Study guide
14.5 Main Cleaning & Maintenance: Flushing, Pigging & Lining
California Water/Wastewater Operator Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: California Water Regulatory Framework & Certification Ladders
1.1 State Water Board & Regional Boards Structure 1.2 Drinking Water Certification: T1-T5 & D1-D5 Requirements 1.3 Wastewater Certification: Grades I-V & OIT Requirements 1.4 Safe Drinking Water Standards, MCLs & Emerging Contaminants 1.5 California Waterworks Standards (Title 22, Chapter 16) 1.6 Public Water System Types, Permits & the Sanitary Survey
2 Chapter 2: California Water Rights, Title 22 & Environmental Policy
2.1 California Title 22 Recycled Water Standards 2.2 California Environmental Quality Act (CEQA) & Proposition 218 2.3 Water Rights & California Water Resources
3 Chapter 3: Drinking Water Source Quality & Coagulation/Flocculation
3.1 Source Water Quality & Watershed Management 3.2 Coagulation Chemistry & Flash Mixing 3.3 Flocculation & Jar Testing 3.4 Wells, Aquifers & Groundwater Hydraulics 3.5 Raw Water Storage, Clearwells & Reservoir Management
4 Chapter 4: Clarification & Granular Media Filtration
4.1 Sedimentation & Advanced Clarification 4.2 Granular Media Filtration Mechanics & Media Types 4.3 Filter Operation, Backwash Cycles & SWTR Compliance
5 Chapter 5: Disinfection, Oxidation & Advanced Water Treatment
5.1 Chlorination Chemistry & Breakpoint Curves 5.2 Disinfection Kinetics & CT Calculations 5.3 Alternative Disinfection: Ozone, UV & Chlorine Dioxide 5.4 Advanced Treatment: Membranes, AOP & PFAS Adsorption 5.5 Chloramination & Nitrification Control 5.6 Iron & Manganese Removal 5.7 Fluoridation Practice & Compliance 5.8 Corrosion Control Treatment & Water Stability 5.9 Taste & Odor Control and Algal Toxin Management
6 Chapter 6: Wastewater Preliminary & Primary Treatment
6.1 Preliminary Treatment: Screening & Grit Removal 6.2 Primary Clarification Operations 6.3 Primary Sludge Characteristics & Pumping 6.4 Stabilization Ponds, Lagoons & Small-Plant Processes
7 Chapter 7: Secondary Biological Treatment & Activated Sludge
7.1 Activated Sludge Process Fundamentals 7.2 Process Control Parameters: F/M, MCRT & SVI 7.3 Activated Sludge Microbiology & Troubleshooting 7.4 Fixed-Film & Hybrid Biological Processes
8 Chapter 8: Biological Nutrient Removal, Water Reuse & Solids Handling
8.1 Biological Nitrogen Removal: Nitrification & Denitrification 8.2 Biological Phosphorus Removal (EBPR) & Chemical Precipitation 8.3 Anaerobic & Aerobic Digestion 8.4 Sludge Thickening, Dewatering & Biosolids Disposal 8.5 Wastewater Disinfection: Chlorination, Dechlorination & UV
9 Chapter 9: Distribution Systems, Collection Networks & Hydraulics
9.1 Hydraulics, Pressure & Flow Dynamics 9.2 Centrifugal Pumps, Motors & VFDs 9.3 Distribution Network Infrastructure & Cross-Connection Control 9.4 Wastewater Collection Systems, SSMP & FOG Management
10 Chapter 10: Laboratory Analytics, Safety & Water Math
10.1 Water & Wastewater Laboratory Methods 10.2 Laboratory Quality Assurance & Regulatory Reporting 10.3 Chemical Safety, Hazardous Gases & Confined Space 10.4 Essential Water & Wastewater Math for Operators
11 Chapter 11: Federal & California Drinking Water Rules
11.1 The Revised Total Coliform Rule & Assessments 11.2 The Lead and Copper Rule and Service Line Replacement 11.3 Surface Water Treatment Rules & Log Removal Credit 11.4 Stage 1 & Stage 2 Disinfection Byproduct Rules 11.5 Secondary MCLs, Notification Levels & Response Levels 11.6 Public Notification, Consumer Confidence Reports & Recordkeeping
12 Chapter 12: Distribution System Design, Demand & Hydraulics
12.1 System Layout, Pressure Zones & Distribution Maps 12.2 Water Demand, Peaking Factors & Fire Flow 12.3 Distribution Storage: Types, Sizing & Turnover 12.4 Head Loss, C-Factor & Distribution Hydraulic Calculations 12.5 Water Hammer, Surge Control & Air Management
13 Chapter 13: Distribution Equipment Operation, Maintenance & Inspection
13.1 Valves: Types, Operation & Exercising Programs 13.2 Fire Hydrants: Types, Testing & Maintenance 13.3 Water Meters: Types, Accuracy & Meter Management 13.4 Instrumentation, In-Line Sensors, Telemetry & SCADA 13.5 Electrical Systems, Motors & Standby Generators 13.6 External Corrosion, Cathodic Protection & Asset Inspection
14 Chapter 14: Water Mains, Piping & Field Construction
14.1 Pipe Materials & Pipe Selection 14.2 Joints, Fittings, Thrust Restraint & Bedding 14.3 Main Installation, Tapping & Service Line Installation 14.4 Leak Detection, Water Loss Auditing & Main Repair 14.5 Main Cleaning & Maintenance: Flushing, Pigging & Lining 14.6 Excavation, Trench Safety & Utility Locating
15 Chapter 15: Disinfecting Distribution Facilities & Maintaining Water Quality
15.1 Water Main Disinfection (AWWA C651) 15.2 Disinfecting Storage Reservoirs (C652) & Wells (C654) 15.3 Maintaining Distribution Water Quality: Residual, Biofilm & Discolored Water 15.4 Cross-Connection Control Program Administration & Device Testing
16 Chapter 16: Plant Equipment, Chemical Feed & Maintenance
16.1 Chemical Feed Systems: Metering Pumps, Dry Feeders & Calibration 16.2 Gas Chlorination Equipment & Hypochlorite Systems 16.3 Blowers, Compressors & Aeration Equipment 16.4 Flow Measurement Devices: Meters, Weirs & Flumes 16.5 Preventive Maintenance, CMMS & Asset Management
17 Chapter 17: Utility Management, Administration & Emergency Response
17.1 Planning, Organizing, Directing & Controlling a Utility Work Group 17.2 Budgets, Water Rates & Financial Management 17.3 Operator Training, Staffing & Safety Program Development 17.4 Energy Management & Optimization 17.5 Emergency Response Planning, Risk & Resilience & Security 17.6 Water Conservation Planning & Drought Response
18 Chapter 18: Applied Operator Mathematics Workshop
18.1 The Exam Conversion Sheet, Units & Dimensional Analysis 18.2 Distribution & Hydraulic Math Workshop 18.3 Treatment & Wastewater Process Math Workshop
14.5 Main Cleaning & Maintenance: Flushing, Pigging & Lining
Key Takeaways Explain This Topic AI
Cleaning and Maintenance is a named sub-topic in the Water Mains and Piping category, and Unidirectional Flushing is a separate named sub-topic under Water Quality.
Conventional flushing opens hydrants to waste water, while unidirectional flushing uses planned valve closures to force high scouring velocity along a defined path.
Unidirectional flushing targets a velocity of about 5 to 8 ft/s, well above normal operating velocity, to actually scour deposits.
Swabbing, pigging, and air scouring provide mechanical cleaning where flushing alone cannot restore water quality or capacity.
Cleaning and lining restores C-factor and stops internal corrosion, and the main must be disinfected under AWWA C651 and shown coliform-negative before return to service.
Last updated: September 2026
Why Mains Need Cleaning
Four things accumulate on the inside of a distribution main:
Corrosion products and tubercles - iron oxides in unlined cast iron and steel; they destroy C-factor and release as red water
Sediment - fine particles carried from the plant or from the source, settling in low-velocity mains and dead ends
Manganese and iron deposits - a soft black or brown film that releases as black water on any velocity change
Biofilm - which shelters organisms from disinfectant, exerts chlorine demand, harbors nitrifiers in chloraminated systems, and generates taste and odor
The symptoms are familiar: discolored water complaints clustered after a fire flow , loss of disinfectant residual at the ends of the system , rising HPC , nitrification episodes , and falling C-factor .
Conventional Flushing
Open hydrants and blowoffs and let water run to waste until it clears. Simple, and it has real limitations:
Water arrives at the flushed hydrant from multiple directions , so velocity in any one pipe may be far below scouring velocity
- It redistributes deposits rather than removing them, sometimes pushing sediment into a clean area
- It uses a large volume for a modest result
Conventional flushing is still the right tool for dead ends on a routine schedule and for rapid response to a complaint , but it is not a cleaning program.
Unidirectional Flushing (UDF)
Unidirectional flushing is a designed program. Valves are closed so water is forced to travel one direction along a defined path , at a velocity high enough to scour, using clean water from an already-flushed segment .
Design Rules
- Element Target
- Scouring velocity 5 to 8 ft/s (some programs accept 3-5 ft/s as a minimum)
- Direction of work From the clean source outward , sequentially - never pull dirty water into a clean segment
- Segment size Small enough that the available hydrant flow produces the target velocity in the target pipe
Duration Until the water runs clear and turbidity and chlorine residual meet targets, usually a defined number of pipe volumes
Verification Turbidity, color, chlorine residual, and often iron and manganese, before and after
Worked example. To achieve 6 ft/s in an 8-inch main: Q = 2.448 × D 2 × V = 2.448 × 64 × 6 = 940 gpm Q = 2.448 \times D^{2} \times V = 2.448 \times 64 \times 6 = \textbf{940 gpm} Q = 2.448 × D 2 × V = 2.448 × 64 × 6 = 940 gpm
A single 2.5-inch hydrant outlet flowing roughly 500-900 gpm may or may not get there. In a 12-inch main the requirement is 2.448 x 144 x 6 = 2,115 gpm , which usually needs the 4.5-inch steamer outlet or two hydrants. This calculation is the heart of UDF design : if the available flow cannot reach scouring velocity in that pipe, flushing it accomplishes little.
- Benefits Over Conventional Flushing
- Uses substantially less water for a better result, because every gallon is doing work at scouring velocity
- Removes deposits rather than moving them
- Verifies valve operation as a by-product - the crew discovers inoperable valves during the sequence
- Produces a documented, repeatable annual program with before-and-after water quality data
- Mechanical Cleaning
Where deposits are too consolidated for flushing:
Method Description Notes
Swabbing Soft polyurethane foam swab pushed through by water pressure Gentle; good for sediment and soft deposits; multiple passes with progressively larger swabs
Poly pigging Denser foam or coated pig, sometimes with a wire or carbide coating Removes harder deposits
Air scouring Compressed air injected into a flowing main creates a turbulent slug flow Effective in smaller mains; needs careful air control to avoid surge
Mechanical scraping / power boring Rotating cutters pulled through the main Removes heavy tuberculation ahead of lining
Ice pigging An ice slurry pumped through the main behaves as a soft plug Low risk of sticking; no launch and retrieval pig traps needed
Practical constraints: butterfly valves obstruct pigs and swabs , so the path must be verified; a stuck pig requires excavation; and every mechanical method requires launch and retrieval points , isolation, and a plan for the removed material.
Cleaning and Lining
For heavily tuberculated unlined cast iron, the durable answer is clean and line :
Isolate and dewater the main; establish temporary service (a bypass, often a surface-laid HDPE line with its own disinfection and sampling)
Mechanically clean by scraping or power boring to bare metal
Apply a cement-mortar lining (spun in place, then troweled at the joints) or a spray-applied polyurea/epoxy lining
Cure per the manufacturer's requirements
Disinfect per AWWA C651-05 , flush, and sample; samples must be coliform-negative before return to service under 22 CCR 64580
The payoff: C-factor restored from perhaps 60 to 120 or better , internal corrosion stopped, red water eliminated, and chlorine demand reduced - typically at a fraction of the cost and disruption of replacement, provided the pipe has adequate remaining wall thickness and an acceptable break history.
Discharge Control
Flushing puts large volumes of chlorinated water onto the ground, and that carries obligations:
Obligation Practice
Dechlorination Discharge that can reach a storm drain, creek, wetland, or the ocean must generally be dechlorinated. Use tablets in a diffuser, or meter sodium bisulfite or ascorbic acid. Chlorine residual is acutely toxic to fish at concentrations far below drinking water levels
Erosion and sediment control Use a diffuser to break the jet; protect slopes, unpaved shoulders, and landscaping
Turbidity The discharge itself must not create a turbidity violation in a receiving water
Traffic and pedestrian safety Cones, signage, spotters; do not flood a travel lane or a sidewalk in freezing weather
Notification Notify customers in the flushing area; discolored water complaints follow flushing, and a notice converts a complaint into an understood inconvenience
Volume accounting Estimate and record the volume as unbilled authorized consumption in the water audit
Water conservation optics During drought, publicize why flushing is being done and that the program is designed to minimize volume - which is one of the strongest arguments for UDF over conventional flushing
Tip
Sequence matters more than duration. A UDF program that flushes segments in the wrong order pulls dirty water through clean pipe and generates complaints in areas that were fine before the crew arrived. Always work outward from a known-clean source, and verify each segment before opening the next.