combustion Chemistry, Flammability Limits & Ignition Temperatures 4.3 Complete vs. Incomplete Combustion, Carbon Monoxide Hazards & Air Requirements
5 Chapter 5: Ontario Acts, Regulations & G.3 Scope of Authority
5.1 Technical Standards and Safety Act & O. Reg. 215/01 Certification 5.2 O. Reg. 211/01, O. Reg. 212/01 & TSSA Code Adoption Documents (CAD) 5.3 Unacceptable Conditions, Warning Notices & Red Tag Procedures
6 Chapter 6: CSA B149 Code Navigation & General Requirements
6.1 CSA B149.1 & CSA B149.2 Scope, Structure & Key Definitions 6.2 General Installation Rules: Instructions, Access, Clearances & Garages (Clause 4)
7 Chapter 7: Introduction to Electricity & Electrical Safety
7.1 Electrical Fundamentals: Ohm's Law, Power & Circuit Configurations 7.2 Line Voltage (120V) vs. Low Voltage (24V), Transformers & Circuit Protection 7.3 Basic Electrical Controls, Switches & Ladder Diagram Schematics
8 Chapter 8: Technical Manuals, Specifications & Architectural Drawings
8.1 Reading Appliance Rating Plates, Certified Manuals & Specifications 8.2 Architectural Blueprints, Mechanical Drawings & Piping Schematics
9 Chapter 9: Customer Relations, Professional Conduct & Documentation
9.1 Professional Communication, Ethics & Customer Service Standards 9.2 Work Orders, Service Documentation & Red Tag Communication
10 Chapter 10: Piping & Tubing Systems: Materials, Joining & Installation
10.1 Piping & Tubing Materials: Steel, Copper, CSST & Plastic 10.2 Pipe Joining Methods: Threading, Flaring, Brazing & Approved Sealants 10.3 Piping Installation: Supports, Hangers, Drip Legs, Dirt Pockets & Valves
11 Chapter 11: Gas Pipe Sizing, Pressure Testing & Purging Procedures
11.1 Gas Pipe & Tubing Sizing Fundamentals (Tables & Pressure Drop) 11.2 Pressure Testing, Leak Testing & the Ontario Test Tag (Clause 6.22) 11.3 Purging Procedures, Safety Protocols & Leak Detection (Clauses 6.23–6.24)
12 Chapter 12: Gas Appliances, Burners & Combustion Air Fundamentals
12.1 Appliance Classifications, Categories (I–IV), Approvals & Clearances 12.2 Atmospheric & Power Burners: Operation, Aeration & Flame Adjustment 12.3 Ignition Systems & Flame Safeguards: Standing Pilot, HSI, DSI, Thermocouples & Flame Rods 12.4 Combustion Air & Basic Venting Requirements (Clause 8)
11.1 Gas Pipe & Tubing Sizing Fundamentals (Tables & Pressure Drop)
Key Takeaways Explain This Topic AI
The CSA B149.1 Annex A and B tables are applied with the Longest Developed Length (LDL) method: measure the developed length from the meter or last-stage regulator outlet to the most remote appliance and size every segment from that length row.
Appliance input ratings in BTU/h \text{BTU/h} BTU/h must be converted to volumetric fuel demand in cubic feet per hour ( CFH = BTU/h ÷ Heating Value \text{CFH} = \text{BTU/h} \div \text{Heating Value} CFH = BTU/h ÷ Heating Value ), applying nominal heating values of 1,000 BTU/cu ft 1{,}000\text{ BTU/cu ft} 1 , 000 BTU/cu ft for Natural Gas ( SG ≈ 0.60 \text{SG} \approx 0.60 SG ≈ 0.60 ) and 2,500 BTU/cu ft 2{,}500\text{ BTU/cu ft} 2 , 500 BTU/cu ft for Commercial Propane ( SG ≈ 1.52 \text{SG} \approx 1.52 SG ≈ 1.52 ).
CSA B149.1 Table 6.1 limits pressure drop to 0.5 in. w.c. 0.5\text{ in. w.c.} 0.5 in. w.c. where supply pressure is below 7 in. w.c. 7\text{ in. w.c.} 7 in. w.c. (Tables A.1 and A.8) and to 1 in. w.c. 1\text{ in. w.c.} 1 in. w.c. for supplies of 7 to 14 in. w.c. 7\text{ to }14\text{ in. w.c.} 7 to 14 in. w.c. (Tables A.2 and A.9 for natural gas; B.1 and B.6 for propane).
When executing the LDL method, every individual pipe segment—including main distribution trunks and all appliance branch takeoffs—must be sized using the row corresponding to the total system LDL (or the next higher table increment), never using a branch's individual developed length alone.
Although commercial propane vapor is heavier than air ( SG ≈ 1.52 \text{SG} \approx 1.52 SG ≈ 1.52 vs 0.60 0.60 0.60 ), its 2.5 × 2.5\times 2.5 × higher volumetric energy density ( 2,500 BTU/cu ft 2{,}500\text{ BTU/cu ft} 2 , 500 BTU/cu ft vs 1,000 BTU/cu ft 1{,}000\text{ BTU/cu ft} 1 , 000 BTU/cu ft ) reduces required volumetric flow by 60 % 60\% 60% , allowing smaller pipe and tubing diameters for identical appliance heat inputs.
Last updated: October 2026
Gas Pipe & Tubing Sizing Fundamentals (Tables & Pressure Drop)
In fuel gas distribution, correct pipe and tubing sizing is the engineering foundation of appliance performance and operational safety. An undersized piping system causes excessive friction loss, leading to severe pressure drop during peak firing conditions. Pressure starvation destabilizes appliance burner manifolds, produces unstable lifting flames, causes incomplete combustion and toxic carbon monoxide ( C O CO CO ) generation, and triggers nuisance dropouts of low-pressure safety switches. Conversely, severely oversized piping introduces unnecessary material costs and creates excessively large internal fuel volumes that complicate pressure testing and purging procedures.
Under the Technical Standards and Safety Act, 2000 , Ontario Regulation 212/01 ( Gaseous Fuels ), and the CSA B149.1 Natural Gas and Propane Installation Code , certified Gas Technician 3 (G.3) certificate holders must master the physical principles of gas flow, volumetric conversions, table navigation in Annex A and Annex B, and the Longest Developed Length (LDL) sizing methodology.
Principles of Fuel Gas Flow & Pressure Drop
Gas flowing through a closed conduit experiences continuous internal fluid resistance caused by fluid viscosity and friction against the pipe wall. The fundamental relationship governing low-pressure fuel gas flow (operating below 0.5 psig / 14 in. w.c. 0.5\text{ psig} / 14\text{ in. w.c.} 0.5 psig /14 in. w.c. ) is expressed through empirical flow formulations such as Pole's Formula and the Weymouth Equation :
Q = C × Δ P × d 5 S G × L Q = C \times \sqrt{\frac{\Delta P \times d^5}{SG \times L}} Q = C × SG × L Δ P × d 5
Where:
Q Q Q = Volumetric flow rate in cubic feet per hour ( CFH \text{CFH} CFH )
Δ P \Delta P Δ P = Allowable pressure drop across the pipe run (inches water column, in. w.c. \text{in. w.c.} in. w.c. )
- d d d = Internal diameter of the pipe or tubing (inches)
- S G SG SG = Specific gravity of the fuel gas relative to air ( 1.00 1.00 1.00 )
- L L L = Developed length of the piping run (feet)
- C C C = Empirical friction and flow coefficient
Analyzing this fluid dynamic relationship reveals four core rules essential for gas technicians:
Direct Impact of Pipe Diameter ( d 5 d^5 d 5 ): Flow capacity is proportional to the fifth power of internal diameter. A minor increase in pipe size yields an exponential expansion in capacity. For example, moving from nominal 1 / 2 -inch 1/2\text{-inch} 1/2 -inch Schedule 40 pipe ( d = 0.622 in d = 0.622\text{ in} d = 0.622 in ) to 3 / 4 -inch 3/4\text{-inch} 3/4 -inch pipe ( d = 0.824 in d = 0.824\text{ in} d = 0.824 in ) more than doubles the flow capacity at identical length and pressure drop.
Inverse Impact of Length ( L \sqrt{L} L ): As developed length increases, friction accumulates. Doubling the length of a pipe reduces its delivery capacity by a factor of 2 ≈ 1.414 \sqrt{2} \approx 1.414 2 ≈ 1.414 (a 29.3 % 29.3\% 29.3% flow reduction).
Square-Root Impact of Allowable Drop ( Δ P \sqrt{\Delta P} Δ P ): Increasing allowable pressure drop increases capacity, but only by the square root of the drop ratio.
Inverse Impact of Specific Gravity ( S G \sqrt{SG} SG ): Heavier gases encounter greater inertial resistance. A gas with a higher specific gravity experiences slower flow velocities under identical differential pressures.
Volumetric Flow Conversion: BTU/h \text{BTU/h} BTU/h to CFH \text{CFH} CFH
Appliance rating plates specify thermal input capacities in British Thermal Units per hour ( BTU/h \text{BTU/h} BTU/h ) or Kilowatts ( kW \text{kW} kW ) ( 1 kW = 3,412.14 BTU/h 1\text{ kW} = 3{,}412.14\text{ BTU/h} 1 kW = 3 , 412.14 BTU/h ). Pipe capacity tables, however, are commonly expressed as volume flow— Cubic Feet per Hour ( CFH \text{CFH} CFH ) or Cubic Metres per Hour ( m 3 /h \text{m}^3\text{/h} m 3 /h ) ( 1 m 3 /h = 35.315 CFH 1\text{ m}^3\text{/h} = 35.315\text{ CFH} 1 m 3 /h = 35.315 CFH )—so always check the units in the table heading.
To size any pipe run, technicians must convert thermal ratings to volumetric flow using the gross heating value of the fuel gas:
Volumetric Flow (CFH) = Appliance Input Rating (BTU/h) Gross Heating Value of Fuel (BTU/cu ft) \text{Volumetric Flow (CFH)} = \frac{\text{Appliance Input Rating (BTU/h)}}{\text{Gross Heating Value of Fuel (BTU/cu ft)}} Volumetric Flow (CFH) = Gross Heating Value of Fuel (BTU/cu ft) Appliance Input Rating (BTU/h)
Natural Gas vs. Commercial Propane Energetics
Fuel Parameter Natural Gas (Utility Supply) Commercial Propane (HD-5)
Nominal Chemical Composition Methane ( CH 4 \text{CH}_4 CH 4 , 85 % to 95 % 85\%\text{ to }95\% 85% to 95% ) Propane ( C 3 H 8 \text{C}_3\text{H}_8 C 3 H 8 , ≥ 90 % \ge 90\% ≥ 90% )
Gross Heating Value (Imperial) 1,000 BTU/cu ft 1{,}000\text{ BTU/cu ft} 1 , 000 BTU/cu ft (nominal) 2,500 BTU/cu ft 2{,}500\text{ BTU/cu ft} 2 , 500 BTU/cu ft (nominal)
Gross Heating Value (SI Metric) 37.3 MJ/m 3 37.3\text{ MJ/m}^3 37.3 MJ/m 3 93.1 MJ/m 3 93.1\text{ MJ/m}^3 93.1 MJ/m 3
Specific Gravity ( S G SG SG , Air = 1.00 1.00 1.00 ) 0.60 0.60 0.60 (Nominal range 0.55 to 0.65 0.55\text{ to }0.65 0.55 to 0.65 ; Lighter) 1.52 1.52 1.52 (Nominal range 1.50 to 1.55 1.50\text{ to }1.55 1.50 to 1.55 ; Heavier)
Standard Low-Pressure Delivery 7.0 in. w.c. 7.0\text{ in. w.c.} 7.0 in. w.c. ( 1.75 kPa 1.75\text{ kPa} 1.75 kPa ) 11.0 in. w.c. 11.0\text{ in. w.c.} 11.0 in. w.c. ( 2.75 kPa 2.75\text{ kPa} 2.75 kPa )
Standard Manifold Pressure 3.5 in. w.c. 3.5\text{ in. w.c.} 3.5 in. w.c. ( 0.87 kPa 0.87\text{ kPa} 0.87 kPa ) 10.0 in. w.c. 10.0\text{ in. w.c.} 10.0 in. w.c. ( 2.50 kPa 2.50\text{ kPa} 2.50 kPa )
Note
Use the heating value from the gas supplier when you have it. A nominal 1,000 BTU/cu ft 1{,}000\text{ BTU/cu ft} 1 , 000 BTU/cu ft ( 37.3 MJ/m 3 37.3\text{ MJ/m}^3 37.3 MJ/m 3 ) is the customary value for natural gas sizing exercises, and Ontario pipeline gas is close to it.
Comparative Flow Calculation
Consider a high-efficiency condensing furnace with an input rating of 100,000 BTU/h 100{,}000\text{ BTU/h} 100 , 000 BTU/h :
Operating on Natural Gas: CFH NG = 100,000 BTU/h 1,000 BTU/cu ft = 100 CFH \text{CFH}_{\text{NG}} = \frac{100{,}000\text{ BTU/h}}{1{,}000\text{ BTU/cu ft}} = 100\text{ CFH} CFH NG = 1 , 000 BTU/cu ft 100 , 000 BTU/h = 100 CFH
Operating on Commercial Propane: CFH LP = 100,000 BTU/h 2,500 BTU/cu ft = 40 CFH \text{CFH}_{\text{LP}} = \frac{100{,}000\text{ BTU/h}}{2{,}500\text{ BTU/cu ft}} = 40\text{ CFH} CFH LP = 2 , 500 BTU/cu ft 100 , 000 BTU/h = 40 CFH
Even though propane is more than twice as dense as natural gas ( S G = 1.52 SG = 1.52 SG = 1.52 vs 0.60 0.60 0.60 ), its volumetric energy concentration is 2.5 times 2.5\text{ times} 2.5 times greater. Consequently, an appliance requires 60 % 60\% 60% less volume of propane to deliver the exact same thermal output. This critical distinction explains why propane piping and copper tubing lines are almost always smaller in diameter than natural gas piping serving equivalent loads.
Pressure Regimes & Allowable Pressure Drops
Piping sizing tables in CSA B149.1 Annex A (Natural Gas) and Annex B (Propane) are categorized by inlet operating pressure , allowable pressure drop ( Δ P \Delta P Δ P ) , and piping material .
Low-Pressure Systems (up to 14 in. w.c.)
CSA B149.1 Clause 6.3.2 and Table 6.1 set the maximum pressure drop allowed between the meter (or last-stage regulator) and the appliance:
Piping system supply pressure Maximum allowable pressure drop Natural gas tables (Annex A) Propane tables (Annex B)
- Less than 7 in. w.c. (1.75 kPa) 0.5 in. w.c. (0.125 kPa) Tables A.1 and A.8 —
- 7 in. w.c. up to 14 in. w.c. (1.75–3.5 kPa) 1 in. w.c. (0.25 kPa) Tables A.2 and A.9 Tables B.1 and B.6
Ontario residential natural gas is delivered at about 7 in. w.c., so Table 6.1 allows a 1 in. w.c. drop and the Table A.2 capacities. Sizing to a 0.5 in. w.c. drop (Table A.1) is more conservative and also complies—useful where an appliance needs a higher minimum inlet pressure or the supply sits at the low end of its range. Propane systems supplied at about 11 in. w.c. use the 1 in. w.c. tables in Annex B. The tables already include an allowance for a reasonable number of fittings.
Medium-Pressure Hybrid Systems ( 2 psig / 14 kPa 2\text{ psig} / 14\text{ kPa} 2 psig /14 kPa )
Modern large residential and commercial buildings frequently employ 2 psig 2\text{ psig} 2 psig ( 14 kPa 14\text{ kPa} 14 kPa ) natural gas distribution:
Gas is distributed through compact, small-diameter piping (often 3 / 8 -inch 3/8\text{-inch} 3/8 -inch or 1 / 2 -inch 1/2\text{-inch} 1/2 -inch CSST or copper tubing) from the meter to central manifolds.
Dedicated Line Pressure Regulators (LPRs) certified to CSA 6.22 / ANSI Z21.80 reduce the pressure from 2 psig 2\text{ psig} 2 psig down to appliance operating levels ( 7 in. w.c. 7\text{ in. w.c.} 7 in. w.c. ) immediately adjacent to each appliance or appliance manifold.
Clause 6.3.4 sizes 2 psig systems from the minimum pressure available at the line pressure regulator, using the 2 psig tables in Annex A (Tables A.2, A.3, A.4, A.10 and A.11) or Annex B (Tables B.2 and B.7) for propane.
Practice Capacity Table (0.5 in. w.c. Drop)
The table below is an illustrative practice table : rounded capacities for Schedule 40 steel pipe carrying natural gas ( S G = 0.60 SG = 0.60 SG = 0.60 ) at a 0.5 in. w.c. 0.5\text{ in. w.c.} 0.5 in. w.c. drop, following the pattern of published low-pressure capacity tables. Use it to practise the method. On the job and in the TSSA exam, read the actual CSA B149.1 Annex A table for your allowed pressure drop.
Total Developed Length (Feet) Nominal 1/2" Pipe (CFH) Nominal 3/4" Pipe (CFH) Nominal 1" Pipe (CFH) Nominal 1-1/4" Pipe (CFH) Nominal 1-1/2" Pipe (CFH) Nominal 2" Pipe (CFH)
- 10 175 360 680 1,400 2,100 3,950
- 20 120 250 465 950 1,460 2,750
- 30 97 200 375 770 1,180 2,200
- 40 82 170 320 660 990 1,900
- 50 73 151 285 580 870 1,680
- 60 66 138 260 530 790 1,520
- 70 61 125 240 490 730 1,400
- 80 57 118 220 460 690 1,300
- 90 53 110 205 430 650 1,220
- 100 50 104 195 400 620 1,160
- 125 44 93 175 360 550 1,020
- 150 40 84 160 325 500 930
Important
When the measured developed length of a system falls between two table values (for example, 74 feet 74\text{ feet} 74 feet ), do not interpolate —use the next longer length row (in this case, 80 feet 80\text{ feet} 80 feet ). This conservative rule prevents undersizing.
The Longest Developed Length (LDL) Methodology
The Longest Developed Length (LDL) method is the standard way to use the Annex A and B tables for branched low-pressure systems. It is based on a foundational physical principle: the total friction drop across any path from the gas meter to an appliance must not exceed the allowable limit ( 0.5 in. w.c. 0.5\text{ in. w.c.} 0.5 in. w.c. ) .
If a technician were to size a short appliance branch (e.g., 15 feet 15\text{ feet} 15 feet ) using the 15 -foot 15\text{-foot} 15 -foot table column while the main header runs 80 feet 80\text{ feet} 80 feet , the cumulative pressure drop across both segments would exceed the allowed drop. Sizing every segment from the total system LDL keeps the drop within the Table 6.1 limit under full load.
The Six-Step Sizing Protocol
Establish Total System Load: Sum the maximum firing rates of all connected appliances in BTU/h \text{BTU/h} BTU/h and convert each to volumetric flow ( CFH \text{CFH} CFH ) by dividing by the fuel heating value.
Measure Developed Lengths: Determine the linear length of pipe from the meter or regulator outlet to each individual appliance shutoff valve. Developed length includes actual pipe travel plus an allowance for fittings if using advanced equivalent length methods (under standard residential Annex A tables, fitting friction is incorporated into conservative table margins).
Identify the Longest Developed Length (LDL): Find the single farthest appliance from the gas supply. Round this distance UP to the next higher row in the applicable sizing table. This row becomes the sole sizing reference for the entire piping network.
Size Main Distribution Trunk Sections: Starting at the meter, size each main line segment based on the cumulative CFH demand of all downstream appliances, reading across the established LDL row.
Size Intermediate Distribution Headers: At each tee or junction, recalculate the remaining downstream load and select the required pipe diameter from the LDL row.
Size Individual Appliance Branch Lines: Size each branch takeoff based strictly on that individual appliance's CFH \text{CFH} CFH demand, using the exact same system LDL row —regardless of how short that branch pipe actually is.
Worked Trade Sizing Example: Residential Installation
To master this procedure, work through a complete residential sizing problem using the practice table above.
Jobsite Specifications
Fuel Gas: Natural Gas ( 1,000 BTU/cu ft 1{,}000\text{ BTU/cu ft} 1 , 000 BTU/cu ft , S G = 0.60 SG = 0.60 SG = 0.60 )
Supply Pressure: 7.0 in. w.c. 7.0\text{ in. w.c.} 7.0 in. w.c. ( < 0.5 psig <0.5\text{ psig} < 0.5 psig )
Allowable Pressure Drop: 0.5 in. w.c. 0.5\text{ in. w.c.} 0.5 in. w.c. (a conservative choice; Table 6.1 would allow 1 in. w.c. 1\text{ in. w.c.} 1 in. w.c. at a 7 in. w.c. 7\text{ in. w.c.} 7 in. w.c. supply)
- Piping Material: Schedule 40 Black Steel Pipe
- Appliance Schedule & Firing Rates
Appliance A — High-Efficiency Furnace: 100,000 BTU/h = 100 CFH 100{,}000\text{ BTU/h} = 100\text{ CFH} 100 , 000 BTU/h = 100 CFH
Appliance B — Domestic Water Heater: 40,000 BTU/h = 40 CFH 40{,}000\text{ BTU/h} = 40\text{ CFH} 40 , 000 BTU/h = 40 CFH
Appliance C — Gas Cooking Range: 65,000 BTU/h = 65 CFH 65{,}000\text{ BTU/h} = 65\text{ CFH} 65 , 000 BTU/h = 65 CFH
Appliance D — Gas Fireplace: 35,000 BTU/h = 35 CFH 35{,}000\text{ BTU/h} = 35\text{ CFH} 35 , 000 BTU/h = 35 CFH
Total Connected System Demand: 100 + 40 + 65 + 35 = 240 CFH 100 + 40 + 65 + 35 = \mathbf{240\text{ CFH}} 100 + 40 + 65 + 35 = 240 CFH
- Layout & Linear Piping Distances
- Meter to Junction 1 (J1): 20 feet 20\text{ feet} 20 feet
Junction 1 to Water Heater (Branch B): 15 feet 15\text{ feet} 15 feet (Total distance from meter: 20 + 15 = 35 ft 20 + 15 = 35\text{ ft} 20 + 15 = 35 ft )
Junction 1 to Junction 2 (J2): 15 feet 15\text{ feet} 15 feet
Junction 2 to Furnace (Branch A): 10 feet 10\text{ feet} 10 feet (Total distance from meter: 20 + 15 + 10 = 45 ft 20 + 15 + 10 = 45\text{ ft} 20 + 15 + 10 = 45 ft )
Junction 2 to Junction 3 (J3): 20 feet 20\text{ feet} 20 feet
Junction 3 to Range (Branch C): 10 feet 10\text{ feet} 10 feet (Total distance from meter: 20 + 15 + 20 + 10 = 65 ft 20 + 15 + 20 + 10 = 65\text{ ft} 20 + 15 + 20 + 10 = 65 ft )
Junction 3 to Fireplace (Branch D): 20 feet 20\text{ feet} 20 feet (Total distance from meter: 20 + 15 + 20 + 20 = 75 ft 20 + 15 + 20 + 20 = \mathbf{75\text{ ft}} 20 + 15 + 20 + 20 = 75 ft )
- Step-by-Step Sizing Execution
- Step 1: Identify Longest Developed Length (LDL)
The farthest appliance is the Gas Fireplace , located at a total developed distance of 75 feet 75\text{ feet} 75 feet from the meter outlet. The practice table does not list 75 feet 75\text{ feet} 75 feet ; therefore, round UP to the 80 -foot 80\text{-foot} 80 -foot row .
All pipe segments in this system will be sized using the 80 -foot 80\text{-foot} 80 -foot row.
At 80 feet 80\text{ feet} 80 feet , the practice table gives:
- 1 / 2 -inch 1/2\text{-inch} 1/2 -inch : 57 CFH 57\text{ CFH} 57 CFH
- 3 / 4 -inch 3/4\text{-inch} 3/4 -inch : 118 CFH 118\text{ CFH} 118 CFH
- 1 -inch 1\text{-inch} 1 -inch : 220 CFH 220\text{ CFH} 220 CFH
- 1 - 1 / 4 -inch 1\text{-}1/4\text{-inch} 1 - 1/4 -inch : 460 CFH 460\text{ CFH} 460 CFH
- Step 2: Size Main Trunk Segment 1 (Meter to J1)
Connected Load: Supplies all 4 appliances ( 240 CFH 240\text{ CFH} 240 CFH total).
Capacity Check at 80 ft 80\text{ ft} 80 ft : A 1 -inch 1\text{-inch} 1 -inch pipe carries 220 CFH 220\text{ CFH} 220 CFH ( 220 < 240 220 < 240 220 < 240 , insufficient). A 1 - 1 / 4 -inch 1\text{-}1/4\text{-inch} 1 - 1/4 -inch pipe carries 460 CFH 460\text{ CFH} 460 CFH ( 460 ≥ 240 460 \ge 240 460 ≥ 240 , compliant).
- Selected Size: 1 - 1 / 4 inch 1\text{-}1/4\text{ inch} 1 - 1/4 inch
- Step 3: Size Branch B to Water Heater (J1 to Water Heater)
Connected Load: 40 CFH 40\text{ CFH} 40 CFH .
Capacity Check at 80 ft 80\text{ ft} 80 ft : A 1 / 2 -inch 1/2\text{-inch} 1/2 -inch pipe carries 57 CFH 57\text{ CFH} 57 CFH ( 57 ≥ 40 57 \ge 40 57 ≥ 40 , compliant).
- Selected Size: 1 / 2 inch 1/2\text{ inch} 1/2 inch
- Step 4: Size Main Trunk Segment 2 (J1 to J2)
Connected Load: Supplies Furnace, Range, and Fireplace ( 100 + 65 + 35 = 200 CFH 100 + 65 + 35 = 200\text{ CFH} 100 + 65 + 35 = 200 CFH ).
Capacity Check at 80 ft 80\text{ ft} 80 ft : A 3 / 4 -inch 3/4\text{-inch} 3/4 -inch pipe carries 118 CFH 118\text{ CFH} 118 CFH (insufficient). A 1 -inch 1\text{-inch} 1 -inch pipe carries 220 CFH 220\text{ CFH} 220 CFH ( 220 ≥ 200 220 \ge 200 220 ≥ 200 , compliant).
- Selected Size: 1 inch 1\text{ inch} 1 inch
- Step 5: Size Branch A to Furnace (J2 to Furnace)
Connected Load: 100 CFH 100\text{ CFH} 100 CFH .
Capacity Check at 80 ft 80\text{ ft} 80 ft : A 1 / 2 -inch 1/2\text{-inch} 1/2 -inch pipe carries only 57 CFH 57\text{ CFH} 57 CFH (insufficient). A 3 / 4 -inch 3/4\text{-inch} 3/4 -inch pipe carries 118 CFH 118\text{ CFH} 118 CFH ( 118 ≥ 100 118 \ge 100 118 ≥ 100 , compliant).
Selected Size: 3 / 4 inch 3/4\text{ inch} 3/4 inch
Warning
If an apprentice improperly sized Branch A using its own branch distance of 10 feet 10\text{ feet} 10 feet , the table at 10 feet 10\text{ feet} 10 feet would indicate a 1 / 2 -inch 1/2\text{-inch} 1/2 -inch pipe delivers 175 CFH 175\text{ CFH} 175 CFH , leading to the erroneous selection of 1 / 2 -inch 1/2\text{-inch} 1/2 -inch pipe. Under peak winter firing, the excessive friction across the 45 feet 45\text{ feet} 45 feet of total piping would starve the furnace burner, tripping its low gas pressure switch or causing roll-out.
Step 6: Size Main Trunk Segment 3 (J2 to J3)
Connected Load: Supplies Range and Fireplace ( 65 + 35 = 100 CFH 65 + 35 = 100\text{ CFH} 65 + 35 = 100 CFH ).
Capacity Check at 80 ft 80\text{ ft} 80 ft : A 1 / 2 -inch 1/2\text{-inch} 1/2 -inch pipe carries 57 CFH 57\text{ CFH} 57 CFH (insufficient). A 3 / 4 -inch 3/4\text{-inch} 3/4 -inch pipe carries 118 CFH 118\text{ CFH} 118 CFH ( 118 ≥ 100 118 \ge 100 118 ≥ 100 , compliant).
- Selected Size: 3 / 4 inch 3/4\text{ inch} 3/4 inch
- Step 7: Size Branch C to Range (J3 to Range)
Connected Load: 65 CFH 65\text{ CFH} 65 CFH .
Capacity Check at 80 ft 80\text{ ft} 80 ft : A 1 / 2 -inch 1/2\text{-inch} 1/2 -inch pipe carries 57 CFH 57\text{ CFH} 57 CFH ( 57 < 65 57 < 65 57 < 65 , insufficient). A 3 / 4 -inch 3/4\text{-inch} 3/4 -inch pipe carries 118 CFH 118\text{ CFH} 118 CFH ( 118 ≥ 65 118 \ge 65 118 ≥ 65 , compliant).
- Selected Size: 3 / 4 inch 3/4\text{ inch} 3/4 inch
- Step 8: Size Branch D to Fireplace (J3 to Fireplace)
Connected Load: 35 CFH 35\text{ CFH} 35 CFH .
Capacity Check at 80 ft 80\text{ ft} 80 ft : A 1 / 2 -inch 1/2\text{-inch} 1/2 -inch pipe carries 57 CFH 57\text{ CFH} 57 CFH ( 57 ≥ 35 57 \ge 35 57 ≥ 35 , compliant).
- Selected Size: 1 / 2 inch 1/2\text{ inch} 1/2 inch
- Summary Sizing Schedule
Piping Segment Downstream Load (CFH) Table Length Row Minimum Pipe Size Segment Capacity
Trunk 1 (Meter to J1) 240 CFH 240\text{ CFH} 240 CFH 80 ft 80\text{ ft} 80 ft 1 - 1 / 4 inch 1\text{-}1/4\text{ inch} 1 - 1/4 inch 460 CFH 460\text{ CFH} 460 CFH
Branch B (Water Heater) 40 CFH 40\text{ CFH} 40 CFH 80 ft 80\text{ ft} 80 ft 1 / 2 inch 1/2\text{ inch} 1/2 inch 57 CFH 57\text{ CFH} 57 CFH
Trunk 2 (J1 to J2) 200 CFH 200\text{ CFH} 200 CFH 80 ft 80\text{ ft} 80 ft 1 inch 1\text{ inch} 1 inch 220 CFH 220\text{ CFH} 220 CFH
Branch A (Furnace) 100 CFH 100\text{ CFH} 100 CFH 80 ft 80\text{ ft} 80 ft 3 / 4 inch 3/4\text{ inch} 3/4 inch 118 CFH 118\text{ CFH} 118 CFH
Trunk 3 (J2 to J3) 100 CFH 100\text{ CFH} 100 CFH 80 ft 80\text{ ft} 80 ft 3 / 4 inch 3/4\text{ inch} 3/4 inch 118 CFH 118\text{ CFH} 118 CFH
Branch C (Range) 65 CFH 65\text{ CFH} 65 CFH 80 ft 80\text{ ft} 80 ft 3 / 4 inch 3/4\text{ inch} 3/4 inch 118 CFH 118\text{ CFH} 118 CFH
Branch D (Fireplace) 35 CFH 35\text{ CFH} 35 CFH 80 ft 80\text{ ft} 80 ft 1 / 2 inch 1/2\text{ inch} 1/2 inch 57 CFH 57\text{ CFH} 57 CFH
- Tubing Sizing Nuances: Copper & CSST
- Seamless Copper Tubing (Annex A Tables A.8 & A.9)
Copper tubing for fuel gas is ASTM B88 Type K or L, or ASTM B837 Type G. Unlike steel pipe, which is designated by Nominal Pipe Size (NPS) (where 1 / 2 -inch 1/2\text{-inch} 1/2 -inch Schedule 40 has an internal diameter of 0.622 in 0.622\text{ in} 0.622 in and an outside diameter of 0.840 in 0.840\text{ in} 0.840 in ), copper tubing is designated strictly by its Outside Diameter (OD) . Consequently, a 1 / 2 -inch 1/2\text{-inch} 1/2 -inch OD copper tube has an inside diameter of only ≈ 0.430 in \approx 0.430\text{ in} ≈ 0.430 in —significantly smaller than nominal 1 / 2 -inch 1/2\text{-inch} 1/2 -inch steel pipe. Technicians must never use steel pipe tables to size copper tubing; always use the tubing tables in Annex A for the allowed pressure drop (for example Table A.8 at 0.5 in. w.c. 0.5\text{ in. w.c.} 0.5 in. w.c. and Table A.9 at 1 in. w.c. 1\text{ in. w.c.} 1 in. w.c. ).
Corrugated Stainless Steel Tubing (CSST)
CSST features continuous helical or annular corrugations that grant flexibility but induce substantial internal fluid turbulence. Because corrugation geometry varies between manufacturers, CSST cannot be sized with generic pipe tables. Instead, CSST utilizes the Equivalent Hydraulic Diameter (EHD) rating system certified under CSA 6.26 / ANSI LC 1 :
The manufacturer's certified engineering tables must be consulted.
Technicians determine the required EHD number based on gas load and LDL.
If sizing hybrid 2 psig 2\text{ psig} 2 psig CSST systems, the line regulator must be accounted for in the sizing calculation.