3.2 Electrical Multimeters, Combustion Analyzers & Electronic Leak Detectors
TSSA Gas Technician 3 G3
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Safety & Workplace Practices
1.1 Personal Protective Equipment (PPE) & Worksite Hazard Identification 1.2 WHMIS, GHS, Safety Data Sheets (SDS) & Chemical Safety 1.3 Electrical Safety, Lockout/Tagout (LOTO) & Confined Space Awareness
2 Chapter 2: Fasteners, Hand Tools & Power Tools
2.1 Hand Tools for Gas Piping and Mechanical Assembly 2.2 Power Tools, Threading Machines & Mechanical Fasteners
3 Chapter 3: Testing Instruments & Diagnostics
3.1 Pressure Measurement: U-Tube, Inclined & Digital Manometers 3.2 Electrical Multimeters, Combustion Analyzers & Electronic Leak Detectors
4 Chapter 4: Fuel Gas Properties & Combustion Principles
4.1 Chemical & Physical Properties of Natural Gas vs. Propane 4.2 Combustion Chemistry, Flammability Limits & Ignition Temperatures 4.3 Complete vs. Incomplete Combustion, Carbon Monoxide Hazards & Air Requirements
5 Chapter 5: Ontario Acts, Regulations & G.3 Scope of Authority
5.1 Technical Standards and Safety Act & O. Reg. 215/01 Certification 5.2 O. Reg. 211/01, O. Reg. 212/01 & TSSA Code Adoption Documents (CAD) 5.3 Unacceptable Conditions, Warning Notices & Red Tag Procedures
6 Chapter 6: CSA B149 Code Navigation & General Requirements
6.1 CSA B149.1 & CSA B149.2 Scope, Structure & Key Definitions 6.2 General Installation Rules: Instructions, Access, Clearances & Garages (Clause 4)
7 Chapter 7: Introduction to Electricity & Electrical Safety
7.1 Electrical Fundamentals: Ohm's Law, Power & Circuit Configurations 7.2 Line Voltage (120V) vs. Low Voltage (24V), Transformers & Circuit Protection 7.3 Basic Electrical Controls, Switches & Ladder Diagram Schematics
8 Chapter 8: Technical Manuals, Specifications & Architectural Drawings
8.1 Reading Appliance Rating Plates, Certified Manuals & Specifications 8.2 Architectural Blueprints, Mechanical Drawings & Piping Schematics
9 Chapter 9: Customer Relations, Professional Conduct & Documentation
9.1 Professional Communication, Ethics & Customer Service Standards 9.2 Work Orders, Service Documentation & Red Tag Communication
10 Chapter 10: Piping & Tubing Systems: Materials, Joining & Installation
10.1 Piping & Tubing Materials: Steel, Copper, CSST & Plastic 10.2 Pipe Joining Methods: Threading, Flaring, Brazing & Approved Sealants 10.3 Piping Installation: Supports, Hangers, Drip Legs, Dirt Pockets & Valves
11 Chapter 11: Gas Pipe Sizing, Pressure Testing & Purging Procedures
11.1 Gas Pipe & Tubing Sizing Fundamentals (Tables & Pressure Drop) 11.2 Pressure Testing, Leak Testing & the Ontario Test Tag (Clause 6.22) 11.3 Purging Procedures, Safety Protocols & Leak Detection (Clauses 6.23–6.24)
12 Chapter 12: Gas Appliances, Burners & Combustion Air Fundamentals
12.1 Appliance Classifications, Categories (I–IV), Approvals & Clearances 12.2 Atmospheric & Power Burners: Operation, Aeration & Flame Adjustment 12.3 Ignition Systems & Flame Safeguards: Standing Pilot, HSI, DSI, Thermocouples & Flame Rods 12.4 Combustion Air & Basic Venting Requirements (Clause 8)
3.2 Electrical Multimeters, Combustion Analyzers & Electronic Leak Detectors
Key Takeaways Explain This Topic AI
Gas technicians must use Digital Multimeters with a minimum rating of CAT III 600V or 1000V equipped with high-energy ceramic fuses.
Flame rectification current is measured in DC microamperes ( μ A \mu\text{A} μ A ) wired in series with the flame rod, with typical healthy readings between 1.0 μ A and 5.0 μ A DC 1.0\ \mu\text{A}\text{ and }5.0\ \mu\text{A}\text{ DC} 1.0 μ A and 5.0 μ A DC .
Household dish soaps can contain chlorides and ammonia that promote stress corrosion cracking (SCC) in brass fittings and CSST, so use a non-corrosive leak-detection solution as CSST and fitting manufacturers require.
Combustible gas leak sniffers detect hydrocarbons down to tens of ppm but must warm up in clean outdoor air; pinpoint a reading with a leak-detection solution before repairing the joint.
Air-free CO is calculated as CO air-free = CO measured × [ 20.9 / ( 20.9 − % O 2 ) ] \text{CO}_{\text{air-free}} = \text{CO}_{\text{measured}} \times [20.9 / (20.9 - \%O_2)] CO air-free = CO measured × [ 20.9/ ( 20.9 − % O 2 )] ; 400 ppm 400\text{ ppm} 400 ppm air-free is the laboratory certification limit in ANSI Z21/CSA appliance standards, not a CSA B149.1 field limit.
Last updated: October 2026
Electrical Multimeters, Combustion Analyzers & Leak Detectors
Modern gas appliances rely on solid-state electronics, microprocessor controls, flame rectification sensors, and power draft inducers. Safe servicing requires competence not only with gas pressures, but also with digital multimeters (DMMs), electronic combustible gas detectors, approved chemical bubble solutions, and flue gas combustion analyzers. Under Ontario Regulation 215/01 and the CSA B149.1 Installation Code, an Ontario Gas Technician 3 (G3) must master these diagnostic tools to isolate electrical faults, confirm flame safety shutdown, verify piping gas-tightness, and evaluate combustion efficiency.
Digital Multimeters: Meter Selection, CAT Ratings & Safety
Gas technicians service line voltage ( 120 VAC 120\text{ VAC} 120 VAC ) and low-voltage control circuits ( 24 VAC 24\text{ VAC} 24 VAC , 5 to 24 VDC 5\text{ to }24\text{ VDC} 5 to 24 VDC ). Using an unrated meter presents serious shock and arc-flash hazards.
Under IEC/CSA 61010 standards, test instruments are classified by Overvoltage Categories:
CAT I: Signal-level electronics and circuit boards isolated from mains.
CAT II: Portable tools and single-phase plug-in branch receptacles.
CAT III: Distribution wiring, feeder panels, and hardwired equipment including furnaces, boilers, and water heaters.
CAT IV: Origin of utility electrical service, outdoor conductors, and electricity meters.
Warning
Gas technicians must use a multimeter rated at least CAT III 600V or CAT III 1000V / CAT IV 600V . HVAC service exposes instruments to transient voltage spikes reaching 6 , 000 V 6,000\text{ V} 6 , 000 V from inductive motor switching. Professional meters use high-energy, fast-acting ceramic fuses (HRC fuses) engineered to safely quench arc faults inside the meter body.
Always practice the Live-Dead-Live protocol: test the multimeter on a known live voltage source, verify zero voltage on the de-energized appliance circuit, and re-test on the known live source to confirm meter operation.
Core Electrical Diagnostics on Gas Heating Equipment
A professional DMM performs four primary measurements in heating system diagnostics:
1. AC Voltage ( 120 VAC 120\text{ VAC} 120 VAC and 24 VAC 24\text{ VAC} 24 VAC )
Line Voltage: Line ( L 1 L_1 L 1 ) to Neutral ( N N N ) confirms nominal utility power ( 115 to 125 VAC 115\text{ to }125\text{ VAC} 115 to 125 VAC ). Measuring L 1 L_1 L 1 to Ground should also read 120 VAC 120\text{ VAC} 120 VAC .
Polarity and Grounding: Neutral to Ground must register under 2.0 VAC 2.0\text{ VAC} 2.0 VAC (ideally 0.0 VAC 0.0\text{ VAC} 0.0 VAC ). A reading of 120 VAC 120\text{ VAC} 120 VAC indicates reversed polarity, which blinds flame safeguard controls and triggers safety lockouts.
Low-Voltage Control: The step-down transformer secondary supplies 24 VAC 24\text{ VAC} 24 VAC between R R R and C C C . A reading of 24 VAC 24\text{ VAC} 24 VAC across safety switch terminals indicates an open safety control.
2. Resistance and Continuity (Ohms, Ω \Omega Ω )
Resistance testing must only be performed on de-energized, isolated circuits:
Gas Valve Coils: Dual solenoid shut-off valves contain coils typically measuring 20 Ω to 100 Ω 20\ \Omega\text{ to }100\ \Omega 20 Ω to 100 Ω . An infinite reading ( O.L. \text{O.L.} O.L. ) indicates an open, failed coil.
Hot Surface Igniters (HSI): Silicon carbide igniters measure 40 Ω to 100 Ω 40\ \Omega\text{ to }100\ \Omega 40 Ω to 100 Ω cold at room temperature; replace if above 100 Ω 100\ \Omega 100 Ω . Silicon nitride igniters operate between 10 Ω and 20 Ω 10\ \Omega\text{ and }20\ \Omega 10 Ω and 20 Ω .
Transformer Windings: The primary winding typically measures 50 Ω to 150 Ω 50\ \Omega\text{ to }150\ \Omega 50 Ω to 150 Ω ; the secondary measures 1 Ω to 5 Ω 1\ \Omega\text{ to }5\ \Omega 1 Ω to 5 Ω .
Flame Rectification Testing (DC Microamperes)
Modern automatic gas burners verify flame presence through flame rectification. Ionized gas molecules in combustion flames conduct electrical current.
Because the grounded burner metal surface area is much larger than the slender flame rod (typically a 4 : 1 4:1 4 : 1 ratio or greater), alternating current ( 120 VAC 120\text{ VAC} 120 VAC ) applied to the sensor passes more readily in one direction. The flame acts as a half-wave rectifier, converting AC voltage into a tiny direct current measured in DC microamperes ( μ A \mu\text{A} μ A ): 1 μ A = 1 × 10 − 6 A = 0.000001 A 1\ \mu\text{A} = 1 \times 10^{-6}\text{ A} = 0.000001\text{ A} 1 μ A = 1 × 1 0 − 6 A = 0.000001 A
Diagnostic Procedure
To measure flame rectification signal:
Disconnect power to the appliance and remove the flame sensor lead wire.
Configure the DMM to DC Microamperes ( DC μ A \text{DC }\mu\text{A} DC μ A ).
Connect the meter test leads in series : one lead to the flame rod terminal and the other to the wire leading to the control board.
Restore power, initiate a heating call, and record the microampere reading once main flame establishes.
Flame Current Reading Operating Status Diagnostic Action
0.0 μ A to 0.4 μ A 0.0\ \mu\text{A}\text{ to }0.4\ \mu\text{A} 0.0 μ A to 0.4 μ A Flame Dropout / Lockout Burners extinguish within trial time. Clean rod, check ground.
0.5 μ A to 0.9 μ A 0.5\ \mu\text{A}\text{ to }0.9\ \mu\text{A} 0.5 μ A to 0.9 μ A Marginal Signal Near dropout limit. Intermittent lockouts; clean or replace rod.
1.0 μ A to 5.0 μ A 1.0\ \mu\text{A}\text{ to }5.0\ \mu\text{A} 1.0 μ A to 5.0 μ A Normal Operation Healthy flame rectification signal.
Low readings typically stem from non-conductive silica or carbon glaze on the rod, an oxidized burner ground wire, or flame lifting caused by excessive manifold pressure. Clean rods with fine steel wool or a fine abrasive pad as the appliance manufacturer directs; never use coarse sandpaper.
Combustible Gas Leak Detectors (Sniffers)
Electronic combustible gas sniffers detect hydrocarbon fuel gases at concentrations down to roughly 20 to 50 ppm 20\text{ to }50\text{ ppm} 20 to 50 ppm (about 0.04 % to 0.1 % 0.04\%\text{ to }0.1\% 0.04% to 0.1% of the methane LEL).
Sensor Mechanisms & Protocols
Catalytic Bead Sensors (Pellistors): Combustible gas oxidizes on a heated catalytic bead, raising temperature and resistance relative to an inactive reference bead in a Wheatstone bridge.
Metal Oxide Semiconductor (MOS) Sensors: Fuel gas reacts with a heated tin dioxide ( SnO 2 \text{SnO}_2 SnO 2 ) element, lowering electrical resistance across methane, propane, and butane.
Clean-Air Calibration: Sniffers must always be turned on and warmed up ( 30 to 120 seconds 30\text{ to }120\text{ seconds} 30 to 120 seconds ) in clean outdoor air. Starting inside a gas-filled room zeros out background levels, blinding the sensor.
False Positives: Volatile organic compounds (pipe dope, PVC primer, spray lubricants) trigger false alarms or contaminate catalytic beads.
Screening Role: Sniffers identify the general area of a leak quickly. CSA B149.1 Clause 6.22.3 accepts either a liquid solution or a leak-detection device; most technicians pinpoint a sniffer reading with solution before repairing the joint.
Approved Liquid Leak Detection Solutions
CSA B149.1 Clause 6.22 covers pressure testing of new piping (air, inert gas, or carbon dioxide) and the leak test after gas is introduced, when every connection is checked with a liquid solution or a leak-detection device.
Important
Never use household dishwashing soap or laundry detergent to test gas piping joints, brass fittings, or corrugated stainless steel tubing (CSST). Dish soaps contain chlorides, sulfates, and ammonia. Chlorides attack metal grain boundaries, causing stress corrosion cracking (SCC) in brass, copper, and stainless steel. This chemical attack causes catastrophic joint failure months or years after installation.
Purpose-made leak detection fluids are formulated to be:
Chloride-Free: Chemically neutral formulation prevents stress corrosion cracking.
Persistent Bubbling: High-surface-tension surfactants create durable foaming bubbles over pinhole leaks even under low gas pressures.
Freeze-Protected: Winterized formulations are rated down to − 40 ∘ C -40^\circ\text{C} − 4 0 ∘ C ( − 40 ∘ F -40^\circ\text{F} − 4 0 ∘ F ) for winter outdoor service in Ontario.
Flue Gas Combustion Analysis & Carbon Monoxide Diagnostics
Electronic combustion analyzers draw flue gas through a stainless steel probe inserted into the venting system, utilizing electrochemical cells to measure oxygen ( O 2 \text{O}_2 O 2 ) and carbon monoxide ( CO \text{CO} CO ), while a thermocouple measures net stack temperature. An internal processor calculates carbon dioxide ( CO 2 \text{CO}_2 CO 2 ), excess air, and combustion efficiency.
Stoichiometric Benchmarks
To ensure complete combustion and prevent soot or carbon monoxide formation, appliances operate with controlled excess air:
Combustion Metric Natural Gas (Atmospheric) Propane (Atmospheric) High-Efficiency Condensing (NG)
Oxygen ( O 2 \text{O}_2 O 2 ) 6.0 % to 9.0 % 6.0\%\text{ to }9.0\% 6.0% to 9.0% 6.0 % to 9.0 % 6.0\%\text{ to }9.0\% 6.0% to 9.0% 4.0 % to 7.0 % 4.0\%\text{ to }7.0\% 4.0% to 7.0%
Carbon Dioxide ( CO 2 \text{CO}_2 CO 2 ) 7.0 % to 8.5 % 7.0\%\text{ to }8.5\% 7.0% to 8.5% 8.0 % to 10.0 % 8.0\%\text{ to }10.0\% 8.0% to 10.0% 8.0 % to 9.5 % 8.0\%\text{ to }9.5\% 8.0% to 9.5%
Max Theoretical CO 2 \text{CO}_2 CO 2 11.7 % 11.7\% 11.7% 13.7 % 13.7\% 13.7% 11.7 % 11.7\% 11.7%
Net Stack Temp 175 ∘ C to 260 ∘ C 175^\circ\text{C}\text{ to }260^\circ\text{C} 17 5 ∘ C to 26 0 ∘ C 175 ∘ C to 260 ∘ C 175^\circ\text{C}\text{ to }260^\circ\text{C} 17 5 ∘ C to 26 0 ∘ C 38 ∘ C to 55 ∘ C 38^\circ\text{C}\text{ to }55^\circ\text{C} 3 8 ∘ C to 5 5 ∘ C
Air-Free Carbon Monoxide Calculation
Excess combustion air dilutes flue gas, masking high carbon monoxide production. Combustion analyzers and appliance standards therefore express CO on an air-free basis ( CO air-free \text{CO}_{\text{air-free}} CO air-free ) , normalizing readings to stoichiometric air: CO air-free = CO measured × ( 20.9 20.9 − % O 2 ) \text{CO}_{\text{air-free}} = \text{CO}_{\text{measured}} \times \left(\frac{20.9}{20.9 - \%O_2}\right) CO air-free = CO measured × ( 20.9 − % O 2 20.9 )
For example, an analyzer measuring 60 ppm CO 60\text{ ppm CO} 60 ppm CO in a flue sample with 8.9 % O 2 8.9\%\text{ O}_2 8.9% O 2 calculates: CO air-free = 60 × ( 20.9 20.9 − 8.9 ) = 60 × 1.7417 = 104.5 ppm \text{CO}_{\text{air-free}} = 60 \times \left(\frac{20.9}{20.9 - 8.9}\right) = 60 \times 1.7417 = 104.5\text{ ppm} CO air-free = 60 × ( 20.9 − 8.9 20.9 ) = 60 × 1.7417 = 104.5 ppm
The often-quoted 400 ppm 400\text{ ppm} 400 ppm air-free figure is the laboratory certification limit used in ANSI Z21/CSA appliance standards (for example ANSI Z21.47/CSA 2.3 for central furnaces); it is not a CSA B149.1 field pass mark. In the field, compare readings with the manufacturer's instructions and investigate any CO well above the appliance's normal baseline. Ontario does set one hard number: the Gaseous Fuels Code Adoption Document (clause 7.1.13, Annex Q) requires G.1, G.2, and G.3 technicians servicing a residential natural-draft boiler of 300,000 Btu/h 300{,}000\text{ Btu/h} 300 , 000 Btu/h or less between October 15 and April 30 to measure CO upstream of the draft control device. Above 100 ppm 100\text{ ppm} 100 ppm the boiler is an immediate hazard: correct it, or shut off the fuel and give the notices required by O. Reg. 212/01 s. 13.