3.1 Pressure Measurement: U-Tube, Inclined & Digital Manometers

TSSA Gas Technician 3 G3

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Safety & Workplace Practices

1.1 Personal Protective Equipment (PPE) & Worksite Hazard Identification 1.2 WHMIS, GHS, Safety Data Sheets (SDS) & Chemical Safety 1.3 Electrical Safety, Lockout/Tagout (LOTO) & Confined Space Awareness

2 Chapter 2: Fasteners, Hand Tools & Power Tools

2.1 Hand Tools for Gas Piping and Mechanical Assembly 2.2 Power Tools, Threading Machines & Mechanical Fasteners

3 Chapter 3: Testing Instruments & Diagnostics

3.1 Pressure Measurement: U-Tube, Inclined & Digital Manometers 3.2 Electrical Multimeters, Combustion Analyzers & Electronic Leak Detectors

4 Chapter 4: Fuel Gas Properties & Combustion Principles

4.1 Chemical & Physical Properties of Natural Gas vs. Propane 4.2 Combustion Chemistry, Flammability Limits & Ignition Temperatures 4.3 Complete vs. Incomplete Combustion, Carbon Monoxide Hazards & Air Requirements

5 Chapter 5: Ontario Acts, Regulations & G.3 Scope of Authority

5.1 Technical Standards and Safety Act & O. Reg. 215/01 Certification 5.2 O. Reg. 211/01, O. Reg. 212/01 & TSSA Code Adoption Documents (CAD) 5.3 Unacceptable Conditions, Warning Notices & Red Tag Procedures

6 Chapter 6: CSA B149 Code Navigation & General Requirements

6.1 CSA B149.1 & CSA B149.2 Scope, Structure & Key Definitions 6.2 General Installation Rules: Instructions, Access, Clearances & Garages (Clause 4)

7 Chapter 7: Introduction to Electricity & Electrical Safety

7.1 Electrical Fundamentals: Ohm's Law, Power & Circuit Configurations 7.2 Line Voltage (120V) vs. Low Voltage (24V), Transformers & Circuit Protection 7.3 Basic Electrical Controls, Switches & Ladder Diagram Schematics

8 Chapter 8: Technical Manuals, Specifications & Architectural Drawings

8.1 Reading Appliance Rating Plates, Certified Manuals & Specifications 8.2 Architectural Blueprints, Mechanical Drawings & Piping Schematics

9 Chapter 9: Customer Relations, Professional Conduct & Documentation

9.1 Professional Communication, Ethics & Customer Service Standards 9.2 Work Orders, Service Documentation & Red Tag Communication

10 Chapter 10: Piping & Tubing Systems: Materials, Joining & Installation

10.1 Piping & Tubing Materials: Steel, Copper, CSST & Plastic 10.2 Pipe Joining Methods: Threading, Flaring, Brazing & Approved Sealants 10.3 Piping Installation: Supports, Hangers, Drip Legs, Dirt Pockets & Valves

11 Chapter 11: Gas Pipe Sizing, Pressure Testing & Purging Procedures

11.1 Gas Pipe & Tubing Sizing Fundamentals (Tables & Pressure Drop) 11.2 Pressure Testing, Leak Testing & the Ontario Test Tag (Clause 6.22) 11.3 Purging Procedures, Safety Protocols & Leak Detection (Clauses 6.23–6.24)

12 Chapter 12: Gas Appliances, Burners & Combustion Air Fundamentals

12.1 Appliance Classifications, Categories (I–IV), Approvals & Clearances 12.2 Atmospheric & Power Burners: Operation, Aeration & Flame Adjustment 12.3 Ignition Systems & Flame Safeguards: Standing Pilot, HSI, DSI, Thermocouples & Flame Rods 12.4 Combustion Air & Basic Venting Requirements (Clause 8)

3.1 Pressure Measurement: U-Tube, Inclined & Digital Manometers

Key Takeaways Explain This Topic AI

1 psig 1\text{ psig} 1 psig equals 27.7 in. w.c. 27.7\text{ in. w.c.} 27.7 in. w.c. , 16 oz/in 2 16\text{ oz/in}^2 16 oz/in 2 , or 6.895 kPa 6.895\text{ kPa} 6.895 kPa ; 1 in. w.c. 1\text{ in. w.c.} 1 in. w.c. equals approximately 249 Pa 249\text{ Pa} 249 Pa .

Standard residential natural gas supply pressure is nominal 7.0 in. w.c. 7.0\text{ in. w.c.} 7.0 in. w.c. (a typical rating-plate inlet range is 5.0 to 10.5 in. w.c. 5.0\text{ to }10.5\text{ in. w.c.} 5.0 to 10.5 in. w.c. ) with manifold pressure commonly regulated to 3.5 in. w.c. 3.5\text{ in. w.c.} 3.5 in. w.c. .

Residential propane delivers supply pressure of 11.0 to 14.0 in. w.c. 11.0\text{ to }14.0\text{ in. w.c.} 11.0 to 14.0 in. w.c. with manifold pressure regulated to 10.0 to 11.0 in. w.c. 10.0\text{ to }11.0\text{ in. w.c.} 10.0 to 11.0 in. w.c. .

When reading a vertical U-tube manometer with a center-zero scale, technicians must add the fluid drop in the pressurized leg to the fluid rise in the atmospheric leg.

Inclined manometers magnify minute pressure changes using a shallow slope, allowing precise draft measurements from 0.01 to 0.5 in. w.c. 0.01\text{ to }0.5\text{ in. w.c.} 0.01 to 0.5 in. w.c. ( 2.5 to 125 Pa 2.5\text{ to }125\text{ Pa} 2.5 to 125 Pa ).

Last updated: October 2026

Pressure Measurement: Principles, Instruments & Diagnostics

In fuel gas distribution and appliance servicing, accurate pressure measurement is essential for combustion safety, burner stability, and code compliance. Gas appliances operate within tight aerodynamic and fuel-to-air limits. An error of just a few inches of water column can cause soot accumulation, deadly carbon monoxide generation, delayed ignition, or heat exchanger failure. Ontario Gas Technician 3 (G3) certificate holders must master pressure units, hydrostatic and electronic manometers, and the distinction between static and operating pressures under the CSA B149.1 Natural Gas and Propane Installation Code.

Pressure Units and Field Conversions

Gas technicians encounter both Imperial and SI metric pressure units on rating plates, codes, and diagnostic instruments:

Pounds per Square Inch Gauge (psig): Measures pressure relative to atmospheric ( 14.7 psia 14.7\text{ psia} 14.7 psia ). Used for propane storage and piping pressure tests.

Inches of Water Column (in. w.c.): Primary unit for low-pressure systems, representing vertical water column displacement.

Ounces per Square Inch (oz/in²): Used in utility distribution and commercial gas meters.

Pascals (Pa) and Kilopascals (kPa): Metric standards in Canadian codes and modern rating plates.

The standard reference column is distilled water at 60 ∘ F 60^\circ\text{F} 6 0 ∘ F ( 15.6 ∘ C 15.6^\circ\text{C} 15. 6 ∘ C ). Key conversion factors include: 1 psig = 27.7 in. w.c. ≈ 16 oz/in 2 ≈ 6.895 kPa 1\text{ psig} = 27.7\text{ in. w.c.} \approx 16\text{ oz/in}^2 \approx 6.895\text{ kPa} 1 psig = 27.7 in. w.c. ≈ 16 oz/in 2 ≈ 6.895 kPa 1 in. w.c. ≈ 249 Pa = 0.249 kPa ≈ 0.578 oz/in 2 1\text{ in. w.c.} \approx 249\text{ Pa} = 0.249\text{ kPa} \approx 0.578\text{ oz/in}^2 1 in. w.c. ≈ 249 Pa = 0.249 kPa ≈ 0.578 oz/in 2 1 oz/in 2 ≈ 1.73 in. w.c. 1\text{ oz/in}^2 \approx 1.73\text{ in. w.c.} 1 oz/in 2 ≈ 1.73 in. w.c.

Pressure Unit Symbol Equivalent in in. w.c. Typical Gas Application

Inches of Water Column in. w.c. \text{in. w.c.} in. w.c. 1.0 in. w.c. 1.0\text{ in. w.c.} 1.0 in. w.c. Appliance supply, manifold pressure, draft

Ounces per Square Inch oz/in 2 \text{oz/in}^2 oz/in 2 1.73 in. w.c. 1.73\text{ in. w.c.} 1.73 in. w.c. Utility gas supply, commercial metering

Pounds per Square Inch psig \text{psig} psig 27.7 in. w.c. 27.7\text{ in. w.c.} 27.7 in. w.c. 2-psig hybrid systems, piping pressure tests

Pascal / Kilopascal Pa \text{Pa} Pa / kPa \text{kPa} kPa 1 in. w.c. = 249 Pa 1\text{ in. w.c.} = 249\text{ Pa} 1 in. w.c. = 249 Pa Venting draft, metric rating plates

Static vs. Dynamic Supply and Manifold Pressures

Gas technicians evaluate pressures at two locations: the combination valve inlet (supply) and outlet (manifold), tested under two conditions:

Static Supply Pressure: Measured when all appliance burners are off. It reveals regulator lockup pressure—the point where the upstream regulator shuts off against flow. Compare lockup with the regulator manufacturer's specification; lockup well above the set point points to a worn or dirty regulator seat.

Dynamic / Operating Supply Pressure: Measured while the appliance fires at full rate alongside any co-piped equipment. Frictional resistance drops pressure below static levels; piping is sized so the drop stays within CSA B149.1 Table 6.1 ( 0.5 in. w.c. 0.5\text{ in. w.c.} 0.5 in. w.c. where supply is below 7 in. w.c. 7\text{ in. w.c.} 7 in. w.c. ; 1 in. w.c. 1\text{ in. w.c.} 1 in. w.c. for 7 to 14 in. w.c. 7\text{ to }14\text{ in. w.c.} 7 to 14 in. w.c. supply).

Fuel Gas Type Residential Supply (Inlet) Manifold Pressure Supply Operating Range

Natural Gas (NG) 7.0 in. w.c. 7.0\text{ in. w.c.} 7.0 in. w.c. ( 1.75 kPa 1.75\text{ kPa} 1.75 kPa ) 3.5 in. w.c. 3.5\text{ in. w.c.} 3.5 in. w.c. ( 0.87 kPa 0.87\text{ kPa} 0.87 kPa ) Typically 5.0 to 10.5 in. w.c. 5.0\text{ to }10.5\text{ in. w.c.} 5.0 to 10.5 in. w.c. per rating plate (Max 14.0 in. w.c. 14.0\text{ in. w.c.} 14.0 in. w.c. )

Propane (LP) 11.0 to 14.0 in. w.c. 11.0\text{ to }14.0\text{ in. w.c.} 11.0 to 14.0 in. w.c. ( 2.74 to 3.49 kPa 2.74\text{ to }3.49\text{ kPa} 2.74 to 3.49 kPa ) 10.0 to 11.0 in. w.c. 10.0\text{ to }11.0\text{ in. w.c.} 10.0 to 11.0 in. w.c. ( 2.49 to 2.74 kPa 2.49\text{ to }2.74\text{ kPa} 2.49 to 2.74 kPa ) 11.0 to 14.0 in. w.c. 11.0\text{ to }14.0\text{ in. w.c.} 11.0 to 14.0 in. w.c. (Max 14.0 in. w.c. 14.0\text{ in. w.c.} 14.0 in. w.c. )

Important

Always verify pressures against the appliance rating plate. Two-stage and modulating furnaces operate with multi-stage manifold pressures (such as 1.5 in. w.c. 1.5\text{ in. w.c.} 1.5 in. w.c. on low fire and 3.5 in. w.c. 3.5\text{ in. w.c.} 3.5 in. w.c. on high fire). Never set gas pressures by visual flame appearance alone.

U-Tube Manometers: Mechanics and Dual-Column Reading

The U-tube manometer is a hydrostatic instrument operating on fluid balance without electronic calibration or springs. It features a transparent U-shaped tube filled halfway with water or dyed oil, mounted beside a calibrated scale.

Dual-Column Displacement Rule

When both columns are open to atmosphere, fluid rests evenly at the center zero ( 0.0 0.0 0.0 ) mark. Connecting one column to a gas tap pushes fluid down in the pressurized leg while forcing the open leg upward by the exact same distance: h total = h drop + h rise h_{\text{total}} = h_{\text{drop}} + h_{\text{rise}} h total ​ = h drop ​ + h rise ​

Warning

Apprentice technicians often read only one column and record that single displacement as total system pressure. If fluid drops 1.75 inches 1.75\text{ inches} 1.75 inches below zero on the pressurized side, it rises 1.75 inches 1.75\text{ inches} 1.75 inches above zero on the open side. The actual pressure is 1.75 + 1.75 = 3.5 in. w.c. 1.75 + 1.75 = 3.5\text{ in. w.c.} 1.75 + 1.75 = 3.5 in. w.c. . Reading one column alone halves the actual value, risking extreme overfiring.

Many manometers feature a sliding scale: slide the zero mark to align with the lower fluid meniscus, allowing total pressure to be read directly from the upper meniscus without addition.

Water has a specific gravity ( S G SG SG ) of 1.0 1.0 1.0 , whereas red gauge oil has an S G SG SG of approximately 0.826 0.826 0.826 . Because lighter fluids travel further under identical pressures, oil must only be used with scales pre-calibrated for that fluid. Never add automotive antifreeze or windshield washer fluid to a water manometer without recalibrating.

Inclined Manometers: Measuring Minute Draft Pressures

Vertical manometers cannot reliably resolve minute chimney drafts ( 0.01 to 0.5 in. w.c. 0.01\text{ to }0.5\text{ in. w.c.} 0.01 to 0.5 in. w.c. ). For Category I atmospheric appliances, technicians employ an inclined manometer (draft gauge).

By angling the tube along a shallow incline (such as a 10 : 1 10:1 10 : 1 slope), fluid travels 1.0 inch 1.0\text{ inch} 1.0 inch along the angled scale for every 0.1 inch 0.1\text{ inch} 0.1 inch of vertical rise. This geometric magnification permits precise readings down to 0.01 in. w.c. 0.01\text{ in. w.c.} 0.01 in. w.c. ( 2.5 Pa 2.5\text{ Pa} 2.5 Pa ).

Operating protocols require:

Precision Leveling: Align the built-in spirit level before zeroing.

Specific Fluid: Use only manufacturer-certified red gauge oil ( S G = 0.826 SG = 0.826 SG = 0.826 ).

Draft Checks: Category I appliances must establish continuous negative draft (typically − 0.02 to − 0.04 in. w.c. -0.02\text{ to }-0.04\text{ in. w.c.} − 0.02 to − 0.04 in. w.c. ) within five minutes of ignition to avoid combustion product spillage.

Digital Differential Manometers & Field Diagnostics

Modern digital manometers utilize solid-state piezoresistive sensors. Gas pressure flexes a silicon diaphragm, altering electrical resistance in proportion to applied pressure, which onboard electronics convert into instant numerical readouts.

Differential Port Diagnostics

Digital manometers feature dual ports: positive ( + + + ) and negative/reference ( − - − ). This enables differential measurements ( Δ P = P high − P low \Delta P = P_{\text{high}} - P_{\text{low}} Δ P = P high ​ − P low ​ ):

Furnace Draft Pressure Switches: Condensing Category IV furnaces pull flue gas via an induced draft fan. A normally open pressure switch monitors negative static draft. If a switch rated for − 0.65 in. w.c. -0.65\text{ in. w.c.} − 0.65 in. w.c. fails to close when the manometer reads − 0.75 in. w.c. -0.75\text{ in. w.c.} − 0.75 in. w.c. , the switch or sensing tubing is defective.

Air Filter and Coil Resistance: Measuring static differential across an air filter or indoor coil identifies blockages before airflow limits trip; compare the reading with the filter or coil manufacturer's rated pressure drop.

External Static Pressure (ESP): Supply plenum pressure minus return plenum negative pressure confirms total system airflow meets manufacturer CFM charts.

Note

Always zero digital manometers in clean ambient air before attaching sensing lines. Temperature changes between a service vehicle and an equipment room cause sensor drift. Never connect high-pressure gas lines to a low-range draft manometer ( 0 to 2 in. w.c. 0\text{ to }2\text{ in. w.c.} 0 to 2 in. w.c. ), as excessive pressure will permanently rupture the internal sensing diaphragm.

Loading diagram... Gas Appliance Pressure Diagnostic Sequence