2.3 Fluid Mechanics and Airflow Fundamentals

CIH Certified Industrial Hygienist Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: The CIH Exam and How to Use This Guide

1.1 CIH Exam Format, Scoring, and Test-Day Logistics 1.2 Eligibility, Application Windows, Fees, and Certification Maintenance 1.3 The BGC Blueprint, Subject Areas, and a Calculation-First Study Plan

2 Chapter 2: Basic Science & Calculations

2.1 Gas Laws and Vapor Calculations 2.2 Unit Conversions: ppm, mg/m³, and Standard Temperature/Pressure 2.3 Fluid Mechanics and Airflow Fundamentals

3 Chapter 3: Air Sampling & Instrumentation

3.1 Active and Passive Air Sampling Strategies 3.2 Particulate and Aerosol Sampling 3.3 Direct-Reading Instruments and Calibration

4 Chapter 4: Analytical Chemistry & Lab Methods

4.1 Gas Chromatography and Mass Spectrometry 4.2 High-Performance Liquid Chromatography and Ion Chromatography 4.3 Spectroscopy and Elemental Analysis 4.4 Gravimetric, Microscopy, and Wet Chemical Methods 4.5 Laboratory Quality Assurance, Chain of Custody, and Desorption Efficiency

5 Chapter 5: Biostatistics & Epidemiology

5.1 Lognormal Distributions and Exposure Data Statistics 5.2 Upper Confidence Limits (UCL95) and Compliance Decision Rules 5.3 Epidemiological Study Designs and Measures of Association 5.4 Sampling Strategy: Sample Size, Power, and Worker Selection

6 Chapter 6: Toxicology & Biological Monitoring

6.1 Dose-Response Relationships and Points of Departure 6.2 Toxicokinetics: Absorption, Distribution, Metabolism, and Elimination 6.3 Aerosol Deposition, Clearance, and Respiratory Tract Dosimetry 6.4 Hepatic, Renal, Neurologic, and Hematologic Target Organ Toxicity 6.5 Pulmonary Toxicology, Carcinogenicity, and Reproductive Hazards 6.6 OEL Frameworks, Classifications, and Excursion Limits 6.7 Chemical Mixtures and Extended Work-Shift OEL Adjustments 6.8 Biological Exposure Indices (BEIs) and Biomonitoring

7 Chapter 7: Biohazards & Indoor Environmental Quality

7.1 Mold, Fungi, and Microbial Contaminants 7.2 Infectious Agents, Bloodborne Pathogens, and Biosafety Levels 7.3 Indoor Environmental Quality (IEQ) Investigations 7.4 Sanitation, Potable Water, and Personal Hygiene Programs

8 Chapter 8: Community Exposure & Environmental Health

8.1 Clean Air Act Framework, NAAQS, and New Source Review 8.2 Hazardous Air Pollutants, CEMS, and EPA Reference Methods 8.3 Atmospheric Stability, Lapse Rates, and Plume Morphology 8.4 Gaussian Plume Modeling, Plume Rise, and Environmental Fate 8.5 HAZWOPER Scope, Mandates, and Training Tiers 8.6 Protection Levels, Site Zoning, Incident Command, and Decontamination 8.7 Water Pollution, Hazardous Waste, and Community Right-to-Know

9 Chapter 9: Health Risk Analysis & Hazard Communication

9.1 GHS Hazard Classification: Health and Physical Hazard Criteria 9.2 GHS Labels, Safety Data Sheets, and Trade Secret Rules 9.3 The AIHA Exposure Assessment Strategy and Similar Exposure Groups 9.4 Qualitative Exposure Profiling and the AIHA Risk Matrix 9.5 Quantitative Health Risk Characterization: HQ, HI, and ELCR 9.6 NIOSH Occupational Exposure Banding 9.7 Risk Communication and Reporting to Affected Parties

10 Chapter 10: Industrial Ventilation Principles & LEV Design

10.1 Elimination, Substitution, Isolation, Containment, and Process Change 10.2 LEV Hood Taxonomy and Capture Velocity Selection 10.3 Hood Airflow Equations, Entry Losses, and Hood Static Pressure 10.4 Particulate Transport Aerodynamics and Duct Sizing 10.5 Duct Friction, Fitting Losses, and System Balancing 10.6 Fan Categories and Pressure Dynamics Across the Fan 10.7 System Curves, the Fan Laws, and Density Corrections

11 Chapter 11: General Ventilation, Air Cleaning & Diagnostics

11.1 Dilution Ventilation Principles and Steady-State Modeling 11.2 Transient Purging and Air Distribution Geometry 11.3 Particulate Air Cleaning: Cyclones, Baghouses, Scrubbers, and ESPs 11.4 Gaseous Emission Control and Air Cleaner Selection 11.5 Ventilation System Troubleshooting and Testing

12 Chapter 12: Noise Measurement & Hearing Conservation

12.1 Acoustic Physics and Decibel Mathematics 12.2 Sound Propagation, Octave Bands, and Frequency Weighting 12.3 Noise Dose Metrics and OSHA versus ACGIH Criteria 12.4 Exchange Rates, Extended Shifts, and Dosimetry Field Protocols 12.5 Engineering Noise Controls and Hearing Protector Attenuation 12.6 Hearing Conservation Programs and Standard Threshold Shifts 12.7 Hand-Arm and Whole-Body Vibration

13 Chapter 13: Thermal Stress Assessment & Control

13.1 Wet Bulb Globe Temperature (WBGT) and Heat Stress Indices 13.2 Heat-Related Disorders, Acclimatization, and Work/Rest Regimens 13.3 Cold Stress Evaluation and Wind Chill

14 Chapter 14: Ionizing Radiation Protection

14.1 Ionizing Radiation Physics and Radioactive Decay Kinetics 14.2 Radiation Units, Radiobiology, and Health Effects 14.3 ALARA, Stay-Time, and the Inverse Square Law 14.4 Shielding Physics, Material Selection, and Gamma Constants 14.5 Radiation Detection Instruments and Spectrometry 14.6 Personnel Dosimetry, Dose Limits, and Contamination Surveys

15 Chapter 15: Non-Ionizing Radiation & Laser Safety

15.1 The Non-Ionizing Spectrum and Static/ELF Field Exposures 15.2 Radiofrequency and Microwave Exposure: SAR, Standards, and Surveys 15.3 Ultraviolet, Visible, and Infrared Radiation Hazards 15.4 Laser Safety Classifications and Optical Density Calculations 15.5 Illumination, Lighting Design, and Visual Performance

16 Chapter 16: Non-Engineering Controls & Personal Protective Equipment

16.1 Respiratory Protection Programs and Assigned Protection Factors 16.2 Maximum Use Concentration, Oxygen Deficiency, and Breathing Air 16.3 Particulate Filters, Sorbent Cartridges, and Change Schedules 16.4 Respirator Fit Testing Protocols 16.5 Chemical Protective Clothing and Dermal Exposure Control

17 Chapter 17: Ergonomics & Workstation Design

17.1 Soft-Tissue Biomechanics and WMSD Pathophysiology 17.2 Ergonomic Risk Factors and Their Interaction Effects 17.3 The Revised NIOSH Lifting Equation 17.4 RULA, REBA, the Strain Index, and the ACGIH HAL TLV 17.5 Anthropometry and Workstation Geometry 17.6 VDT Workstations, Hand Tool Design, and Administrative Ergonomics

18 Chapter 18: Work Environments & Industrial Processes

18.1 Welding Fume Emissions, Metal Fume Fever, and Cr(VI)/Manganese Toxicology 18.2 Foundry Operations and Hot Work Fire Prevention 18.3 Vapor Degreasing, Pickling, Electroplating, and Cyanide Baths 18.4 Spray Coatings, Isocyanates, and Semiconductor Manufacturing 18.5 Confined Spaces and High-Hazard Industrial Operations 18.6 Asbestos, Lead, and Silica: Regulated Substance Programs 18.7 Abrasive Blasting and Surface Preparation

19 Chapter 19: IH Program Management & Professional Ethics

19.1 The BGC Code of Ethics: Canons and Enforcement 19.2 Professional Liability, Standard of Care, and Expert Testimony 19.3 Occupational Health & Safety Management Systems (ISO 45001, ANSI Z10) 19.4 Exposure Records Access and Medical Surveillance 19.5 OSHA Injury and Illness Recordkeeping and Enforcement

2.3 Fluid Mechanics and Airflow Fundamentals

Key Takeaways Explain This Topic AI

The Continuity Equation (Q = V × A) dictates that for incompressible airflow, volumetric flow rate remains constant along a duct, meaning velocity varies inversely with cross-sectional area.

Total Pressure is the algebraic sum of Static Pressure and Velocity Pressure (TP = SP + VP); while Static Pressure can be positive or negative, Velocity Pressure is always positive.

Velocity Pressure converts to duct air velocity via V = 4005 × √(VP) at standard air density (0.075 lb/ft³), or VP = (V / 4005)².

The Reynolds number (Re = ρVD / μ) determines flow regime in ducts; Re < 2,000 represents laminar flow, whereas Re > 4,000 indicates fully turbulent flow with flattened velocity profiles.

Duct friction losses scale directly with duct length and velocity squared, and inversely with duct diameter according to the Darcy-Weisbach equation (hf = f · (L/D) · VP).

Last updated: August 2026

Fluid Mechanics and Airflow Fundamentals

Local exhaust ventilation (LEV), dilution ventilation, air sampling manifolds, and particle transport lines operate according to the fundamental laws of fluid mechanics. Industrial hygienists must evaluate airflow quantities, duct velocities, static and dynamic pressure distributions, and energy losses to design, test, and troubleshoot engineering control systems. This section covers the continuity equation, Bernoulli's energy conservation, duct pressure relationships, the velocity pressure equation, Reynolds numbers, and friction loss calculations.

1. The Continuity Equation and Conservation of Mass

In fluid dynamics, the Law of Conservation of Mass states that mass can neither be created nor destroyed in a steady-state fluid system. For flow through a closed conduit or ventilation duct: m ˙ = ρ 1 A 1 V 1 = ρ 2 A 2 V 2 = constant \dot{m} = \rho_1 A_1 V_1 = \rho_2 A_2 V_2 = \text{constant} m ˙ = ρ 1 ​ A 1 ​ V 1 ​ = ρ 2 ​ A 2 ​ V 2 ​ = constant

Where:

  • m = mass flow rate (lb/min or kg/s)
  • ρ = fluid density (lb/ft³ or kg/m³)
  • A = cross-sectional area of duct (ft² or m²)
  • V = average fluid velocity (ft/min or m/s)
  • Incompressibility Assumption in Industrial Ventilation

Under standard industrial ventilation conditions, pressure differentials rarely exceed ± 20 inches of water gauge (≈ 0.72 psi or 5 kPa), which represents less than a 5% variation from atmospheric pressure (14.7 psia). Air velocities in LEV systems are almost always well below 10,000 fpm (Mach number < 0.15).

Consequently, air can be treated as an incompressible fluid of constant density (ρ1 = ρ2) , simplifying the continuity equation to volumetric flow rate (Q): Q = V × A ⟺ Q = V 1 A 1 = V 2 A 2 \mathbf{Q = V \times A} \quad \Longleftrightarrow \quad \mathbf{Q = V_1 A_1 = V_2 A_2} Q = V × A ⟺ Q = V 1 ​ A 1 ​ = V 2 ​ A 2 ​

Where:

  • Q = Volumetric airflow rate in Cubic Feet per Minute (CFM) or m³/s
  • V = Average air velocity in Feet per Minute (FPM) or m/s
  • A = Cross-sectional duct area in Square Feet (extft²) or m²
  • Duct Geometry Formulas

Duct Shape Cross-Sectional Area (A) Formula Parameter Definitions

Round / Circular Duct A = (π D²)/4 = (π d²)/576 D = diameter in feet, d = diameter in inches (A = (π (d/12)²)/4)

  • Rectangular Duct A = W × H = (w × h)/144 W, H in feet; w, h in inches
  • Equivalent Hydraulic Diameter Dh = 4A/Pw = (2 × W × H)/(W + H) Pw = wetted perimeter (2W + 2H)
  • 2. Bernoulli's Principle & Total, Static, and Velocity Pressure

Bernoulli's Theorem expresses the conservation of mechanical energy along a streamline in steady, frictionless fluid flow: P 1 ρ g + V 1 2 2 g + z 1 = P 2 ρ g + V 2 2 2 g + z 2 + h loss \frac{P_1}{\rho g} + \frac{V_1^2}{2g} + z_1 = \frac{P_2}{\rho g} + \frac{V_2^2}{2g} + z_2 + h_{\text{loss}} ρ g P 1 ​ ​ + 2 g V 1 2 ​ ​ + z 1 ​ = ρ g P 2 ​ ​ + 2 g V 2 2 ​ ​ + z 2 ​ + h loss ​

Because the density of air is low, elevation head changes (z1 - z2) across industrial duct runs are negligible and set to zero. Energy in a ventilation duct is therefore expressed in terms of fluid pressures, measured in inches of water gauge (in. w.g.) or Pascals (Pa) .

The Fundamental Duct Pressure Relationship

At any point in a duct system, the Total Pressure (TP) is the algebraic sum of Static Pressure (SP) and Velocity Pressure (VP) : T P = S P + V P \mathbf{TP = SP + VP} TP = SP + VP +-------------------------------------------------------------+

  • | VENTILATION PRESSURE COMPONENTS |
  • +-------------------------------------------------------------+
  • | |
  • | STATIC PRESSURE (SP) + VELOCITY PRESSURE (VP) |
  • | - Potential energy - Kinetic energy of motion |
  • | - Exerted in all directions - Exerted only in flow dir |
  • | - Can be POSITIVE or NEGATIVE - ALWAYS POSITIVE (> 0) |
  • | - Collapses/bursts duct walls - Directly yields velocity |
  • | |
  • | = |
  • | |
  • | TOTAL PRESSURE (TP) |
  • | - Total energy in duct |
  • | - Decreases downstream (losses) |
  • +-------------------------------------------------------------+
  • Detailed Characterization of Pressure Components

Static Pressure (SP):

Represents the potential energy of the air.

Acts perpendicularly and equally in all directions against the interior duct walls.

Sign Convention: On the suction side of the fan (upstream/inlet), SP is negative (below atmospheric pressure), acting to collapse the duct. On the discharge side of the fan (downstream/outlet), SP is positive (above atmospheric pressure), acting to expand the duct.

Measured using a static pressure tap flush with the duct wall.

Velocity Pressure (VP):

Represents the kinetic energy of the moving airstream.

Acts exclusively in the direction of airflow.

Sign Convention: Velocity pressure is always positive (VP > 0) in moving air, and zero in stationary air.

Measured using the differential between the impact tip and static side ports of a Standard Pitot-Static tube.

Total Pressure (TP):

Measures the total mechanical energy present in the fluid stream.

Because friction and turbulence convert mechanical energy into irreversible thermal energy, TP always decreases in the direction of airflow through passive ductwork, fittings, and hoods. Only the fan adds energy to create a sudden rise in TP.

3. Derivation of the Velocity Pressure Equation (V = 4005√(VP))

A cornerstone formula on the CIH exam is the equation converting measured velocity pressure (VP, in inches of water) to average linear air velocity (V, in feet per minute).

Step-by-Step Mathematical Derivation

From basic physics, kinetic energy head is h = V²/2g, or V = √(2gh).

Express fluid velocity in feet per second (v): v = 2 g h air v = \sqrt{2 g h_{\text{air}}} v = 2 g h air ​ ​

Where g = 32.174 ft/s² and hair is fluid column height in feet of air.

Convert column height from inches of water (VP) to feet of air (hair):

Standard density of liquid water at 70°F: ρwater = 62.37 lb/ft³ ≈ 62.4 lb/ft³

Standard density of dry air at 70°F (21.1°C) and 29.92 in. Hg (760 mmHg): ρair = 0.07495 lb/ft³ ≈ 0.075 lb/ft³ h air = ( V P in. w.g. 12 in/ft ) × ( ρ water ρ air ) = ( V P 12 ) × ( 62.37 0.07495 ) = 69.345 × V P h_{\text{air}} = \left(\frac{VP\text{ in. w.g.}}{12\text{ in/ft}}\right) \times \left(\frac{\rho_{\text{water}}}{\rho_{\text{air}}}\right) = \left(\frac{VP}{12}\right) \times \left(\frac{62.37}{0.07495}\right) = 69.345 \times VP h air ​ = ( 12 in/ft V P in. w.g. ​ ) × ( ρ air ​ ρ water ​ ​ ) = ( 12 V P ​ ) × ( 0.07495 62.37 ​ ) = 69.345 × V P

Substitute into the velocity equation and convert velocity from ft/sec to ft/min (V = 60 × v): v ( ft/s ) = 2 × 32.174 × ( 69.345 × V P ) = 4462.6 × V P = 66.803 × V P v(\text{ft/s}) = \sqrt{2 \times 32.174 \times (69.345 \times VP)} = \sqrt{4462.6 \times VP} = 66.803 \times \sqrt{VP} v ( ft/s ) = 2 × 32.174 × ( 69.345 × V P ) ​ = 4462.6 × V P ​ = 66.803 × V P ​ V ( ft/min ) = 60 × v ( ft/s ) = 60 × 66.803 × V P = 4008.2 × V P ≈ 4005 V P V(\text{ft/min}) = 60 \times v(\text{ft/s}) = 60 \times 66.803 \times \sqrt{VP} = \mathbf{4008.2 \times \sqrt{VP} \approx 4005\sqrt{VP}} V ( ft/min ) = 60 × v ( ft/s ) = 60 × 66.803 × V P ​ = 4008.2 × VP ​ ≈ 4005 VP ​

Working Equations for Standard and Non-Standard Conditions V = 4005 V P ⟺ V P = ( V 4005 ) 2 ( Standard Air: 70 ∘ F , 29.92 in. Hg ) \mathbf{V = 4005 \sqrt{VP}} \quad \Longleftrightarrow \quad \mathbf{VP = \left(\frac{V}{4005}\right)^2} \quad (\text{Standard Air: } 70^\circ\text{F}, 29.92\text{ in. Hg}) V = 4005 VP ​ ⟺ VP = ( 4005 V ​ ) 2 ( Standard Air: 7 0 ∘ F , 29.92 in. Hg )

For non-standard temperatures or elevations, density correction factor (d = ρactual / 0.075) is applied: V = 4005 V P d where d = ( 530 T ( ∘ F ) + 460 ) × ( P baro ( in. Hg ) 29.92 ) V = 4005 \sqrt{\frac{VP}{d}} \quad \text{where } d = \left(\frac{530}{T(^\circ\text{F}) + 460}\right) \times \left(\frac{P_{\text{baro}}(\text{in. Hg})}{29.92}\right) V = 4005 d V P ​ ​ where d = ( T ( ∘ F ) + 460 530 ​ ) × ( 29.92 P baro ​ ( in. Hg ) ​ )

4. Reynolds Number & Flow Regimes in Ducts and Sampling Lines

The Reynolds Number (Re) is a dimensionless parameter representing the ratio of inertial forces to viscous forces in fluid flow: R e = ρ V D μ = V D ν Re = \frac{\rho V D}{\mu} = \frac{V D}{\nu} R e = μ ρ V D ​ = ν V D ​

Where:

  • ρ = fluid density (kg/m³ or lb/ft³)
  • V = average velocity (m/s or ft/s)
  • D = internal pipe/duct diameter (m or ft)
  • µ = absolute dynamic viscosity (Pa·s or lb/(ft·s))
  • ν = µ / ρ = kinematic viscosity (m²/s or ft²/s)
  • Flow Regimes in Circular Pipes and Ventilation Ducts

Flow Regime Reynolds Number Range Velocity Profile Characteristics Industrial Hygiene Application

Laminar Flow Re < 2,000 Parabolic profile; centerline velocity Vmax = 2.0 × Vavg; smooth streamlines without radial mixing Critical flow orifices, low-flow personal sampling tubes, cyclone aerosol pre-separators

Transition Zone 2,000 ≤ Re ≤ 4,000 Unstable flow fluctuating between laminar and turbulent states Avoid designing industrial LEV systems in this regime

Turbulent Flow Re > 4,000 Flattened velocity profile; centerline velocity Vmax ≈ 1.15 - 1.25 × Vavg; intense eddy mixing Industrial LEV exhaust ductwork, stack discharge, particulate transport lines

Key Principle in Particulate Transport: Industrial exhaust systems capturing dusts and fumes are intentionally designed for fully turbulent flow (Re >> 10,000, with transport velocities typically between 3,500 fpm and 4,500 fpm) to keep particles suspended and prevent duct clogging.

5. Duct Friction Losses & The Darcy-Weisbach Equation

As air moves through a duct, friction against the duct walls and internal turbulent eddies dissipate mechanical energy as heat. The fundamental equation for friction head loss (hf) is the Darcy-Weisbach Equation : h f = f ( L D ) ( V 2 2 g ) = f ( L D ) V P h_f = f \left(\frac{L}{D}\right) \left(\frac{V^2}{2g}\right) = f \left(\frac{L}{D}\right) VP h f ​ = f ( D L ​ ) ( 2 g V 2 ​ ) = f ( D L ​ ) V P

Where:

  • hf = friction head loss in duct (in. w.g.)
  • f = dimensionless Darcy friction factor (determined by pipe roughness and Re on the Moody Diagram)
  • L = duct length (feet)
  • D = duct diameter (feet)
  • VP = velocity pressure (in. w.g.)
  • Duct Loss Coefficient Method (K)

For hood entries, elbows, branch entries, expansions, and contractions, pressure losses are expressed as a fraction of the velocity pressure: h loss = K × V P h_{\text{loss}} = K \times VP h loss ​ = K × V P

Where K is the specific fitting loss coefficient (e.g., K = 0.50 for a standard 90° flanged hood entry, K = 0.25 for a smooth rounded 5-piece duct elbow).

  • 6. Worked Step-by-Step Calculation Examples
  • Worked Example 1.6: Continuity Equation and Duct Sizing for Particulate Transport

Problem: A local exhaust ventilation hood captures metal grinding dust from a buffing wheel at a required volumetric flow rate of Q = 1,400 CFM. To prevent heavy metallic dust particles from settling out and clogging the ductwork, the ACGIH Industrial Ventilation Manual recommends a minimum duct transport velocity of V = 4,000 fpm.

Calculate the required duct cross-sectional area in square feet.

Determine the exact duct diameter in inches.

If standard round spiral duct is available in whole-inch increments (e.g., 7-inch, 8-inch, 9-inch), select the correct size and calculate the resulting actual duct velocity.

Solution Steps:

Calculate required area using Q = V × A: A = Q V = 1 , 400 CFM 4 , 000 fpm = 0.350 ft 2 A = \frac{Q}{V} = \frac{1,400\text{ CFM}}{4,000\text{ fpm}} = 0.350\text{ ft}^2 A = V Q ​ = 4 , 000 fpm 1 , 400 CFM ​ = 0.350 ft 2

Calculate exact duct diameter (d in inches): A = π d 2 576 ⟹ d = 576 × A π = 576 × 0.350 3.14159 = 64.17 = 8.01 inches A = \frac{\pi d^2}{576} \implies d = \sqrt{\frac{576 \times A}{\pi}} = \sqrt{\frac{576 \times 0.350}{3.14159}} = \sqrt{64.17} = 8.01\text{ inches} A = 576 π d 2 ​ ⟹ d = π 576 × A ​ ​ = 3.14159 576 × 0.350 ​ ​ = 64.17 ​ = 8.01 inches

Select standard duct size and verify transport velocity:

If a 9-inch duct were selected (A = 0.4418 ft²), actual velocity would be V = 1400 / 0.4418 = 3,169 fpm, which is below the 4,000 fpm minimum and would allow duct settling.

Therefore, select an 8-inch diameter duct : A actual = π ( 8 ) 2 576 = 201.06 576 = 0.3491 ft 2 A_{\text{actual}} = \frac{\pi (8)^2}{576} = \frac{201.06}{576} = 0.3491\text{ ft}^2 A actual ​ = 576 π ( 8 ) 2 ​ = 576 201.06 ​ = 0.3491 ft 2 V actual = Q A actual = 1 , 400 CFM 0.3491 ft 2 = 4 , 010 fpm V_{\text{actual}} = \frac{Q}{A_{\text{actual}}} = \frac{1,400\text{ CFM}}{0.3491\text{ ft}^2} = 4,010\text{ fpm} V actual ​ = A actual ​ Q ​ = 0.3491 ft 2 1 , 400 CFM ​ = 4 , 010 fpm

Result: Select an 8-inch duct , providing an actual transport velocity of 4,010 fpm , safely satisfying transport requirements.

Worked Example 1.7: Pitot-Static Tube Velocity and Airflow Rate Calculation

Problem: A CIH performs a multi-point Pitot-tube traverse on a 12-inch diameter circular exhaust duct at standard air density. The average of the square roots of the velocity pressures across the traverse points is √(VP)-bar = 0.750 (in. w.g.)(1/2).

Calculate the average air velocity (V) in feet per minute.

Calculate the total volumetric flow rate (Q) in CFM.

Solution Steps:

Calculate average velocity using V = 4005 × √(VP)-bar:

Measurement Rule: Always average the square roots of the velocity pressures, rather than averaging velocity pressures and taking the square root afterward (Vavg = 4005 × avg(√(VP)) ≠ 4005 × √(avg(VP))). V = 4005 × 0.750 = 3 , 003.75 fpm ≈ 3 , 004 fpm V = 4005 \times 0.750 = 3,003.75\text{ fpm} \approx 3,004\text{ fpm} V = 4005 × 0.750 = 3 , 003.75 fpm ≈ 3 , 004 fpm

Calculate duct area (A) for a 12-inch diameter duct: A = π ( 12 in ) 2 576 = 3.14159 × 144 576 = 0.7854 ft 2 A = \frac{\pi (12\text{ in})^2}{576} = \frac{3.14159 \times 144}{576} = 0.7854\text{ ft}^2 A = 576 π ( 12 in ) 2 ​ = 576 3.14159 × 144 ​ = 0.7854 ft 2

Calculate volumetric flow rate (Q = V × A): Q = 3 , 003.75 fpm × 0.7854 ft 2 = 2 , 359.1 CFM Q = 3,003.75\text{ fpm} \times 0.7854\text{ ft}^2 = 2,359.1\text{ CFM} Q = 3 , 003.75 fpm × 0.7854 ft 2 = 2 , 359.1 CFM

Result: The duct air velocity is 3,004 fpm and the total airflow is 2,359 CFM .

Worked Example 1.8: Total, Static, and Velocity Pressure Balance Across a Hood

Problem: In an LEV branch duct located upstream of the exhaust fan, a technician measures a static pressure of SP = -2.75 in. w.g. and a velocity pressure of VP = 0.64 in. w.g..

Calculate the Total Pressure (TP) at this measurement plane.

Explain the physical significance of the sign of each pressure value.

Solution Steps:

Apply the total pressure equation (TP = SP + VP): T P = S P + V P = − 2.75 in. w.g. + 0.64 in. w.g. = − 2.11 in. w.g. TP = SP + VP = -2.75\text{ in. w.g.} + 0.64\text{ in. w.g.} = -2.11\text{ in. w.g.} TP = SP + V P = − 2.75 in. w.g. + 0.64 in. w.g. = − 2.11 in. w.g.

Physical Analysis:

SP = -2.75 in. w.g.: Negative potential energy because the duct is under suction from the fan inlet, drawing air into the hood against friction and entry losses.

VP = +0.64 in. w.g.: Positive kinetic energy corresponding to a duct velocity of V = 4005√(0.64) = 4005 × 0.80 = 3,204 fpm.

TP = -2.11 in. w.g.: Negative total energy relative to ambient room pressure (0.0 in. w.g.), reflecting the energy loss required to accelerate air into the hood and overcome upstream friction.