Study guide
5.2 Disinfection Kinetics & CT Calculations
California Water/Wastewater Operator Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: California Water Regulatory Framework & Certification Ladders
1.1 State Water Board & Regional Boards Structure 1.2 Drinking Water Certification: T1-T5 & D1-D5 Requirements 1.3 Wastewater Certification: Grades I-V & OIT Requirements 1.4 Safe Drinking Water Standards, MCLs & Emerging Contaminants 1.5 California Waterworks Standards (Title 22, Chapter 16) 1.6 Public Water System Types, Permits & the Sanitary Survey
2 Chapter 2: California Water Rights, Title 22 & Environmental Policy
2.1 California Title 22 Recycled Water Standards 2.2 California Environmental Quality Act (CEQA) & Proposition 218 2.3 Water Rights & California Water Resources
3 Chapter 3: Drinking Water Source Quality & Coagulation/Flocculation
3.1 Source Water Quality & Watershed Management 3.2 Coagulation Chemistry & Flash Mixing 3.3 Flocculation & Jar Testing 3.4 Wells, Aquifers & Groundwater Hydraulics 3.5 Raw Water Storage, Clearwells & Reservoir Management
4 Chapter 4: Clarification & Granular Media Filtration
4.1 Sedimentation & Advanced Clarification 4.2 Granular Media Filtration Mechanics & Media Types 4.3 Filter Operation, Backwash Cycles & SWTR Compliance
5 Chapter 5: Disinfection, Oxidation & Advanced Water Treatment
5.1 Chlorination Chemistry & Breakpoint Curves 5.2 Disinfection Kinetics & CT Calculations 5.3 Alternative Disinfection: Ozone, UV & Chlorine Dioxide 5.4 Advanced Treatment: Membranes, AOP & PFAS Adsorption 5.5 Chloramination & Nitrification Control 5.6 Iron & Manganese Removal 5.7 Fluoridation Practice & Compliance 5.8 Corrosion Control Treatment & Water Stability 5.9 Taste & Odor Control and Algal Toxin Management
6 Chapter 6: Wastewater Preliminary & Primary Treatment
6.1 Preliminary Treatment: Screening & Grit Removal 6.2 Primary Clarification Operations 6.3 Primary Sludge Characteristics & Pumping 6.4 Stabilization Ponds, Lagoons & Small-Plant Processes
7 Chapter 7: Secondary Biological Treatment & Activated Sludge
7.1 Activated Sludge Process Fundamentals 7.2 Process Control Parameters: F/M, MCRT & SVI 7.3 Activated Sludge Microbiology & Troubleshooting 7.4 Fixed-Film & Hybrid Biological Processes
8 Chapter 8: Biological Nutrient Removal, Water Reuse & Solids Handling
8.1 Biological Nitrogen Removal: Nitrification & Denitrification 8.2 Biological Phosphorus Removal (EBPR) & Chemical Precipitation 8.3 Anaerobic & Aerobic Digestion 8.4 Sludge Thickening, Dewatering & Biosolids Disposal 8.5 Wastewater Disinfection: Chlorination, Dechlorination & UV
9 Chapter 9: Distribution Systems, Collection Networks & Hydraulics
9.1 Hydraulics, Pressure & Flow Dynamics 9.2 Centrifugal Pumps, Motors & VFDs 9.3 Distribution Network Infrastructure & Cross-Connection Control 9.4 Wastewater Collection Systems, SSMP & FOG Management
10 Chapter 10: Laboratory Analytics, Safety & Water Math
10.1 Water & Wastewater Laboratory Methods 10.2 Laboratory Quality Assurance & Regulatory Reporting 10.3 Chemical Safety, Hazardous Gases & Confined Space 10.4 Essential Water & Wastewater Math for Operators
11 Chapter 11: Federal & California Drinking Water Rules
11.1 The Revised Total Coliform Rule & Assessments 11.2 The Lead and Copper Rule and Service Line Replacement 11.3 Surface Water Treatment Rules & Log Removal Credit 11.4 Stage 1 & Stage 2 Disinfection Byproduct Rules 11.5 Secondary MCLs, Notification Levels & Response Levels 11.6 Public Notification, Consumer Confidence Reports & Recordkeeping
12 Chapter 12: Distribution System Design, Demand & Hydraulics
12.1 System Layout, Pressure Zones & Distribution Maps 12.2 Water Demand, Peaking Factors & Fire Flow 12.3 Distribution Storage: Types, Sizing & Turnover 12.4 Head Loss, C-Factor & Distribution Hydraulic Calculations 12.5 Water Hammer, Surge Control & Air Management
13 Chapter 13: Distribution Equipment Operation, Maintenance & Inspection
13.1 Valves: Types, Operation & Exercising Programs 13.2 Fire Hydrants: Types, Testing & Maintenance 13.3 Water Meters: Types, Accuracy & Meter Management 13.4 Instrumentation, In-Line Sensors, Telemetry & SCADA 13.5 Electrical Systems, Motors & Standby Generators 13.6 External Corrosion, Cathodic Protection & Asset Inspection
14 Chapter 14: Water Mains, Piping & Field Construction
14.1 Pipe Materials & Pipe Selection 14.2 Joints, Fittings, Thrust Restraint & Bedding 14.3 Main Installation, Tapping & Service Line Installation 14.4 Leak Detection, Water Loss Auditing & Main Repair 14.5 Main Cleaning & Maintenance: Flushing, Pigging & Lining 14.6 Excavation, Trench Safety & Utility Locating
15 Chapter 15: Disinfecting Distribution Facilities & Maintaining Water Quality
15.1 Water Main Disinfection (AWWA C651) 15.2 Disinfecting Storage Reservoirs (C652) & Wells (C654) 15.3 Maintaining Distribution Water Quality: Residual, Biofilm & Discolored Water 15.4 Cross-Connection Control Program Administration & Device Testing
16 Chapter 16: Plant Equipment, Chemical Feed & Maintenance
16.1 Chemical Feed Systems: Metering Pumps, Dry Feeders & Calibration 16.2 Gas Chlorination Equipment & Hypochlorite Systems 16.3 Blowers, Compressors & Aeration Equipment 16.4 Flow Measurement Devices: Meters, Weirs & Flumes 16.5 Preventive Maintenance, CMMS & Asset Management
17 Chapter 17: Utility Management, Administration & Emergency Response
17.1 Planning, Organizing, Directing & Controlling a Utility Work Group 17.2 Budgets, Water Rates & Financial Management 17.3 Operator Training, Staffing & Safety Program Development 17.4 Energy Management & Optimization 17.5 Emergency Response Planning, Risk & Resilience & Security 17.6 Water Conservation Planning & Drought Response
18 Chapter 18: Applied Operator Mathematics Workshop
18.1 The Exam Conversion Sheet, Units & Dimensional Analysis 18.2 Distribution & Hydraulic Math Workshop 18.3 Treatment & Wastewater Process Math Workshop
5.2 Disinfection Kinetics & CT Calculations
Key Takeaways Explain This Topic AI
Disinfection kinetics are governed by the Chick-Watson Law (ln(N/N₀) = -k·C·t), demonstrating that microbial inactivation is a direct product of disinfectant concentration (C) and contact time (t).
Under the Surface Water Treatment Rule (SWTR), disinfection compliance is quantified using the CT concept (CT = C × T₁₀), where C is the residual disinfectant concentration in mg/L and T₁₀ is the effective contact time in minutes.
T₁₀ represents the time required for 10% of the water volume to pass through the contact basin (representing 90% detention), determined via tracer studies and multiplied by a Baffling Factor (BF) ranging from 0.1 (unbaffled) to 1.0 (ideal plug flow).
The SWTR mandates minimum overall treatment removals of 3-log (99.9%) for Giardia lamblia cysts, 4-log (99.99%) for enteric viruses, and 2-log (99%) for Cryptosporidium oocysts.
Free chlorine CT requirements increase dramatically under cold water temperatures and elevated pH conditions, requiring operators to calculate real-time Inactivation Ratios (Ratio = CT_actual / CT_required ≥ 1.0) across all contact segments.
Last updated: August 2026
Disinfection Kinetics & CT Calculations
The fundamental goal of drinking water disinfection is to ensure that treated water delivered to consumers is microbiologically safe. To guarantee adequate inactivation of waterborne pathogens—specifically protozoan cysts ( Giardia lamblia ), protozoan oocysts ( Cryptosporidium parvum ), and enteric viruses—the US Environmental Protection Agency (EPA) and the California State Water Resources Control Board Division of Drinking Water (DDW) enforce the Surface Water Treatment Rule (SWTR) and its subsequent enhancements (IESWTR, LT1ESWTR, LT2ESWTR).
The regulatory compliance framework is built upon the mathematical principles of disinfection kinetics and the empirical C T CT CT concept .
Disinfection Kinetics & The Chick-Watson Law
Chemical disinfection does not occur instantaneously; it is a time-dependent biochemical reaction in which chemical disinfectants diffuse across cell membranes and oxidize vital cellular components. In 1908, Harriet Chick proposed that microbial destruction follows first-order chemical reaction kinetics, analogous to radioactive decay: d N d t = − k N \frac{dN}{dt} = -k N d t d N = − k N
Where N N N is the number of surviving viable microorganisms at time t t t , and k k k is the inactivation rate constant. In 1908, H.E. Watson expanded Chick's relationship to incorporate the concentration of the chemical disinfectant ( C C C ): d N d t = − k C n N \frac{dN}{dt} = -k C^n N d t d N = − k C n N
Assuming the empirical coefficient of dilution n ≈ 1 n \approx 1 n ≈ 1 (the standard assumption in water engineering), integrating this differential equation from time 0 0 0 to t t t yields the classical Chick-Watson Law : ln ( N N 0 ) = − k ⋅ C ⋅ t \ln\left(\frac{N}{N_0}\right) = -k \cdot C \cdot t ln ( N 0 N ) = − k ⋅ C ⋅ t log 10 ( N N 0 ) = − k 2.303 ⋅ C ⋅ t \log_{10}\left(\frac{N}{N_0}\right) = -\frac{k}{2.303} \cdot C \cdot t lo g 10 ( N 0 N ) = − 2.303 k ⋅ C ⋅ t
Where:
N 0 N_0 N 0 = Initial microbial population (influent concentration).
N N N = Surviving microbial population at contact time t t t .
C C C = Disinfectant residual concentration (in mg/L \text{mg/L} mg/L ).
t t t = Contact time (in minutes).
k k k = Inactivation rate constant (dependent on specific pathogen, disinfectant type, temperature, and pH).
Defining Log Reduction Values (LRV)
In regulatory compliance, pathogen reduction is quantified in logarithms (Log Reduction Values or LRV) rather than percentages: Log Inactivation = log 10 ( N 0 N ) = − log 10 ( 1 − % Inactivation 100 ) \text{Log Inactivation} = \log_{10}\left(\frac{N_0}{N}\right) = -\log_{10}\left(1 - \frac{\% \text{ Inactivation}}{100}\right) Log Inactivation = lo g 10 ( N N 0 ) = − lo g 10 ( 1 − 100 % Inactivation ) ┌──────────────────────────────────────────────────────────────────────────┐
- │ Pathogen Log Inactivation vs. Percent Removal │
- ├──────────────┬────────────────────────────┬──────────────────────────────┤
- │ Log Credit │ Fractional Survival (N/N₀) │ Percent Inactivation / Kill │
- ├──────────────┼────────────────────────────┼──────────────────────────────┤
- │ 1.0-log │ 1 / 10 = 0.10 │ 90.0% │
- │ 2.0-log │ 1 / 100 = 0.01 │ 99.0% │
- │ 3.0-log │ 1 / 1,000 = 0.001 │ 99.9% │
- │ 4.0-log │ 1 / 10,000 = 0.0001 │ 99.99% │
- │ 5.0-log │ 1 / 100,000 = 0.00001 │ 99.999% │
- │ 6.0-log │ 1 / 1,000,000 = 0.000001 │ 99.9999% │
- └──────────────┴────────────────────────────┴──────────────────────────────┘
- The Concentration × Time ( C T CT CT ) Concept
The Chick-Watson relationship proves that pathogen inactivation is directly proportional to the product of disinfectant concentration ( C C C ) and contact time ( t t t ). In water treatment, this parameter is universally known as C T CT CT : CT = C × T 10 \text{CT} = C \times T_{10} CT = C × T 10
Where:
C C C = Measured residual disinfectant concentration (in mg/L \text{mg/L} mg/L ) at or before the compliance sampling point.
T 10 T_{10} T 10 = The effective contact time (in minutes) corresponding to the time required for 10% of the water volume to pass through the basin (meaning 90% of the water is retained in the basin for at least T 10 T_{10} T 10 ). The SWTR explicitly forbids using the theoretical mean hydraulic detention time ( H D T HDT HD T ) because non-ideal hydraulic short-circuiting would leave a portion of the water under-disinfected.
Hydraulic Contact Time ( T 10 T_{10} T 10 ) & Baffling Factors
The theoretical Hydraulic Detention Time ( H D T HDT HD T or θ \theta θ ) of a contact chamber is calculated as: H D T = Basin Volume ( V ) Peak Flow Rate ( Q ) HDT = \frac{\text{Basin Volume } (V)}{\text{Peak Flow Rate } (Q)} HD T = Peak Flow Rate ( Q ) Basin Volume ( V )
Because real-world basins exhibit hydraulic inefficiencies such as dead zones, recirculation eddies, and short-circuiting, T 10 T_{10} T 10 is significantly shorter than H D T HDT HD T . The relationship between T 10 T_{10} T 10 and H D T HDT HD T is defined by the Baffling Factor ( B F BF BF ) : T 10 = H D T × B F = ( V Q ) × B F T_{10} = HDT \times BF = \left(\frac{V}{Q}\right) \times BF T 10 = HD T × BF = ( Q V ) × BF ┌──────────────────────────────────────────────────────────────────────────┐
- │ US EPA & Title 22 Baffling Factors │
- ├──────────────┬────────┬──────────────────────────────────────────────────┤
- │ Baffling Tier│ BF │ Physical Configuration & Description │
- ├──────────────┼────────┼──────────────────────────────────────────────────┤
- │ Unbaffled │ 0.10 │ Single inlet/outlet, open rectangular or circular│
- │ (None) │ │ storage tank, no internal walls, severe bypass. │
- ├──────────────┼────────┼──────────────────────────────────────────────────┤
- │ Poor │ 0.30 │ Single baffle wall, unbaffled inlet/outlet weirs,│
- │ │ │ significant stagnant/dead storage volume. │
- ├──────────────┼────────┼──────────────────────────────────────────────────┤
- │ Average │ 0.50 │ Multiple intra-basin baffles or cross-baffling, │
- │ (Moderate) │ │ submerged or perforated inlet/outlet structures. │
- ├──────────────┼────────┼──────────────────────────────────────────────────┤
- │ Superior │ 0.70 │ Serpentine multi-pass channels with high length- │
- │ │ │ to-width ratio (L:W > 40:1), perforated diffusers│
- ├──────────────┼────────┼──────────────────────────────────────────────────┤
- │ Perfect │ 1.00 │ Ideal plug-flow reactor; long pressurized │
- │ (Plug Flow) │ │ transmission pipelines with no dead space. │
- └──────────────┴────────┴──────────────────────────────────────────────────┘
- Determination of T 10 T_{10} T 10 via Physical Tracer Studies
To establish regulatory T 10 T_{10} T 10 values, utilities perform empirical tracer studies under peak design flow conditions using approved tracer chemicals:
Tracer Chemicals: Fluoride ion ( F − F^- F − ), Sodium Chloride ( N a C l NaCl N a Cl via electrical conductivity), or Rhodamine WT fluorescent dye.
Test Methods: Step-dose injection (continuous steady chemical addition) or pulse-dose injection (slug injection).
Calculation: The tracer concentration at the basin effluent is plotted against elapsed time. T 10 T_{10} T 10 is the exact time at which the normalized effluent concentration ( C / C 0 C/C_0 C / C 0 ) reaches 10% (0.10) of the steady-state feed concentration.
Surface Water Treatment Rule (SWTR) Mandates
Under Title 22 CCR and the federal SWTR, all public water systems utilizing surface water or Groundwater Under the Direct Influence of Surface Water (GWUDI) must achieve mandatory minimum cumulative log reductions:
Giardia lamblia: 3.0-log (99.9%) reduction/inactivation.
Enteric Viruses: 4.0-log (99.99%) reduction/inactivation.
Cryptosporidium oocysts: 2.0-log (99.0%) removal (mandated under LT2ESWTR for Bin 1 sources, with higher log removal required for Bin 2–4 sources based on raw water monitoring).
Filtration Credit vs. Disinfection Credit Allocation
In a conventional water treatment plant, pathogen removal is achieved through a multi-barrier combination of physical filtration and chemical disinfection:
Pathogen Target Total SWTR Mandate Conventional Filtration Removal Credit Required Chemical Disinfection Credit Notes & Restrictions
Giardia lamblia 3.0-log (99.9%) 2.5-log (99.7%) 0.5-log (68.4%) Disinfection must deliver remaining 0.5-log CT
Enteric Viruses 4.0-log (99.99%) 2.0-log (99.0%) 2.0-log (99.0%) Disinfection must deliver remaining 2.0-log CT
Cryptosporidium 2.0-log (99.0%) 2.0-log (99.0%) 0.0-log* *Free chlorine receives 0.0-log credit (UV or ozone required for chemical inactivation)
For Direct Filtration plants (no sedimentation basin), physical filtration receives only 2.0-log Giardia credit and 1.0-log virus credit , requiring chemical disinfection to achieve 1.0-log Giardia inactivation and 3.0-log virus inactivation .
SWTR CT Tables: Environmental Dependencies
The EPA publishes standardized lookup tables listing the required C T CT CT values ( C T required CT_{\text{required}} C T required ) to achieve specific log inactivations of Giardia and viruses using free chlorine, chloramines, chlorine dioxide, and ozone.
Key Environmental Factors Governing Free Chlorine CT Requirements:
Water Temperature: Biological inactivation kinetics slow down dramatically in cold water. Lower water temperatures require substantially higher C T CT CT values. For example, achieving 3-log Giardia inactivation at 0.5°C requires roughly 3 to 4 times higher C T CT CT than at 20°C.
Water pH: As pH increases from 6.0 to 9.0, hypochlorous acid ( H O C l HOCl H OCl ) dissociates into hypochlorite ions ( O C l − OCl^- OC l − ). Because O C l − OCl^- OC l − is a weak germicide, the required C T CT CT increases dramatically at higher pH levels.
Free Chlorine Concentration: At higher free chlorine residual concentrations, hypochlorous acid partially forms dimers, slightly reducing unit germicidal activity; hence, the required C T CT CT increases slightly with increasing residual concentration.
Water Temp (°C) Required CT at pH 6.5 Required CT at pH 7.0 Required CT at pH 7.5 Required CT at pH 8.0
0.5 °C 162 mg ⋅ min/L 162\text{ mg}\cdot\text{min/L} 162 mg ⋅ min/L 202 mg ⋅ min/L 202\text{ mg}\cdot\text{min/L} 202 mg ⋅ min/L 254 mg ⋅ min/L 254\text{ mg}\cdot\text{min/L} 254 mg ⋅ min/L 320 mg ⋅ min/L 320\text{ mg}\cdot\text{min/L} 320 mg ⋅ min/L
5.0 °C 117 mg ⋅ min/L 117\text{ mg}\cdot\text{min/L} 117 mg ⋅ min/L 146 mg ⋅ min/L 146\text{ mg}\cdot\text{min/L} 146 mg ⋅ min/L 183 mg ⋅ min/L 183\text{ mg}\cdot\text{min/L} 183 mg ⋅ min/L 232 mg ⋅ min/L 232\text{ mg}\cdot\text{min/L} 232 mg ⋅ min/L
10.0 °C 88 mg ⋅ min/L 88\text{ mg}\cdot\text{min/L} 88 mg ⋅ min/L 110 mg ⋅ min/L 110\text{ mg}\cdot\text{min/L} 110 mg ⋅ min/L 137 mg ⋅ min/L 137\text{ mg}\cdot\text{min/L} 137 mg ⋅ min/L 174 mg ⋅ min/L 174\text{ mg}\cdot\text{min/L} 174 mg ⋅ min/L
15.0 °C 59 mg ⋅ min/L 59\text{ mg}\cdot\text{min/L} 59 mg ⋅ min/L 73 mg ⋅ min/L 73\text{ mg}\cdot\text{min/L} 73 mg ⋅ min/L 91 mg ⋅ min/L 91\text{ mg}\cdot\text{min/L} 91 mg ⋅ min/L 116 mg ⋅ min/L 116\text{ mg}\cdot\text{min/L} 116 mg ⋅ min/L
20.0 °C 44 mg ⋅ min/L 44\text{ mg}\cdot\text{min/L} 44 mg ⋅ min/L 55 mg ⋅ min/L 55\text{ mg}\cdot\text{min/L} 55 mg ⋅ min/L 69 mg ⋅ min/L 69\text{ mg}\cdot\text{min/L} 69 mg ⋅ min/L 87 mg ⋅ min/L 87\text{ mg}\cdot\text{min/L} 87 mg ⋅ min/L
- CT Compliance Calculations & Multi-Segment Chambers
- Single-Segment Compliance: The Inactivation Ratio
To verify continuous regulatory compliance, operators calculate the Inactivation Ratio (IR) in real time: Inactivation Ratio (IR) = C T actual C T required \text{Inactivation Ratio (IR)} = \frac{CT_{\text{actual}}}{CT_{\text{required}}} Inactivation Ratio (IR) = C T required C T actual Achieved Log Inactivation = Target Log Inactivation × ( C T actual C T required ) \text{Achieved Log Inactivation} = \text{Target Log Inactivation} \times \left(\frac{CT_{\text{actual}}}{CT_{\text{required}}}\right) Achieved Log Inactivation = Target Log Inactivation × ( C T required C T actual )
If IR ≥ 1.0 \text{IR} \ge 1.0 IR ≥ 1.0 , the treatment facility meets regulatory disinfection requirements.
If IR < 1.0 \text{IR} < 1.0 IR < 1.0 , the facility is in violation of the SWTR treatment technique requirement and must immediately increase chlorine dose or reduce plant flow.
Multi-Segment Cumulative Log Credit Calculation
In modern surface water facilities, disinfection occurs sequentially across multiple unit processes (e.g., flocculator effluent, sedimentation basin, clearwell, and treated water transmission main). Compliance is determined by summing the inactivation ratios across all segments: Total Inactivation Ratio = ∑ i = 1 n C T actual , i C T required , i = C T actual , 1 C T required , 1 + C T actual , 2 C T required , 2 + ⋯ + C T actual , n C T required , n \text{Total Inactivation Ratio} = \sum_{i=1}^{n} \frac{CT_{\text{actual}, i}}{CT_{\text{required}, i}} = \frac{CT_{\text{actual}, 1}}{CT_{\text{required}, 1}} + \frac{CT_{\text{actual}, 2}}{CT_{\text{required}, 2}} + \dots + \frac{CT_{\text{actual}, n}}{CT_{\text{required}, n}} Total Inactivation Ratio = i = 1 ∑ n C T required , i C T actual , i = C T required , 1 C T actual , 1 + C T required , 2 C T actual , 2 + ⋯ + C T required , n C T actual , n Total Achieved Log Credit = Target Log Credit × Total Inactivation Ratio \text{Total Achieved Log Credit} = \text{Target Log Credit} \times \text{Total Inactivation Ratio} Total Achieved Log Credit = Target Log Credit × Total Inactivation Ratio
Step-by-Step Operator Math Example
Operational Scenario: A conventional water treatment plant is operating at a peak design flow rate of 8.0 MGD . Disinfection occurs in an on-site clearwell storage basin with a physical operating volume of 1.50 million gallons (MG) . A conservative tracer study determined the clearwell has an Average Baffling Factor ( B F = 0.50 BF = 0.50 BF = 0.50 ) .
Finished water leaving the clearwell has a free chlorine residual of C = 1.40 mg/L C = 1.40\text{ mg/L} C = 1.40 mg/L .
Clearwell operating conditions: water temperature is 10.0 ∘ C 10.0^\circ\text{C} 10. 0 ∘ C and pH is 7.50 7.50 7.50 .
The plant must achieve 0.50-log Giardia disinfection credit.
According to SWTR CT tables, the required C T CT CT for 3.0-log Giardia inactivation at 10.0 ∘ C 10.0^\circ\text{C} 10. 0 ∘ C , pH 7.50, and C = 1.40 mg/L C = 1.40\text{ mg/L} C = 1.40 mg/L is 143 mg ⋅ min/L 143\text{ mg}\cdot\text{min/L} 143 mg ⋅ min/L .
Question: Does the facility satisfy SWTR CT compliance, and what is the actual achieved Giardia log inactivation?
Step 1: Calculate Theoretical Hydraulic Detention Time ( H D T HDT HD T )
First, convert daily flow into gallons per minute (gpm): Q = 8 , 000 , 000 gal/day 1 , 440 min/day = 5 , 555.56 gpm Q = \frac{8,000,000\text{ gal/day}}{1,440\text{ min/day}} = 5,555.56\text{ gpm} Q = 1 , 440 min/day 8 , 000 , 000 gal/day = 5 , 555.56 gpm H D T = V Q = 1 , 500 , 000 gal 5 , 555.56 gpm = 270.0 minutes HDT = \frac{V}{Q} = \frac{1,500,000\text{ gal}}{5,555.56\text{ gpm}} = 270.0\text{ minutes} HD T = Q V = 5 , 555.56 gpm 1 , 500 , 000 gal = 270.0 minutes
Step 2: Calculate Effective Contact Time ( T 10 T_{10} T 10 ) T 10 = H D T × B F = 270.0 min × 0.50 = 135.0 minutes T_{10} = HDT \times BF = 270.0\text{ min} \times 0.50 = 135.0\text{ minutes} T 10 = HD T × BF = 270.0 min × 0.50 = 135.0 minutes
Step 3: Calculate Actual Provided CT ( C T actual CT_{\text{actual}} C T actual ) C T actual = C × T 10 = 1.40 mg/L × 135.0 min = 189.0 mg ⋅ min/L CT_{\text{actual}} = C \times T_{10} = 1.40\text{ mg/L} \times 135.0\text{ min} = 189.0\text{ mg}\cdot\text{min/L} C T actual = C × T 10 = 1.40 mg/L × 135.0 min = 189.0 mg ⋅ min/L
Step 4: Calculate Required CT for 0.5-Log Inactivation ( C T required, 0.5-log CT_{\text{required, 0.5-log}} C T required, 0.5-log )
Since CT requirements scale linearly with log credit: C T required, 0.5-log = 0.5 -log 3.0 -log × C T required, 3.0-log = 1 6 × 143 mg ⋅ min/L = 23.83 mg ⋅ min/L CT_{\text{required, 0.5-log}} = \frac{0.5\text{-log}}{3.0\text{-log}} \times CT_{\text{required, 3.0-log}} = \frac{1}{6} \times 143\text{ mg}\cdot\text{min/L} = 23.83\text{ mg}\cdot\text{min/L} C T required, 0.5-log = 3.0 -log 0.5 -log × C T required, 3.0-log = 6 1 × 143 mg ⋅ min/L = 23.83 mg ⋅ min/L
Step 5: Calculate Inactivation Ratio (IR) and Achieved Log Credit IR = C T actual C T required, 0.5-log = 189.0 mg ⋅ min/L 23.83 mg ⋅ min/L = 7.93 \text{IR} = \frac{CT_{\text{actual}}}{CT_{\text{required, 0.5-log}}} = \frac{189.0\text{ mg}\cdot\text{min/L}}{23.83\text{ mg}\cdot\text{min/L}} = 7.93 IR = C T required, 0.5-log C T actual = 23.83 mg ⋅ min/L 189.0 mg ⋅ min/L = 7.93 Achieved Log Credit = 0.50 -log × 7.93 = 3.97 -log Giardia inactivation \text{Achieved Log Credit} = 0.50\text{-log} \times 7.93 = 3.97\text{-log Giardia inactivation} Achieved Log Credit = 0.50 -log × 7.93 = 3.97 -log Giardia inactivation
Conclusion: The Inactivation Ratio of 7.93 is well above the minimum threshold of 1.0 , confirming full regulatory compliance.