Study guide

5.2 O. Reg. 211/01, O. Reg. 212/01 & TSSA Code Adoption Documents (CAD)

TSSA Gas Technician 3 G3

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Safety & Workplace Practices

1.1 Personal Protective Equipment (PPE) & Worksite Hazard Identification 1.2 WHMIS, GHS, Safety Data Sheets (SDS) & Chemical Safety 1.3 Electrical Safety, Lockout/Tagout (LOTO) & Confined Space Awareness

2 Chapter 2: Fasteners, Hand Tools & Power Tools

2.1 Hand Tools for Gas Piping and Mechanical Assembly 2.2 Power Tools, Threading Machines & Mechanical Fasteners

3 Chapter 3: Testing Instruments & Diagnostics

3.1 Pressure Measurement: U-Tube, Inclined & Digital Manometers 3.2 Electrical Multimeters, Combustion Analyzers & Electronic Leak Detectors

4 Chapter 4: Fuel Gas Properties & Combustion Principles

4.1 Chemical & Physical Properties of Natural Gas vs. Propane 4.2 Combustion Chemistry, Flammability Limits & Ignition Temperatures 4.3 Complete vs. Incomplete Combustion, Carbon Monoxide Hazards & Air Requirements

5 Chapter 5: Ontario Acts, Regulations & G.3 Scope of Authority

5.1 Technical Standards and Safety Act & O. Reg. 215/01 Certification 5.2 O. Reg. 211/01, O. Reg. 212/01 & TSSA Code Adoption Documents (CAD) 5.3 Unacceptable Conditions, Warning Notices & Red Tag Procedures

6 Chapter 6: CSA B149 Code Navigation & General Requirements

6.1 CSA B149.1 & CSA B149.2 Scope, Structure & Key Definitions 6.2 General Installation Rules: Instructions, Access, Clearances & Garages (Clause 4)

7 Chapter 7: Introduction to Electricity & Electrical Safety

7.1 Electrical Fundamentals: Ohm's Law, Power & Circuit Configurations 7.2 Line Voltage (120V) vs. Low Voltage (24V), Transformers & Circuit Protection 7.3 Basic Electrical Controls, Switches & Ladder Diagram Schematics

8 Chapter 8: Technical Manuals, Specifications & Architectural Drawings

8.1 Reading Appliance Rating Plates, Certified Manuals & Specifications 8.2 Architectural Blueprints, Mechanical Drawings & Piping Schematics

9 Chapter 9: Customer Relations, Professional Conduct & Documentation

9.1 Professional Communication, Ethics & Customer Service Standards 9.2 Work Orders, Service Documentation & Red Tag Communication

10 Chapter 10: Piping & Tubing Systems: Materials, Joining & Installation

10.1 Piping & Tubing Materials: Steel, Copper, CSST & Plastic 10.2 Pipe Joining Methods: Threading, Flaring, Brazing & Approved Sealants 10.3 Piping Installation: Supports, Hangers, Drip Legs, Dirt Pockets & Valves

11 Chapter 11: Gas Pipe Sizing, Pressure Testing & Purging Procedures

11.1 Gas Pipe & Tubing Sizing Fundamentals (Tables & Pressure Drop) 11.2 Pressure Testing, Leak Testing & the Ontario Test Tag (Clause 6.22) 11.3 Purging Procedures, Safety Protocols & Leak Detection (Clauses 6.23–6.24)

12 Chapter 12: Gas Appliances, Burners & Combustion Air Fundamentals

12.1 Appliance Classifications, Categories (I–IV), Approvals & Clearances 12.2 Atmospheric & Power Burners: Operation, Aeration & Flame Adjustment 12.3 Ignition Systems & Flame Safeguards: Standing Pilot, HSI, DSI, Thermocouples & Flame Rods 12.4 Combustion Air & Basic Venting Requirements (Clause 8)

5.2 O. Reg. 211/01, O. Reg. 212/01 & TSSA Code Adoption Documents (CAD)

Key Takeaways Explain This Topic AI

O. Reg. 212/01 is the Gaseous Fuels regulation and O. Reg. 211/01 is the Propane Storage and Handling regulation; each adopts national codes through its own Code Adoption Document under O. Reg. 223/01.

Gaseous Fuels CAD amendment FS-279-26 adopted CSA B149.1-25 with Ontario amendments effective June 1, 2026, replacing the 2021 adoption of B149.1-20.

Under O. Reg. 212/01 s. 8, a gas distributor has access at reasonable times and on reasonable notice to examine appliances and disconnect any that do not conform to the regulation.

Under O. Reg. 212/01 s. 12, apparent carbon monoxide poisoning, asphyxiation, explosion or fire caused by gas must be reported forthwith to a TSSA inspector.

The Gaseous Fuels CAD states that where it conflicts with an adopted code, the CAD prevails—so Ontario amendments override the national B149.1 text.

Last updated: October 2026

Ontario does not regulate natural gas and propane under one rule book. Each fuel has its own regulation under the TSS Act, and each regulation adopts national CSA codes through a Code Adoption Document (CAD) . Mixing up the regulation numbers is one of the most common G.3 exam errors, so learn this pairing first.

1. The Regulatory Map

Instrument Covers Codes it brings into force

O. Reg. 212/01 – Gaseous Fuels Natural gas (and the other "gases" defined in its CAD) — appliances, piping, distributors, contractors Gaseous Fuels CAD : CSA B149.1-25 with Ontario amendments, CSA B149.3-25 (field approval), B149.3 Annex J (mobile food service equipment), CSA B149.6-25 (biogas) and NFPA 160 (flame effects) — amendment FS-279-26, effective June 1, 2026

O. Reg. 211/01 – Propane Storage and Handling Propane storage, handling, filling, distribution, propane appliances and works Propane CAD (adopts CSA B149.2, the propane storage and handling code, with Ontario amendments)

O. Reg. 215/01 – Fuel Industry Certificates Who may do fuel work (G.1, G.2, G.3 and others) —

O. Reg. 223/01 – Codes and Standards Adopted by Reference The mechanism that lets a director adopt and amend codes through CADs —

FS-279-26 replaced the 2021 Gaseous Fuels CAD (which had adopted B149.1-20). From June 1, 2026, the B149.1 edition you use in Ontario—and bring to the exam—is B149.1-25 as amended by the CAD .

2. O. Reg. 212/01 (Gaseous Fuels): Sections a G.3 Must Know

Section Rule

s. 4 Where approval is required, no one may sell, lease or install an appliance, equipment or thing unless it is approved (with listed exceptions such as Bunsen burners and manually operated industrial appliances of 20,000 Btu/h or less)

s. 5 No one may handle gas without a licence for that purpose

s. 6 No one may install, alter, purge, activate, repair, service or remove gas equipment without a certificate for that purpose; s. 6(3) allows an uncertified person to do the work in the presence of the certificate holder

s. 7 Where premises are connected to gas for the first time, no appliance may be put into use until the distributor has examined the installation and is satisfied it complies

s. 8 The distributor has access at all reasonable times, on reasonable notice, to examine appliances and disconnect any that do not conform, and to work on its meters and regulators

s. 11 Employers must instruct employees to comply and take every reasonable precaution to ensure they do

s. 12 If carbon monoxide poisoning, asphyxiation, explosion or fire appears to have occurred because of gas, a certificate holder, contractor or distributor must forthwith notify an inspector ; the scene must not be disturbed except for public safety, saving life, relieving suffering, continuity of service or preserving property

  • s. 13–14 Unacceptable conditions, with and without immediate hazard (see section 5.3)
  • s. 15 Owners and users must keep appliances and works in safe operating condition

s. 16 A distributor may not supply gas unless satisfied the installation complies and it has been inspected within the previous 10 years or under a quality-assurance inspection program

s. 17 Owners of special (industrial, institutional, assembly) buildings must have maintenance procedures evaluated and the appliances inspected at least once every 10 years

s. 21 No one may act as a contractor unless registered; registration expires one year after issue, a late renewal is treated as a new application, evidence of registration is displayed at the business, and address changes are reported within 30 days

3. O. Reg. 211/01 (Propane Storage and Handling)

O. Reg. 211/01 mirrors much of the gaseous-fuels structure for propane: certificates and contractor registration, distributor access, occurrence reporting, and unacceptable conditions (ss. 19–20, with the same shut-off and notice steps as O. Reg. 212/01). It adds rules for cylinder handling facilities, filling plants, container refill centres, tank trucks and licensing.

Risk and Safety Management Plans (s. 3.1)

Retail outlets, filling plants, cardlock/keylock sites, private outlets and container refill centres must file a risk and safety management plan (RSMP) with the director. A Level 1 plan applies to smaller facilities—no more than 5,000 USWG total capacity (or 5,000 USWG fixed plus no more than 500 USWG portable storage); larger facilities file a Level 2 plan.

Safe handling of propane cylinders

Filling limit: propane cylinders are filled by weight to a maximum filling density of 42% of their water capacity . Liquid propane expands roughly 1.5% for every 10°F rise, so the remaining vapour space (about 20% by volume) is the safety cushion.

Requalification: Transport Canada (CSA B339) cylinders must not be refilled once their requalification date has passed; a new TC/DOT propane cylinder is due for requalification 10 years after its date of manufacture, and a registered facility re-stamps it.

Location: CSA B149.2's location rules keep a cylinder's relief-valve discharge at least 3 ft (1 m) from any building opening and 10 ft (3 m) from any mechanical air intake, because propane vapour sinks and flows into openings.

On construction projects O. Reg. 213/91 s. 122 requires welding and cutting cylinders to be protected from damage, never transported or stored lying horizontally, and to have their valves closed when not in use.

The filling-by-weight calculation: Maximum propane mass = 0.42 × Water capacity (WC) \text{Maximum propane mass} = 0.42 \times \text{Water capacity (WC)} Maximum propane mass = 0.42 × Water capacity (WC) Full-scale reading = Tare weight (TW) + 0.42 × WC \text{Full-scale reading} = \text{Tare weight (TW)} + 0.42 \times \text{WC} Full-scale reading = Tare weight (TW) + 0.42 × WC

Example: a cylinder stamped WC 47.6 lb and TW 17 lb holds at most 0.42 × 47.6 ≈ 20 lb 0.42 \times 47.6 \approx 20\text{ lb} 0.42 × 47.6 ≈ 20 lb of propane, so the scale should read about 37 lb when full.

4. How a Code Adoption Document Works

A CSA code is a private standard; it becomes enforceable in Ontario only when a CAD adopts it under O. Reg. 223/01 . FS-279-26 says so in plain terms: the Director for O. Reg. 212/01, acting under s. 6(1) of O. Reg. 223/01, revoked and replaced the whole Gaseous Fuels CAD. The CAD then states that "in the event of conflict between a provision of this document and any code or standard referred to in this document, this document shall prevail."

Ontario amendments worth tabbing

  • CAD item Ontario rule
  • 4.1.5 Where certified instructions and the code conflict, the more stringent prevails

4.5.5 An appliance exposed to fire, explosion, flood or other damage may not be sold, installed, re-activated or reconnected without AHJ approval or inspection and confirmation by a G.1 or G.2

6.13.2(a) Drip or dirt pocket depth: at least 3 in. (75 mm) or the pipe's internal diameter, whichever is greater

6.15.4 Buried piping: at least 15 in. (400 mm) of cover, 24 in. (600 mm) under a commercial driveway or parking lot; Annex P for rocky ground

6.18.2 Manual shut-off valve location and tagging (within 50 ft of a residential appliance)

Table 6.3 note 2 Wrapped or factory-coated piping (other than CSST and coated copper) is pressure tested at least 100 psig

  • 6.22.7–6.22.8 Mandatory pressure test tag or sticker
  • 7.1.13 / Annex Q Seasonal CO and safety checks on residential natural-draft boilers of 300,000 Btu/h or less
  • 8.17.3 / Annex R Non-compliant B-vent installed outdoors
  • Orders and guidance

A director's safety order under TSS Act s. 14 is mandatory. TSSA advisories, bulletins and guidelines explain how TSSA reads the code, but the binding text is the regulation, the CAD and the codes it adopts.

Loading diagram... Ontario Fuel Regulations, CADs and Adopted Codes