11.1 The Revised Total Coliform Rule & Assessments

California Water/Wastewater Operator Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: California Water Regulatory Framework & Certification Ladders

1.1 State Water Board & Regional Boards Structure 1.2 Drinking Water Certification: T1-T5 & D1-D5 Requirements 1.3 Wastewater Certification: Grades I-V & OIT Requirements 1.4 Safe Drinking Water Standards, MCLs & Emerging Contaminants 1.5 California Waterworks Standards (Title 22, Chapter 16) 1.6 Public Water System Types, Permits & the Sanitary Survey

2 Chapter 2: California Water Rights, Title 22 & Environmental Policy

2.1 California Title 22 Recycled Water Standards 2.2 California Environmental Quality Act (CEQA) & Proposition 218 2.3 Water Rights & California Water Resources

3 Chapter 3: Drinking Water Source Quality & Coagulation/Flocculation

3.1 Source Water Quality & Watershed Management 3.2 Coagulation Chemistry & Flash Mixing 3.3 Flocculation & Jar Testing 3.4 Wells, Aquifers & Groundwater Hydraulics 3.5 Raw Water Storage, Clearwells & Reservoir Management

4 Chapter 4: Clarification & Granular Media Filtration

4.1 Sedimentation & Advanced Clarification 4.2 Granular Media Filtration Mechanics & Media Types 4.3 Filter Operation, Backwash Cycles & SWTR Compliance

5 Chapter 5: Disinfection, Oxidation & Advanced Water Treatment

5.1 Chlorination Chemistry & Breakpoint Curves 5.2 Disinfection Kinetics & CT Calculations 5.3 Alternative Disinfection: Ozone, UV & Chlorine Dioxide 5.4 Advanced Treatment: Membranes, AOP & PFAS Adsorption 5.5 Chloramination & Nitrification Control 5.6 Iron & Manganese Removal 5.7 Fluoridation Practice & Compliance 5.8 Corrosion Control Treatment & Water Stability 5.9 Taste & Odor Control and Algal Toxin Management

6 Chapter 6: Wastewater Preliminary & Primary Treatment

6.1 Preliminary Treatment: Screening & Grit Removal 6.2 Primary Clarification Operations 6.3 Primary Sludge Characteristics & Pumping 6.4 Stabilization Ponds, Lagoons & Small-Plant Processes

7 Chapter 7: Secondary Biological Treatment & Activated Sludge

7.1 Activated Sludge Process Fundamentals 7.2 Process Control Parameters: F/M, MCRT & SVI 7.3 Activated Sludge Microbiology & Troubleshooting 7.4 Fixed-Film & Hybrid Biological Processes

8 Chapter 8: Biological Nutrient Removal, Water Reuse & Solids Handling

8.1 Biological Nitrogen Removal: Nitrification & Denitrification 8.2 Biological Phosphorus Removal (EBPR) & Chemical Precipitation 8.3 Anaerobic & Aerobic Digestion 8.4 Sludge Thickening, Dewatering & Biosolids Disposal 8.5 Wastewater Disinfection: Chlorination, Dechlorination & UV

9 Chapter 9: Distribution Systems, Collection Networks & Hydraulics

9.1 Hydraulics, Pressure & Flow Dynamics 9.2 Centrifugal Pumps, Motors & VFDs 9.3 Distribution Network Infrastructure & Cross-Connection Control 9.4 Wastewater Collection Systems, SSMP & FOG Management

10 Chapter 10: Laboratory Analytics, Safety & Water Math

10.1 Water & Wastewater Laboratory Methods 10.2 Laboratory Quality Assurance & Regulatory Reporting 10.3 Chemical Safety, Hazardous Gases & Confined Space 10.4 Essential Water & Wastewater Math for Operators

11 Chapter 11: Federal & California Drinking Water Rules

11.1 The Revised Total Coliform Rule & Assessments 11.2 The Lead and Copper Rule and Service Line Replacement 11.3 Surface Water Treatment Rules & Log Removal Credit 11.4 Stage 1 & Stage 2 Disinfection Byproduct Rules 11.5 Secondary MCLs, Notification Levels & Response Levels 11.6 Public Notification, Consumer Confidence Reports & Recordkeeping

12 Chapter 12: Distribution System Design, Demand & Hydraulics

12.1 System Layout, Pressure Zones & Distribution Maps 12.2 Water Demand, Peaking Factors & Fire Flow 12.3 Distribution Storage: Types, Sizing & Turnover 12.4 Head Loss, C-Factor & Distribution Hydraulic Calculations 12.5 Water Hammer, Surge Control & Air Management

13 Chapter 13: Distribution Equipment Operation, Maintenance & Inspection

13.1 Valves: Types, Operation & Exercising Programs 13.2 Fire Hydrants: Types, Testing & Maintenance 13.3 Water Meters: Types, Accuracy & Meter Management 13.4 Instrumentation, In-Line Sensors, Telemetry & SCADA 13.5 Electrical Systems, Motors & Standby Generators 13.6 External Corrosion, Cathodic Protection & Asset Inspection

14 Chapter 14: Water Mains, Piping & Field Construction

14.1 Pipe Materials & Pipe Selection 14.2 Joints, Fittings, Thrust Restraint & Bedding 14.3 Main Installation, Tapping & Service Line Installation 14.4 Leak Detection, Water Loss Auditing & Main Repair 14.5 Main Cleaning & Maintenance: Flushing, Pigging & Lining 14.6 Excavation, Trench Safety & Utility Locating

15 Chapter 15: Disinfecting Distribution Facilities & Maintaining Water Quality

15.1 Water Main Disinfection (AWWA C651) 15.2 Disinfecting Storage Reservoirs (C652) & Wells (C654) 15.3 Maintaining Distribution Water Quality: Residual, Biofilm & Discolored Water 15.4 Cross-Connection Control Program Administration & Device Testing

16 Chapter 16: Plant Equipment, Chemical Feed & Maintenance

16.1 Chemical Feed Systems: Metering Pumps, Dry Feeders & Calibration 16.2 Gas Chlorination Equipment & Hypochlorite Systems 16.3 Blowers, Compressors & Aeration Equipment 16.4 Flow Measurement Devices: Meters, Weirs & Flumes 16.5 Preventive Maintenance, CMMS & Asset Management

17 Chapter 17: Utility Management, Administration & Emergency Response

17.1 Planning, Organizing, Directing & Controlling a Utility Work Group 17.2 Budgets, Water Rates & Financial Management 17.3 Operator Training, Staffing & Safety Program Development 17.4 Energy Management & Optimization 17.5 Emergency Response Planning, Risk & Resilience & Security 17.6 Water Conservation Planning & Drought Response

18 Chapter 18: Applied Operator Mathematics Workshop

18.1 The Exam Conversion Sheet, Units & Dimensional Analysis 18.2 Distribution & Hydraulic Math Workshop 18.3 Treatment & Wastewater Process Math Workshop

11.1 The Revised Total Coliform Rule & Assessments

Key Takeaways Explain This Topic AI

The Total Coliform Rule is a named sub-topic in both the treatment and the distribution Expected Range of Knowledge documents.

The RTCR replaced the old monthly total coliform MCL with a treatment technique built on Level 1 and Level 2 assessments; only E. coli now carries an MCL.

A Level 1 trigger is more than 5.0 percent coliform-positive samples for systems taking 40 or more samples per month, or two or more positives for systems taking fewer than 40, or failure to take every required repeat sample.

A Level 2 trigger is an E. coli MCL violation, a second Level 1 trigger within a rolling 12 months, or for annual-monitoring systems a Level 1 trigger in two consecutive years.

Every routine total coliform-positive sample requires a set of repeat samples, and every total coliform-positive sample must be analyzed for E. coli.

Last updated: September 2026

From an MCL to a Find-and-Fix Rule

The original Total Coliform Rule set a monthly MCL for total coliform . The Revised Total Coliform Rule (RTCR) , effective for all systems from April 1, 2016, changed the philosophy. Total coliform is now treated as an indicator that something may be wrong , not as a health violation in itself. The rule works as a treatment technique : a coliform result above a trigger requires the system to find and fix the sanitary defect .

  • Old TCR RTCR
  • Total coliform MCL violation Trigger for an assessment - no MCL
  • E. coli Acute MCL via a fecal coliform pathway MCL, with a specific definition
  • Response to positives Public notification Level 1 or Level 2 assessment plus corrective action
  • Focus Reporting an exceedance Identifying and correcting sanitary defects

California implements the RTCR through the Division of Drinking Water; the federal rule is at 40 CFR Part 141, Subpart Y .

Routine and Repeat Monitoring

Routine samples are collected on a schedule set by system size and population, at sites listed in the system's sample siting plan . The plan must identify routine sites representative of water throughout the distribution system, plus the repeat sites associated with each routine site.

Repeat monitoring is triggered by any total coliform-positive routine sample. The standard set is:

  • One repeat at the same tap as the original positive
  • One repeat within five service connections upstream
  • One repeat within five service connections downstream

Repeat samples are collected within 24 hours of being notified of the positive result, and every total coliform-positive sample - routine or repeat - must be analyzed for E. coli.

Tip

Getting the repeat set wrong is itself a violation. "Failure to take every required repeat sample after any single total coliform-positive sample" is an explicit Level 1 trigger , independent of what the results show. Missing the paperwork is treated as seriously as missing the bacteria.

  • The Triggers
  • Level 1 Assessment Triggers

Systems collecting 40 or more samples per month: the system exceeds 5.0 percent total coliform-positive samples for the month.

Systems collecting fewer than 40 samples per month: the system has two or more total coliform-positive samples in the same month.

The system fails to take every required repeat sample after any single total coliform-positive sample.

Level 2 Assessment Triggers

An E. coli MCL violation .

A second Level 1 trigger within a rolling 12-month period - unless the State determined a likely reason for the first Level 1 trigger and the system corrected the problem.

For systems on State-approved annual monitoring , a Level 1 trigger in two consecutive years .

What Level 1 and Level 2 Actually Require

Both assessments exist to identify the possible presence of sanitary defects and defects in distribution system coliform monitoring practices .

Level 1 Level 2

Who conducts it The system itself (a trained operator) A State-approved party - often the State, a third-party expert, or a specifically approved system staff member

Depth Review of treatment, source, protocols, monitoring practices, and recent operations More comprehensive, including a detailed review of history, treatment, source, distribution, hydraulics, and operational practices

Timing Submitted to the State within 30 days of learning the trigger was met Same 30-day submission clock

Output Identified sanitary defects, corrective actions taken, and a schedule for those not yet completed Same, at greater depth

A sanitary defect is a defect that could provide a pathway for contamination, that is indicative of a failure or imminent failure in a barrier already in place, or that fails to prevent contamination. Classic examples: an unscreened storage vent, a submerged overflow, a failed well seal, a cross-connection, an unprotected sample tap, or a system operated below 20 psi.

The E. coli MCL

An E. coli MCL violation occurs when any of the following happens:

The system has an E. coli-positive repeat sample following a total coliform-positive routine sample .

The system has a total coliform-positive repeat sample following an E. coli-positive routine sample .

The system fails to take all required repeat samples following an E. coli-positive routine sample.

The system fails to test for E. coli when any repeat sample tests positive for total coliform.

Important

Note that two of the four pathways are procedural failures, not laboratory results . A system that gets an E. coli-positive routine sample and then does not collect the full repeat set has committed an E. coli MCL violation regardless of what the water actually contained. An E. coli MCL violation is an acute violation requiring Tier 1 public notification within 24 hours and triggers a Level 2 assessment.

Other RTCR Requirements Operators Own

Sample siting plan. Must be developed, kept current, and available for State review. Sites must be representative; a plan that samples only the two most convenient taps near the office is a documented defect.

Seasonal systems - those that are not operated year-round, such as campgrounds and seasonal restaurants - must complete a State-approved start-up procedure before serving water to the public , and must certify its completion. Failure to complete the approved start-up procedure is a treatment technique violation.

Groundwater Rule interaction. A total coliform-positive routine sample at a groundwater system without 4-log virus treatment triggers source water (triggered) monitoring under the Ground Water Rule.

Corrective action. Sanitary defects identified in an assessment must be corrected, and the system must consult with the State if it cannot correct a defect before submitting the assessment form.

Reduced monitoring is available to small systems with a clean record, a completed sanitary survey with no significant deficiencies, and an approved sample siting plan.

A Worked Compliance Scenario

A system serving 6,800 people collects 8 routine samples per month . In March, two samples come back total coliform-positive. The system collects the full repeat set for each; all repeats are negative and no E. coli is detected.

Because the system takes fewer than 40 samples per month and had two positives in the same month , a Level 1 trigger has been met.

The system conducts a Level 1 assessment itself and submits it to the State within 30 days .

There is no MCL violation and no acute public notification , because no E. coli was found and no repeat requirement was missed.

If a second Level 1 trigger occurs before the following March, and the State has not determined and the system has not corrected a cause for the first one, that becomes a Level 2 trigger .