Study guide

7.3 Basic Electrical Controls, Switches & Ladder Diagram Schematics

TSSA Gas Technician 3 G3

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Safety & Workplace Practices

1.1 Personal Protective Equipment (PPE) & Worksite Hazard Identification 1.2 WHMIS, GHS, Safety Data Sheets (SDS) & Chemical Safety 1.3 Electrical Safety, Lockout/Tagout (LOTO) & Confined Space Awareness

2 Chapter 2: Fasteners, Hand Tools & Power Tools

2.1 Hand Tools for Gas Piping and Mechanical Assembly 2.2 Power Tools, Threading Machines & Mechanical Fasteners

3 Chapter 3: Testing Instruments & Diagnostics

3.1 Pressure Measurement: U-Tube, Inclined & Digital Manometers 3.2 Electrical Multimeters, Combustion Analyzers & Electronic Leak Detectors

4 Chapter 4: Fuel Gas Properties & Combustion Principles

4.1 Chemical & Physical Properties of Natural Gas vs. Propane 4.2 Combustion Chemistry, Flammability Limits & Ignition Temperatures 4.3 Complete vs. Incomplete Combustion, Carbon Monoxide Hazards & Air Requirements

5 Chapter 5: Ontario Acts, Regulations & G.3 Scope of Authority

5.1 Technical Standards and Safety Act & O. Reg. 215/01 Certification 5.2 O. Reg. 211/01, O. Reg. 212/01 & TSSA Code Adoption Documents (CAD) 5.3 Unacceptable Conditions, Warning Notices & Red Tag Procedures

6 Chapter 6: CSA B149 Code Navigation & General Requirements

6.1 CSA B149.1 & CSA B149.2 Scope, Structure & Key Definitions 6.2 General Installation Rules: Instructions, Access, Clearances & Garages (Clause 4)

7 Chapter 7: Introduction to Electricity & Electrical Safety

7.1 Electrical Fundamentals: Ohm's Law, Power & Circuit Configurations 7.2 Line Voltage (120V) vs. Low Voltage (24V), Transformers & Circuit Protection 7.3 Basic Electrical Controls, Switches & Ladder Diagram Schematics

8 Chapter 8: Technical Manuals, Specifications & Architectural Drawings

8.1 Reading Appliance Rating Plates, Certified Manuals & Specifications 8.2 Architectural Blueprints, Mechanical Drawings & Piping Schematics

9 Chapter 9: Customer Relations, Professional Conduct & Documentation

9.1 Professional Communication, Ethics & Customer Service Standards 9.2 Work Orders, Service Documentation & Red Tag Communication

10 Chapter 10: Piping & Tubing Systems: Materials, Joining & Installation

10.1 Piping & Tubing Materials: Steel, Copper, CSST & Plastic 10.2 Pipe Joining Methods: Threading, Flaring, Brazing & Approved Sealants 10.3 Piping Installation: Supports, Hangers, Drip Legs, Dirt Pockets & Valves

11 Chapter 11: Gas Pipe Sizing, Pressure Testing & Purging Procedures

11.1 Gas Pipe & Tubing Sizing Fundamentals (Tables & Pressure Drop) 11.2 Pressure Testing, Leak Testing & the Ontario Test Tag (Clause 6.22) 11.3 Purging Procedures, Safety Protocols & Leak Detection (Clauses 6.23–6.24)

12 Chapter 12: Gas Appliances, Burners & Combustion Air Fundamentals

12.1 Appliance Classifications, Categories (I–IV), Approvals & Clearances 12.2 Atmospheric & Power Burners: Operation, Aeration & Flame Adjustment 12.3 Ignition Systems & Flame Safeguards: Standing Pilot, HSI, DSI, Thermocouples & Flame Rods 12.4 Combustion Air & Basic Venting Requirements (Clause 8)

7.3 Basic Electrical Controls, Switches & Ladder Diagram Schematics

Key Takeaways Explain This Topic AI

Switch Poles & Throws: Single-Pole Single-Throw (SPST) switches control a single circuit in an on/off state, while Single-Pole Double-Throw (SPDT) switches direct power between two alternative load paths, such as heating versus cooling blower motor speeds.

Normal Contact States: The 'normal' state of electrical contacts (Normally Open [NO] or Normally Closed [NC]) is strictly defined when the device is at rest, de-energized on the shelf, at ambient room temperature, and free from applied pressure or airflow.

Automated Safety Interlocks: Gas heating equipment utilizes specific NC thermal switches (high limits and flame rollout switches) and NO airflow/pressure proving switches wired in series with the gas valve; any safety opening immediately de-energizes the fuel supply.

Ladder Diagram Architecture: In ladder schematics, vertical rails represent the line/hot and neutral/common power sources, horizontal rungs represent individual functional sub-circuits, and all control switches are installed on the hot side of loads to prevent shock hazards when off.

Voltage Drop Diagnostic Logic: Across a closed switch, electrical resistance is near zero and the voltage drop is 0 V 0\text{ V} 0 V ; across an open switch in an active circuit, resistance is infinite, producing a full line or control voltage drop ( 120 V 120\text{ V} 120 V or 24 V 24\text{ V} 24 V ) across its open contacts while downstream loads read 0 V 0\text{ V} 0 V .

Last updated: October 2026

Basic Electrical Controls, Switches & Ladder Diagram Schematics

To ensure fuel gas burns only under safe, controlled, and continuously monitored conditions, gas appliances rely on an interconnected network of manual switches, automated environmental sensors, electromagnetic actuators, and integrated electronic control logic. A Gas Technician 3 (G3) must possess the diagnostic proficiency to interpret industrial ladder schematics, understand the shelf and operating states of electrical contacts, and apply voltage drop principles to troubleshoot complex heating sequences systematically.

1. Electrical Switch Topologies: Poles, Throws, and Contact States

An electrical switch is a mechanical or electromechanical control device designed to connect (close) or disconnect (open) an electrical conducting path within a circuit.

Poles and Throws Classification

Switches are categorized by the number of independent circuits they control ( poles ) and the number of output positions available for each pole ( throws ):

Single-Pole Single-Throw (SPST): Contains one movable contact (one pole) that connects to or disconnects from a single stationary contact (one throw). It serves as a simple on/off switch controlling one circuit. Examples include emergency furnace service switches, primary high-temperature limit switches, and draft inducer pressure switches.

Single-Pole Double-Throw (SPDT): Contains one movable contact (common terminal, COM) that alternates between two separate stationary contacts (one normally closed, one normally open). An SPDT switch routes incoming power to either one load or another, but never both simultaneously. A classic example is a heating/cooling fan relay that directs 120 VAC 120\text{ VAC} 120 VAC to either the high-speed cooling tap or medium-low speed heating tap of a circulating blower motor.

Double-Pole Single-Throw (DPST): Contains two electrically isolated movable poles operated simultaneously by a single mechanical mechanism, each making or breaking one circuit. Commonly used to disconnect both energized 120 V 120\text{ V} 120 V legs (L1 and L2) of a 240 VAC 240\text{ VAC} 240 VAC electric duct heater or commercial water heater.

Double-Pole Double-Throw (DPDT): Contains two isolated poles, each capable of alternating between two separate output contacts. Used for complex interlocks and multi-stage control switching.

The Universal Definition of "Normal" State

In electrical engineering and HVAC schematic drafting, the state of any switch contact—whether designated as Normally Open (NO) or Normally Closed (NC) —is defined under strict, standardized benchmark conditions:

Note

The "Normal" contact state is the condition of the switch contacts when the device is resting on the parts shelf, completely de-energized, at ambient room temperature ( 70 ∘ F / 21 ∘ C 70^\circ\text{F} / 21^\circ\text{C} 7 0 ∘ F /2 1 ∘ C ), and subject to zero external mechanical, thermal, magnetic, or pneumatic forces.

Normally Open (NO) Contacts: Contacts remain physically separated at rest. Current cannot flow through the switch until an external force (temperature change, air pressure, manual depression, or magnetic coil energization) acts upon the mechanism to force the contacts closed.

Normally Closed (NC) Contacts: Contacts remain physically touching at rest under internal spring tension. Current flows freely through the switch until an external force acts upon the mechanism to force the contacts open.

2. Manual and Automated Safety Controls in Gas Appliances

Switches in gas equipment fall into two distinct functional categories: manual switches operated by technicians or homeowners, and automated switches that respond dynamically to environmental conditions.

Manual Switches

Furnace Emergency Disconnect Switch: A wall- or chassis-mounted SPST toggle switch that interrupts 120 VAC 120\text{ VAC} 120 VAC line power to all appliance components.

Blower Compartment Door Interlock Switch: An SPST push-button safety switch mounted inside the circulating air blower compartment frame. When the blower access door is securely fastened, the door panel mechanically depresses the switch plunger, holding its contacts closed . When an installer or homeowner removes the blower access panel, an internal spring pushes the plunger outward, opening the contacts and instantly cutting all line voltage to the furnace. This prevents accidental contact with rotating blower wheels or live electrical terminals.

Automated and Sensing Safety Switches

Automated safety controls protect the building and occupants from fire, combustion product leakage, or structural overheating:

Safety Control Device Sensing Medium Normal State Operating Action Reset Classification Hazard Mitigated

High-Temperature Limit Switch Supply plenum air temperature NC (Normally Closed) Opens when air temperature exceeds threshold ( 170 ∘ F − 200 ∘ F 170^\circ\text{F} - 200^\circ\text{F} 17 0 ∘ F − 20 0 ∘ F ) Automatic reset upon cooling ( 20 ∘ F − 40 ∘ F 20^\circ\text{F} - 40^\circ\text{F} 2 0 ∘ F − 4 0 ∘ F drop) Heat exchanger thermal cracking, fire hazard from air filter blockage

Flame Rollout Switch (FRS) Radiant heat / flame in burner vestibule NC (Normally Closed) Opens upon flame impingement ( 250 ∘ F − 350 ∘ F 250^\circ\text{F} - 350^\circ\text{F} 25 0 ∘ F − 35 0 ∘ F ) Manual reset push-button (or one-time thermal fuse) Blocked flue passes, cracked heat exchanger, severe downdrafts

Combustion Air Pressure Switch Differential draft pressure in vent NO (Normally Open) Closes when inducer establishes negative draft (e.g., − 0.65 in w.c. -0.65\text{ in w.c.} − 0.65 in w.c. ) Automatic reset (opens when inducer stops) Incomplete combustion, carbon monoxide ( CO \text{CO} CO ) release from blocked vent

Draft Hood Spill Switch Temperature of spilling flue gas NC (Normally Closed) Opens if hot flue gas spills out of draft relief opening ( 180 ∘ F 180^\circ\text{F} 18 0 ∘ F ) Manual reset push-button Chimney blockage or backdrafting on atmospheric appliances

Sail Switch / Air Proving Switch Dynamic air velocity in duct NO (Normally Open) Closes when moving airstream deflects mechanical sail/paddle Automatic reset upon airflow loss Burnout of electric heating elements or commercial makeup air burners

3. Electromagnetic Actuators: Relays, Contactors & Solenoid Gas Valves

Electromechanical devices convert electrical energy into physical mechanical movement via magnetic attraction.

Relays

An electromechanical relay consists of four basic components: an electromagnetic coil wound around an iron core, a movable magnetic armature, a mechanical return spring, and one or more sets of electrical contacts.

Operational Principle: When a low-voltage, low-current signal ( 24 VAC 24\text{ VAC} 24 VAC , < 0.1 A < 0.1\text{ A} < 0.1 A ) energizes the relay coil, it creates an intense magnetic field that pulls the armature downward against spring tension, mechanically altering the contact states—closing NO contacts and opening NC contacts.

Isolation Benefit: Relays provide complete electrical isolation between disparate circuits, allowing a sensitive 24 VAC 24\text{ VAC} 24 VAC thermostat circuit to safely switch a high-current 120 VAC 120\text{ VAC} 120 VAC or 240 VAC 240\text{ VAC} 240 VAC blower motor without electrical interconnection.

Contactors

A contactor is essentially a heavy-duty industrial relay engineered to switch high-amperage electrical loads:

Specifications: Equipped with large silver-cadmium oxide contacts capable of handling continuous currents from 20 A 20\text{ A} 20 A to over 60 A 60\text{ A} 60 A and inrush currents exceeding 150 A 150\text{ A} 150 A .

Applications: Used in residential outdoor central air conditioning condensing units, commercial three-phase heat pumps, and high-wattage commercial electric duct heaters. Contactors feature heavy-gauge terminal lugs, replaceable contact sets, and magnetic blowout structures to quench severe electrical arcs.

Solenoid Gas Valves

A solenoid is an electromechanical actuator that produces linear mechanical stroke:

Construction: A copper magnet wire coil surrounds an internal stainless-steel or brass sleeve containing a movable soft-iron core (plunger) held down against a valve seat by a calibrated closing spring.

Operation in Gas Valves: In a modern 24 VAC 24\text{ VAC} 24 VAC redundant gas valve, energizing the valve coil generates a magnetic flux that lifts the iron plunger upward off its synthetic rubber seat against spring resistance, permitting fuel gas to flow through the internal orifices to the main burners.

Failsafe Design: The instant electrical power is interrupted—whether by the room thermostat satisfying, a safety limit opening, or a utility power outage—the magnetic field collapses in milliseconds. The internal spring immediately drives the plunger downward, snapping the gas valve tightly shut to prevent raw gas leakage.

4. Electrical Schematics: Pictorial Wiring vs. Ladder Logic Schematics

To understand how an appliance operates, technicians consult manufacturer wiring diagrams, which are published in two distinct formats:

Pictorial (Connection) Diagrams

A pictorial diagram displays the physical appearance, approximate spatial location, and individual wire runs connecting each component within the appliance cabinet:

Wire colors are explicitly coded (e.g., BLK = Black, WHT = White, RED = Red, BLU = Blue, YEL = Yellow, GRN = Ground).

Terminal strip designations and multi-pin wire harness plug connectors (such as 9-pin or 12-pin Molex plugs) are graphically represented.

Field Use: Essential for locating physical components, tracing wiring harness bundles through cabinet partitions, and verifying correct wire connections after replacing a circuit board or blower motor.

Schematic (Ladder / Elementary) Diagrams

A schematic or ladder diagram strips away all physical geometry, wire bundle paths, and component shapes to display the pure electrical logic and sequence of operation:

Ladder Anatomy:

Vertical Rails: The two outer vertical lines represent the electrical power supply rails. In line-voltage circuits, the left rail represents Line 1 (Hot, 120 VAC 120\text{ VAC} 120 VAC ) and the right rail represents the Neutral ( 0 V 0\text{ V} 0 V to ground) . In low-voltage control circuits, the left rail represents the 24 VAC 24\text{ VAC} 24 VAC Hot (R) and the right rail represents the 24 VAC 24\text{ VAC} 24 VAC Common (C) .

Horizontal Rungs: Each horizontal line spanning between the rails represents an individual operational sub-circuit or logical function.

The Hot-Side Switch Placement Rule: In all standard industrial and residential schematics, control switches and safety interlocks are ALWAYS located on the hot side (L1 or R) of the electrical load , positioned between the hot rail and the load terminal.

Switches are never placed between the load and the neutral/common rail.

If a switch were installed on the neutral side of a motor or solenoid coil, the load would remain energized at full line voltage ( 120 VAC 120\text{ VAC} 120 VAC relative to earth ground) even when the switch was open and the appliance was idle. Any technician touching the load terminals during servicing would become a path to ground, resulting in fatal electric shock.

5. Systematic Troubleshooting: Voltage Drop Principles & Hopscotching

The most powerful diagnostic skill in electrical heating service is the systematic evaluation of voltage drops across switches and loads.

Voltage Drop Principles across Closed vs. Open Switches

By Ohm's Law ( V = I × R V = I \times R V = I × R ), voltage drop across any electrical component depends strictly on its internal resistance and the circuit current:

Measuring Across a Closed Switch:

A properly operating closed switch presents zero or negligible resistance across its metal contacts ( R ≈ 0 Ω R \approx 0\,\Omega R ≈ 0 Ω ).

Because R ≈ 0 Ω R \approx 0\,\Omega R ≈ 0 Ω , multiplying current by resistance yields zero: V drop = I × 0 Ω = 0 Volts V_{\text{drop}} = I \times 0\,\Omega = 0\text{ Volts} V drop ​ = I × 0 Ω = 0 Volts

Conclusion: A voltmeter placed directly across the terminals of a closed switch in an energized, operating circuit reads 0 VAC 0\text{ VAC} 0 VAC . The full source voltage passes unimpeded to the downstream load.

Measuring Across an Open Switch:

An open switch separates its contacts with an air gap, representing virtually infinite electrical resistance ( R = ∞ Ω R = \infty\,\Omega R = ∞ Ω ).

When a technician connects a high-impedance digital multimeter across the open switch contacts, the meter itself completes the series circuit.

Because the multimeter's internal resistance is enormous ( > 10 M Ω > 10\text{ M}\Omega > 10 M Ω ) compared to the few ohms of the downstream load coil, virtually 100% of the circuit voltage drops across the meter leads.

Conclusion: A voltmeter placed across an open switch in an active, energized circuit reads FULL SOURCE VOLTAGE ( 120 VAC 120\text{ VAC} 120 VAC or 24 VAC 24\text{ VAC} 24 VAC ) . Downstream loads receive 0 V 0\text{ V} 0 V and remain de-energized.

Measuring Across a Defective (Pitted) Switch:

If contacts are burned or corroded, they exhibit measurable resistance (e.g., 10 Ω 10\,\Omega 10 Ω ).

Current flowing through this resistance creates an unwanted voltage drop ( V = I × R V = I \times R V = I × R , e.g., 3 to 8 VAC 3\text{ to }8\text{ VAC} 3 to 8 VAC fractionally), starving the downstream gas valve or relay coil of required operating voltage.

The "Hopscotching" Diagnostic Technique

When a gas furnace fails to energize its gas valve despite a demand for heat, technicians isolate open safeties in seconds using the hopscotching technique :

Connect the black (negative/reference) lead of a digital voltmeter permanently to the 24 VAC 24\text{ VAC} 24 VAC Common (C) terminal on the control board or transformer secondary.

Ensure the room thermostat is calling for heat (verifying 24 VAC 24\text{ VAC} 24 VAC between R and C , and between W and C ).

Take the red probe and test each test terminal sequentially down the series safety string, moving from the hot source toward the gas valve:

Test Input of High Limit Switch → \to → Reads 24 VAC 24\text{ VAC} 24 VAC (Power is entering limit).

Test Output of High Limit Switch → \to → Reads 24 VAC 24\text{ VAC} 24 VAC (High limit is closed and healthy).

Test Input of Flame Rollout Switch → \to → Reads 24 VAC 24\text{ VAC} 24 VAC (Power is entering rollout).

Test Output of Flame Rollout Switch → \to → Reads 0 VAC 0\text{ VAC} 0 VAC !

Diagnosis: Because voltage is present at the input terminal of the flame rollout switch but disappears at its output terminal, the rollout switch is open or tripped . The technician has conclusively identified the defective component without disconnecting a single wire.

Loading diagram... Voltage Drop Behavior Across Closed vs. Open Switches in an Energized Circuit