Study guide
2.1 California Title 22 Recycled Water Standards
California Water/Wastewater Operator Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: California Water Regulatory Framework & Certification Ladders
1.1 State Water Board & Regional Boards Structure 1.2 Drinking Water Certification: T1-T5 & D1-D5 Requirements 1.3 Wastewater Certification: Grades I-V & OIT Requirements 1.4 Safe Drinking Water Standards, MCLs & Emerging Contaminants 1.5 California Waterworks Standards (Title 22, Chapter 16) 1.6 Public Water System Types, Permits & the Sanitary Survey
2 Chapter 2: California Water Rights, Title 22 & Environmental Policy
2.1 California Title 22 Recycled Water Standards 2.2 California Environmental Quality Act (CEQA) & Proposition 218 2.3 Water Rights & California Water Resources
3 Chapter 3: Drinking Water Source Quality & Coagulation/Flocculation
3.1 Source Water Quality & Watershed Management 3.2 Coagulation Chemistry & Flash Mixing 3.3 Flocculation & Jar Testing 3.4 Wells, Aquifers & Groundwater Hydraulics 3.5 Raw Water Storage, Clearwells & Reservoir Management
4 Chapter 4: Clarification & Granular Media Filtration
4.1 Sedimentation & Advanced Clarification 4.2 Granular Media Filtration Mechanics & Media Types 4.3 Filter Operation, Backwash Cycles & SWTR Compliance
5 Chapter 5: Disinfection, Oxidation & Advanced Water Treatment
5.1 Chlorination Chemistry & Breakpoint Curves 5.2 Disinfection Kinetics & CT Calculations 5.3 Alternative Disinfection: Ozone, UV & Chlorine Dioxide 5.4 Advanced Treatment: Membranes, AOP & PFAS Adsorption 5.5 Chloramination & Nitrification Control 5.6 Iron & Manganese Removal 5.7 Fluoridation Practice & Compliance 5.8 Corrosion Control Treatment & Water Stability 5.9 Taste & Odor Control and Algal Toxin Management
6 Chapter 6: Wastewater Preliminary & Primary Treatment
6.1 Preliminary Treatment: Screening & Grit Removal 6.2 Primary Clarification Operations 6.3 Primary Sludge Characteristics & Pumping 6.4 Stabilization Ponds, Lagoons & Small-Plant Processes
7 Chapter 7: Secondary Biological Treatment & Activated Sludge
7.1 Activated Sludge Process Fundamentals 7.2 Process Control Parameters: F/M, MCRT & SVI 7.3 Activated Sludge Microbiology & Troubleshooting 7.4 Fixed-Film & Hybrid Biological Processes
8 Chapter 8: Biological Nutrient Removal, Water Reuse & Solids Handling
8.1 Biological Nitrogen Removal: Nitrification & Denitrification 8.2 Biological Phosphorus Removal (EBPR) & Chemical Precipitation 8.3 Anaerobic & Aerobic Digestion 8.4 Sludge Thickening, Dewatering & Biosolids Disposal 8.5 Wastewater Disinfection: Chlorination, Dechlorination & UV
9 Chapter 9: Distribution Systems, Collection Networks & Hydraulics
9.1 Hydraulics, Pressure & Flow Dynamics 9.2 Centrifugal Pumps, Motors & VFDs 9.3 Distribution Network Infrastructure & Cross-Connection Control 9.4 Wastewater Collection Systems, SSMP & FOG Management
10 Chapter 10: Laboratory Analytics, Safety & Water Math
10.1 Water & Wastewater Laboratory Methods 10.2 Laboratory Quality Assurance & Regulatory Reporting 10.3 Chemical Safety, Hazardous Gases & Confined Space 10.4 Essential Water & Wastewater Math for Operators
11 Chapter 11: Federal & California Drinking Water Rules
11.1 The Revised Total Coliform Rule & Assessments 11.2 The Lead and Copper Rule and Service Line Replacement 11.3 Surface Water Treatment Rules & Log Removal Credit 11.4 Stage 1 & Stage 2 Disinfection Byproduct Rules 11.5 Secondary MCLs, Notification Levels & Response Levels 11.6 Public Notification, Consumer Confidence Reports & Recordkeeping
12 Chapter 12: Distribution System Design, Demand & Hydraulics
12.1 System Layout, Pressure Zones & Distribution Maps 12.2 Water Demand, Peaking Factors & Fire Flow 12.3 Distribution Storage: Types, Sizing & Turnover 12.4 Head Loss, C-Factor & Distribution Hydraulic Calculations 12.5 Water Hammer, Surge Control & Air Management
13 Chapter 13: Distribution Equipment Operation, Maintenance & Inspection
13.1 Valves: Types, Operation & Exercising Programs 13.2 Fire Hydrants: Types, Testing & Maintenance 13.3 Water Meters: Types, Accuracy & Meter Management 13.4 Instrumentation, In-Line Sensors, Telemetry & SCADA 13.5 Electrical Systems, Motors & Standby Generators 13.6 External Corrosion, Cathodic Protection & Asset Inspection
14 Chapter 14: Water Mains, Piping & Field Construction
14.1 Pipe Materials & Pipe Selection 14.2 Joints, Fittings, Thrust Restraint & Bedding 14.3 Main Installation, Tapping & Service Line Installation 14.4 Leak Detection, Water Loss Auditing & Main Repair 14.5 Main Cleaning & Maintenance: Flushing, Pigging & Lining 14.6 Excavation, Trench Safety & Utility Locating
15 Chapter 15: Disinfecting Distribution Facilities & Maintaining Water Quality
15.1 Water Main Disinfection (AWWA C651) 15.2 Disinfecting Storage Reservoirs (C652) & Wells (C654) 15.3 Maintaining Distribution Water Quality: Residual, Biofilm & Discolored Water 15.4 Cross-Connection Control Program Administration & Device Testing
16 Chapter 16: Plant Equipment, Chemical Feed & Maintenance
16.1 Chemical Feed Systems: Metering Pumps, Dry Feeders & Calibration 16.2 Gas Chlorination Equipment & Hypochlorite Systems 16.3 Blowers, Compressors & Aeration Equipment 16.4 Flow Measurement Devices: Meters, Weirs & Flumes 16.5 Preventive Maintenance, CMMS & Asset Management
17 Chapter 17: Utility Management, Administration & Emergency Response
17.1 Planning, Organizing, Directing & Controlling a Utility Work Group 17.2 Budgets, Water Rates & Financial Management 17.3 Operator Training, Staffing & Safety Program Development 17.4 Energy Management & Optimization 17.5 Emergency Response Planning, Risk & Resilience & Security 17.6 Water Conservation Planning & Drought Response
18 Chapter 18: Applied Operator Mathematics Workshop
18.1 The Exam Conversion Sheet, Units & Dimensional Analysis 18.2 Distribution & Hydraulic Math Workshop 18.3 Treatment & Wastewater Process Math Workshop
2.1 California Title 22 Recycled Water Standards
Key Takeaways Explain This Topic AI
California Code of Regulations (CCR) Title 22 Division 4 Chapter 3 establishes four primary recycled water classifications: Disinfected Tertiary, Disinfected Secondary-2.2, Disinfected Secondary-23, and Undisinfected Secondary.
Disinfected tertiary recycled water requires strict turbidity control (<= 2 NTU 24-hour average, <= 5 NTU 95% of the time, never > 10 NTU) and disinfection criteria (7-day median coliform <= 2.2 MPN/100 mL, single sample max <= 23 MPN/100 mL, absolute max <= 240 MPN/100 mL, chlorine CT >= 450 mg·min/L with modal contact time >= 90 minutes).
Unrestricted urban reuse—such as food crops with edible surface contact, residential front-yard landscaping, schoolyards, parks, and commercial toilet flushing—strictly mandates disinfected tertiary recycled water.
The State Water Resources Control Board adopted Direct Potable Reuse (DPR) regulations establishing a 12-10-10 Log Reduction Value (LRV) standard (12-log virus, 10-log Cryptosporidium, 10-log Giardia) through multi-barrier purification with continuous Critical Control Point (CCP) monitoring.
Last updated: August 2026
California Title 22 Recycled Water Standards
Water recycling is a cornerstone of California's long-term water resilience strategy. The primary legal framework governing the production, distribution, and use of non-potable and potable recycled water in California is codified in the California Code of Regulations (CCR) Title 22, Division 4, Chapter 3 (known comprehensively as the Water Recycling Criteria ). Enacted to safeguard public health while encouraging resource recovery, Title 22 establishes strict biological, chemical, and operational benchmarks that every certified water and wastewater treatment operator must master.
Regulatory authority is shared between two key state bodies:
State Water Resources Control Board (SWRCB) Division of Drinking Water (DDW) : Formulates health-protective criteria, establishes statutory water quality standards, reviews engineering reports, and approves treatment technologies.
Regional Water Quality Control Boards (RWQCBs) : Issues enforceable permits—including Water Reclamation Requirements (WRRs) , Waste Discharge Requirements (WDRs), and Master Recycling Permits—that mandate ongoing operational compliance and water quality monitoring.
Before any recycled water project can deliver water to end users, the producer and distributor must submit a comprehensive Title 22 Engineering Report (CCR Title 22 § 60323) to DDW and the appropriate Regional Board detailing treatment processes, reliability features, alarm setpoints, and emergency diversion protocols.
The Four Title 22 Recycled Water Quality Classifications
Title 22 categorizes recycled water into four distinct tiers based on the degree of secondary biological oxidation, filtration, and chemical or physical disinfection achieved. As potential human contact and exposure increase, the regulatory treatment standards become progressively more stringent.
Recycled Water Classification Filtration Requirement Total Coliform Disinfection Standard CT / Contact Time Requirement Key Permitted Applications
Disinfected Tertiary Recycled Water Granular media (<= 2 NTU avg) or Membrane (<= 0.2 NTU) 7-day median <= 2.2 MPN/100 mL; max <= 23 in 30 days; never > 240 MPN/100 mL CT >= 450 mg·min/L with modal contact time >= 90 min (or validated UV >= 5-log virus inactivation) Food crops (edible portion contact), parks, schoolyards, residential lawns, toilet flushing, decorative fountains
Disinfected Secondary-2.2 Recycled Water None required (oxidized secondary effluent) 7-day median <= 2.2 MPN/100 mL; max <= 23 MPN/100 mL in any 30-day period Disinfection contact time sufficient to achieve coliform limits Freeway landscaping, surface irrigation of food crops where edible portion is completely above ground (citrus, vineyards)
Disinfected Secondary-23 Recycled Water None required (oxidized secondary effluent) 7-day median <= 23 MPN/100 mL; max <= 240 MPN/100 mL in any 30-day period Disinfection contact time sufficient to achieve coliform limits Pasture for milking animals, landscape impoundments without body contact, industrial cooling without mist, concrete making
Undisinfected Secondary Recycled Water None required (oxidized secondary effluent) No coliform limit specified None required Non-food crops (cotton, grain, silviculture), seed crops, pasture for non-milking livestock, surface orchard irrigation
Disinfected Tertiary Recycled Water: Technical Deep-Dive
Disinfected tertiary recycled water represents the highest standard for non-potable reuse and requires dual barriers: advanced filtration followed by high-level disinfection.
1. Filtration Standards & Turbidity Limits
Filtration removes particulate matter, suspended solids, and parasite cysts (such as Giardia and Cryptosporidium ), ensuring that downstream disinfectants can penetrate remaining microorganisms without shielding.
Conventional Granular Media Filtration (Rapid sand, dual-media anthracite/sand, or multi-media):
Daily 24-hour average turbidity must not exceed 2 NTU (Nephelometric Turbidity Units).
Turbidity must not exceed 5 NTU for more than 5 percent of the time during any 24-hour period.
Turbidity must never exceed 10 NTU at any instantaneous moment.
Membrane Filtration (Microfiltration [MF] or Ultrafiltration [UF]):
Turbidity must not exceed 0.2 NTU for more than 5 percent of the time within any 24-hour period.
Turbidity must never exceed 0.5 NTU at any time.
Operational Directive: If tertiary effluent turbidity exceeds regulatory limits, automated plant controls must immediately divert the off-spec water back to the plant headworks or equalization basins. Unfiltered or improperly filtered water must never reach the disinfection contact basin.
2. Disinfection Kinetics and the CT Standard
Title 22 mandates strict disinfection performance criteria for disinfected tertiary water to ensure near-complete viral and bacterial inactivation:
Chlorine Contact Kinetics ( C T CT CT Concept) : CT = C × T 10 ≥ 450 mg ⋅ min / L \text{CT} = C \times T_{10} \ge 450\text{ mg}\cdot\text{min}/\text{L} CT = C × T 10 ≥ 450 mg ⋅ min / L Where:
C C C is the modal chlorine residual (in mg/L \text{mg/L} mg/L ) measured at the end of the contact chamber.
T 10 T_{10} T 10 is the modal contact time (in minutes) through the chamber under peak dry-weather or wet-weather hourly flow rates.
Title 22 requires a minimum modal contact time of not less than 90 minutes at peak design flow.
Alternative Disinfection (Ultraviolet / UV) :
Facilities utilizing UV disinfection instead of chlorine must demonstrate an inactivation credit equivalent to chlorine disinfection. The National Water Research Institute (NWRI) guidelines, incorporated into Title 22 approvals, require UV systems to achieve at least 5-log inactivation of virus (using MS2 or poliovirus surrogates), typically requiring an applied design dose of >= 100 mJ/cm² .
3. Bacteriological Sampling Standards
Samples must be collected daily at the effluent compliance point:
7-Day Median Total Coliform : Must not exceed 2.2 MPN / 100 mL (Most Probable Number per 100 milliliters).
30-Day Ceiling : Must not exceed 23 MPN / 100 mL in more than one sample in any 30-day rolling window.
Instantaneous Maximum : Must never exceed 240 MPN / 100 mL in any single grab sample.
- Secondary Recycled Water Tiers & Specific Uses
- Disinfected Secondary-2.2
Disinfected Secondary-2.2 utilizes biological oxidation and disinfection without tertiary filtration. Total coliform limits match the 7-day median of tertiary water (<= 2.2 MPN/100 mL, max single sample <= 23 MPN/100 mL in 30 days). Permitted uses include:
Surface irrigation of food crops where the edible portion of the crop grows entirely above ground and receives no direct contact with recycled water (e.g., drip-irrigated citrus orchards, avocado groves, and trellised wine vineyards).
Restricted access landscape irrigation, such as freeway medians and interchange landscaping.
Disinfected Secondary-23
Disinfected Secondary-23 requires biological oxidation and moderate disinfection (7-day median <= 23 MPN/100 mL; max single sample <= 240 MPN/100 mL in 30 days). Permitted uses include:
Irrigation of pasture grazed by milking animals (dairy cattle, goats).
Industrial cooling towers operating without mist-producing draft equipment .
Landscape impoundments without body contact.
Construction water for soil compaction, dust suppression, and concrete batching.
Undisinfected Secondary
Undisinfected secondary water is oxidized secondary effluent that has received no pathogen disinfection. Permitted uses are strictly non-contact:
Irrigation of non-food vegetation, including silviculture (tree farms), fiber crops (cotton), and seed crops.
Pasture grazed exclusively by non-milking livestock (beef cattle).
Direct Potable Reuse (DPR) Regulations (2023/2024 Framework)
In December 2023 (formally codified in 2024), the SWRCB adopted landmark regulations for Direct Potable Reuse (DPR) , establishing rules for introducing purified recycled water directly into a public drinking water distribution system or raw water conveyance upstream of a drinking water treatment plant without an environmental buffer (such as an aquifer or reservoir). +---------------------------------------------------------------------------------------------------------+
- | DIRECT POTABLE REUSE (DPR) TREATMENT TRAIN |
- +---------------------------------------------------------------------------------------------------------+
- | [Secondary BNR Effluent] |
- | | |
- | v |
- | [Microfiltration / Ultrafiltration (MF/UF)] ==> Target: Giardia/Cryptosporidium (>= 4-log removal) |
- | | |
- | v |
- | [Reverse Osmosis (RO)] ==> Target: Salts, PFAS, TOC, Viruses (>= 1.5-2 log) |
- | | |
- | v |
- | [Advanced Oxidation Process (UV/AOP)] ==> Target: NDMA, 1,4-Dioxane, Pathogens (>= 6-log virus)|
- | | |
- | v |
- | [Granular Activated Carbon / Free Chlorine] ==> Target: Disinfection byproducts, Residual stability |
- | | |
- | v |
- | [Engineered Storage Buffer (ESB)] ==> Target: Real-time verification & emergency diversion |
- | | |
- | v |
- | [Finished Potable Drinking Water Distribution] |
- +---------------------------------------------------------------------------------------------------------+
- The 12-10-10 Pathogen Log Reduction Standard
DPR facilities must achieve unprecedented multi-barrier pathogen removal between raw wastewater influent and finished purified water:
Enteric Virus : 12-log reduction ( 99.9999999999 % 99.9999999999\% 99.9999999999% removal/inactivation).
Cryptosporidium oocysts : 10-log reduction ( 99.99999999 % 99.99999999\% 99.99999999% removal/inactivation).
Giardia duodenalis cysts : 10-log reduction ( 99.99999999 % 99.99999999\% 99.99999999% removal/inactivation).
Multi-Barrier Treatment & Capping Mandates
To guarantee fail-safe operation, DDW established strict structural engineering requirements:
Barrier Independence : At least three separate, independent treatment processes must be deployed for each target pathogen class (virus, Cryptosporidium , and Giardia ).
Log Credit Capping : No single treatment process can be credited with more than 6-log reduction toward any pathogen category, preventing over-reliance on a single mechanism.
Continuous Critical Control Point (CCP) Monitoring : Every barrier must be monitored continuously online using validated surrogates (e.g., pressure decay tests for MF/UF, electrical conductivity / TOC reduction for RO, and UV sensor intensity/transmittance for UV-AOP). Any excursion triggers immediate, automatic diversion of off-spec water to the sewer system before it reaches the engineered storage buffer.
Cross-Connection Control & Physical Site Protection
To prevent catastrophic cross-contamination between recycled water and potable drinking water distribution networks, California enforces rigorous physical isolation rules:
Color Coding : All recycled water transmission mains, distribution piping, valves, sprinkler risers, and valve boxes must be colored Pantone 512 Purple or wrapped in purple polyethylene warning tape.
Signage : Warning signs displaying the international "Do Not Drink" symbol and text in English and Spanish ( "CAUTION: RECYCLED WATER – DO NOT DRINK" ) must be posted at all reuse sites.
Separation Distances : Recycled water pipelines must maintain a minimum 10-foot horizontal separation from parallel potable water mains and be installed at least 1 foot below potable lines in vertical crossings.
Setback from Potable Wells : Disinfected tertiary irrigation must maintain a minimum 50-foot setback from domestic drinking water supply wells. Secondary recycled water requires a 100-foot setback .
Cross-Connection Testing : Dual-plumbed buildings (using recycled water for toilet flushing or cooling towers) must undergo mandatory cross-connection shutdown tests prior to initial operation and at least once every 4 years thereafter.