Study guide

10.5 Duct Friction, Fitting Losses, and System Balancing

CIH Certified Industrial Hygienist Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: The CIH Exam and How to Use This Guide

1.1 CIH Exam Format, Scoring, and Test-Day Logistics 1.2 Eligibility, Application Windows, Fees, and Certification Maintenance 1.3 The BGC Blueprint, Subject Areas, and a Calculation-First Study Plan

2 Chapter 2: Basic Science & Calculations

2.1 Gas Laws and Vapor Calculations 2.2 Unit Conversions: ppm, mg/m³, and Standard Temperature/Pressure 2.3 Fluid Mechanics and Airflow Fundamentals

3 Chapter 3: Air Sampling & Instrumentation

3.1 Active and Passive Air Sampling Strategies 3.2 Particulate and Aerosol Sampling 3.3 Direct-Reading Instruments and Calibration

4 Chapter 4: Analytical Chemistry & Lab Methods

4.1 Gas Chromatography and Mass Spectrometry 4.2 High-Performance Liquid Chromatography and Ion Chromatography 4.3 Spectroscopy and Elemental Analysis 4.4 Gravimetric, Microscopy, and Wet Chemical Methods 4.5 Laboratory Quality Assurance, Chain of Custody, and Desorption Efficiency

5 Chapter 5: Biostatistics & Epidemiology

5.1 Lognormal Distributions and Exposure Data Statistics 5.2 Upper Confidence Limits (UCL95) and Compliance Decision Rules 5.3 Epidemiological Study Designs and Measures of Association 5.4 Sampling Strategy: Sample Size, Power, and Worker Selection

6 Chapter 6: Toxicology & Biological Monitoring

6.1 Dose-Response Relationships and Points of Departure 6.2 Toxicokinetics: Absorption, Distribution, Metabolism, and Elimination 6.3 Aerosol Deposition, Clearance, and Respiratory Tract Dosimetry 6.4 Hepatic, Renal, Neurologic, and Hematologic Target Organ Toxicity 6.5 Pulmonary Toxicology, Carcinogenicity, and Reproductive Hazards 6.6 OEL Frameworks, Classifications, and Excursion Limits 6.7 Chemical Mixtures and Extended Work-Shift OEL Adjustments 6.8 Biological Exposure Indices (BEIs) and Biomonitoring

7 Chapter 7: Biohazards & Indoor Environmental Quality

7.1 Mold, Fungi, and Microbial Contaminants 7.2 Infectious Agents, Bloodborne Pathogens, and Biosafety Levels 7.3 Indoor Environmental Quality (IEQ) Investigations 7.4 Sanitation, Potable Water, and Personal Hygiene Programs

8 Chapter 8: Community Exposure & Environmental Health

8.1 Clean Air Act Framework, NAAQS, and New Source Review 8.2 Hazardous Air Pollutants, CEMS, and EPA Reference Methods 8.3 Atmospheric Stability, Lapse Rates, and Plume Morphology 8.4 Gaussian Plume Modeling, Plume Rise, and Environmental Fate 8.5 HAZWOPER Scope, Mandates, and Training Tiers 8.6 Protection Levels, Site Zoning, Incident Command, and Decontamination 8.7 Water Pollution, Hazardous Waste, and Community Right-to-Know

9 Chapter 9: Health Risk Analysis & Hazard Communication

9.1 GHS Hazard Classification: Health and Physical Hazard Criteria 9.2 GHS Labels, Safety Data Sheets, and Trade Secret Rules 9.3 The AIHA Exposure Assessment Strategy and Similar Exposure Groups 9.4 Qualitative Exposure Profiling and the AIHA Risk Matrix 9.5 Quantitative Health Risk Characterization: HQ, HI, and ELCR 9.6 NIOSH Occupational Exposure Banding 9.7 Risk Communication and Reporting to Affected Parties

10 Chapter 10: Industrial Ventilation Principles & LEV Design

10.1 Elimination, Substitution, Isolation, Containment, and Process Change 10.2 LEV Hood Taxonomy and Capture Velocity Selection 10.3 Hood Airflow Equations, Entry Losses, and Hood Static Pressure 10.4 Particulate Transport Aerodynamics and Duct Sizing 10.5 Duct Friction, Fitting Losses, and System Balancing 10.6 Fan Categories and Pressure Dynamics Across the Fan 10.7 System Curves, the Fan Laws, and Density Corrections

11 Chapter 11: General Ventilation, Air Cleaning & Diagnostics

11.1 Dilution Ventilation Principles and Steady-State Modeling 11.2 Transient Purging and Air Distribution Geometry 11.3 Particulate Air Cleaning: Cyclones, Baghouses, Scrubbers, and ESPs 11.4 Gaseous Emission Control and Air Cleaner Selection 11.5 Ventilation System Troubleshooting and Testing

12 Chapter 12: Noise Measurement & Hearing Conservation

12.1 Acoustic Physics and Decibel Mathematics 12.2 Sound Propagation, Octave Bands, and Frequency Weighting 12.3 Noise Dose Metrics and OSHA versus ACGIH Criteria 12.4 Exchange Rates, Extended Shifts, and Dosimetry Field Protocols 12.5 Engineering Noise Controls and Hearing Protector Attenuation 12.6 Hearing Conservation Programs and Standard Threshold Shifts 12.7 Hand-Arm and Whole-Body Vibration

13 Chapter 13: Thermal Stress Assessment & Control

13.1 Wet Bulb Globe Temperature (WBGT) and Heat Stress Indices 13.2 Heat-Related Disorders, Acclimatization, and Work/Rest Regimens 13.3 Cold Stress Evaluation and Wind Chill

14 Chapter 14: Ionizing Radiation Protection

14.1 Ionizing Radiation Physics and Radioactive Decay Kinetics 14.2 Radiation Units, Radiobiology, and Health Effects 14.3 ALARA, Stay-Time, and the Inverse Square Law 14.4 Shielding Physics, Material Selection, and Gamma Constants 14.5 Radiation Detection Instruments and Spectrometry 14.6 Personnel Dosimetry, Dose Limits, and Contamination Surveys

15 Chapter 15: Non-Ionizing Radiation & Laser Safety

15.1 The Non-Ionizing Spectrum and Static/ELF Field Exposures 15.2 Radiofrequency and Microwave Exposure: SAR, Standards, and Surveys 15.3 Ultraviolet, Visible, and Infrared Radiation Hazards 15.4 Laser Safety Classifications and Optical Density Calculations 15.5 Illumination, Lighting Design, and Visual Performance

16 Chapter 16: Non-Engineering Controls & Personal Protective Equipment

16.1 Respiratory Protection Programs and Assigned Protection Factors 16.2 Maximum Use Concentration, Oxygen Deficiency, and Breathing Air 16.3 Particulate Filters, Sorbent Cartridges, and Change Schedules 16.4 Respirator Fit Testing Protocols 16.5 Chemical Protective Clothing and Dermal Exposure Control

17 Chapter 17: Ergonomics & Workstation Design

17.1 Soft-Tissue Biomechanics and WMSD Pathophysiology 17.2 Ergonomic Risk Factors and Their Interaction Effects 17.3 The Revised NIOSH Lifting Equation 17.4 RULA, REBA, the Strain Index, and the ACGIH HAL TLV 17.5 Anthropometry and Workstation Geometry 17.6 VDT Workstations, Hand Tool Design, and Administrative Ergonomics

18 Chapter 18: Work Environments & Industrial Processes

18.1 Welding Fume Emissions, Metal Fume Fever, and Cr(VI)/Manganese Toxicology 18.2 Foundry Operations and Hot Work Fire Prevention 18.3 Vapor Degreasing, Pickling, Electroplating, and Cyanide Baths 18.4 Spray Coatings, Isocyanates, and Semiconductor Manufacturing 18.5 Confined Spaces and High-Hazard Industrial Operations 18.6 Asbestos, Lead, and Silica: Regulated Substance Programs 18.7 Abrasive Blasting and Surface Preparation

19 Chapter 19: IH Program Management & Professional Ethics

19.1 The BGC Code of Ethics: Canons and Enforcement 19.2 Professional Liability, Standard of Care, and Expert Testimony 19.3 Occupational Health & Safety Management Systems (ISO 45001, ANSI Z10) 19.4 Exposure Records Access and Medical Surveillance 19.5 OSHA Injury and Illness Recordkeeping and Enforcement

10.5 Duct Friction, Fitting Losses, and System Balancing

Key Takeaways Explain This Topic AI

Duct friction loss is computed from the Darcy-Weisbach relationship or read from ACGIH friction charts as a loss per 100 feet of duct at a given flow and diameter.

Fitting losses are expressed as a loss factor times velocity pressure; elbow loss depends strongly on centreline radius-to-diameter ratio, with R/D between 1.5 and 2.5 giving the practical optimum.

Entry loss at a branch depends on the entry angle: a 30-degree branch entry is far lower loss than a 90-degree tee.

Balance by design (static pressure balance) redesigns branch diameters so junction static pressures match within about 5%, while balance by blast gate uses adjustable dampers that can be tampered with and require rebalancing.

Last updated: August 2026

Duct Friction, Fitting Losses, and System Balancing

Choosing a transport velocity and a duct diameter fixes the geometry. Predicting whether the fan can actually move that air requires adding up every friction and fitting loss in the run, and then making the branches balance at the junctions.

1. Duct Friction Losses: Darcy-Weisbach & ACGIH Charts

As air travels through ductwork, mechanical energy is converted into non-recoverable heat via fluid friction against the duct walls and internal turbulent shearing.

Darcy-Weisbach Equation h f = f ⋅ ( L D ) ⋅ V P h_f = f \cdot \left(\frac{L}{D}\right) \cdot VP h f ​ = f ⋅ ( D L ​ ) ⋅ V P

Where:

  • hf = Friction loss in inches of water gauge (in. w.g.)
  • f = Dimensionless Darcy friction factor (function of Reynolds number Re and duct roughness ε/D)
  • L = Duct length (ft)
  • D = Duct hydraulic diameter (ft)
  • VP = Velocity pressure in the duct (in. w.g.)
  • The ACGIH Standard Friction Chart

In industrial hygiene design, friction loss is determined using standard ACGIH Air Friction Charts for round galvanized metal ductwork carrying standard air (0.075 lb/ft³ at 70°F and 29.92 in. Hg). Losses are expressed as friction loss per 100 feet of duct (extin. w.g. / 100 ft) : h friction = ( Loss per 100 ft 100 ) × L actual h_{\text{friction}} = \left(\frac{\text{Loss per } 100\text{ ft}}{100}\right) \times L_{\text{actual}} h friction ​ = ( 100 Loss per 100 ft ​ ) × L actual ​

2. Fitting and Transition Dynamic Losses

Whenever air changes direction, expands, contracts, or merges, flow separation and turbulent eddy dissipation induce dynamic fitting losses (hL) , calculated using the dimensionless loss coefficient (K): h L = K × V P d \mathbf{h_L = K \times VP_d} h L ​ = K × V P d ​

Elbow Aerodynamics: Centerline Radius-to-Diameter Ratio (R/D)

When air negotiates a bend, centrifugal force creates a high-pressure zone along the outer radius and a low-pressure separation bubble along the inner radius, generating severe secondary twin-vortex swirling. +-------------------------------------------------------------------------+

  • | ELBOW RADIUS-TO-DIAMETER RATIO (R/D) |
  • +-------------------------------------------------------------------------+
  • | |
  • | Centerline Radius (R) |
  • | <---------------------------> |
  • | +---------------------------+---- |
  • | | | ^ |
  • | | .-''''-. | | Duct Diameter (D) |
  • | | / \ | v |
  • | | | Center | +---- |
  • | | | Line | |
  • | | \ / |
  • | | '-....-' |
  • | | |
  • | * Optimal LEV Design: R/D = 1.5 to 2.5 (K = 0.15 to 0.24) |
  • | * Mitered 90° Elbow: R/D = 0.75 (K = 0.75 to 1.30 - AVOID!) |
  • +-------------------------------------------------------------------------+

The aerodynamic severity of an elbow is determined by its Centerline Radius-to-Diameter Ratio (R/D) : R / D = Centerline Radius of Elbow ( R ) Duct Diameter ( D ) R/D = \frac{\text{Centerline Radius of Elbow }(R)}{\text{Duct Diameter }(D)} R / D = Duct Diameter ( D ) Centerline Radius of Elbow ( R ) ​

Elbow Type & Construction R/D Ratio Loss Coeff. (Kelbow) Performance Characteristics

Mitered 90° Elbow (2-piece, sharp corner) < 1.0 0.75--1.30 Extreme flow separation, heavy erosion, high particulate impact. Unacceptable in LEV.

3-Piece Stamped/Segmented Elbow 1.0 0.35--0.45 Moderate turbulence. Used only where space is severely restricted.

5-Piece Segmented / Stamped Smooth Elbow 1.5 0.24 Standard industrial LEV specification. Excellent balance of low loss and compact size.

5-Piece / Smooth Die-Stamped Elbow 2.0 to 2.5 0.15--0.19 Optimal aerodynamic performance. Minimal turbulence and low wear.

Long Radius Sweep Elbow > 3.0 0.20--0.25 Diminishing aerodynamic returns; extra duct length adds friction that offsets curvature gain.

Exam Key Rule: The optimum economic and aerodynamic elbow design has an R/D ratio between 1.5 and 2.5 (R/D = 2.0 is the ideal target). Designing below R/D = 1.5 dramatically spikes energy loss, while designing above R/D = 2.5 adds unnecessary weight, space, and frictional surface area.

Branch Entry Junctions: Expanding Mains

When a branch duct merges into a main trunk duct:

Angle of Entry (heta): Branches must enter at an angle of 30° to 45° relative to the main duct axis (30° is ideal, Kbranch ≈ 0.15--0.18; 45° yields K ≈ 0.28). 90° T-junctions are strictly prohibited in particulate systems (K > 0.80, severe turbulence and dust fallout).

Expanded Main Transition: Downstream of the branch junction, the main duct diameter must be expanded so that the combined volumetric flow (Qmain = Q(branch 1) + Q(branch 2)) maintains the exact design transport velocity without creating excessive velocity or causing upstream choking. +-------------------------------------------------------------------------+

  • | BRANCH JUNCTION & EXPANDED MAIN DESIGN |
  • +-------------------------------------------------------------------------+
  • | |
  • | Branch Duct (Q1, D1) |
  • | \ |
  • | \ Angle theta = 30° to 45° |
  • | \ |
  • | Upstream Main (Q2, D2) \ Downstream Expanded Main (Q_total, D3)|
  • | -------------------------\ --------------------------------------- |
  • | \ Taper angle <= 30° |
  • | ===========================> ======================================> |
  • | -------------------------------------------------------------------- |
  • | * Q_total = Q1 + Q2 |
  • | * D3 is expanded to maintain minimum transport velocity at Q_total! |
  • +-------------------------------------------------------------------------+
  • 3. Duct System Balancing Methodologies

When multiple exhaust branches connect to a common main manifold leading to a single fan, the system will naturally self-equilibrate according to the laws of fluid resistance: air will distribute such that the total static pressure loss through each parallel branch path to the junction is exactly equal (SP(j,1) = SP(j,2)). If the system is designed incorrectly, branches with lower resistance will steal airflow from high-resistance branches, causing the high-resistance branches to drop below minimum transport velocity.

Industrial hygiene ventilation systems are balanced using one of two primary methods: +-------------------------------------------------------------------------+

  • | BALANCE BY DESIGN VS. BLAST GATE BALANCING |
  • +-------------------------------------------------------------------------+
  • | |
  • | 1. STATIC PRESSURE BALANCE METHOD ("Balance by Design"): |
  • | - Branch duct diameters and fitting geometries are precisely sized |
  • | during engineering design so pressure losses match at junctions. |
  • | - Target: |SP_branchA - SP_branchB| / min(SP) <= 0.05 (within 5%). |
  • | - Tamper-proof; no dampers or blast gates to clog or erode. |
  • | - Permanent, reliable, maintenance-free aerodynamic equilibrium. |
  • | |
  • | 2. BLAST GATE BALANCING METHOD: |
  • | - Branches are oversized, and adjustable sliding mechanical metal |
  • | plates (blast gates) are inserted into each branch line. |
  • | - Gates are manually adjusted during commissioning using Pitot tube.|
  • | - Vulnerabilities: |
  • | * Severe erosion from abrasive dust impacting the gate lip. |
  • | * Particulate damming: Dust piles up behind gate, causing clogs. |
  • | * Unauthorized operator tampering throws whole system off balance.|
  • +-------------------------------------------------------------------------+

Balancing Parameter Static Pressure Balance ("Balance by Design") Blast Gate Balancing Method

Design Principle Calculate branch losses; adjust duct diameters and flow rates to equalize junction SP within 5%. Install sliding gates; throttle flow manually in low-resistance branches.

Capital / Design Effort Requires detailed engineering calculations prior to fabrication. Fast, simple initial design; high field commissioning labor.

Reliability & Tamper Resistance 100% tamper-proof. Workers cannot alter system airflow distribution. Poor. Workers frequently adjust gates to clear odors, destabilizing the entire system.

Particulate Clogging Risk Zero. Smooth interior walls with no internal obstructions. High. Dust accumulates on the upstream side of throttled gate plates.

Abrasive Wear & Erosion Low. Smooth transitions minimize localized particulate impact. Severe. High-velocity dust blasting against gate edges rapidly erodes metal.

CIH Recommendation Strongly preferred standard for all toxic and particulate LEV. Restricted to clean air, non-abrasive, non-toxic, or flexible multi-use systems.

The 5% Static Pressure Balance Criterion

When calculating junction pressures in the Balance by Design method, two converging branches are considered balanced if their calculated branch static pressures at the junction (SPj) agree within 5% : ∣ S P j , Branch 1 − S P j , Branch 2 ∣ min ⁡ ( S P j , 1 , S P j , 2 ) ≤ 0.05 ( ≤ 5 % difference ) \mathbf{\frac{|SP_{j,\text{Branch 1}} - SP_{j,\text{Branch 2}}|}{\min(SP_{j,1}, SP_{j,2})} \le 0.05 \quad (\le 5\%\text{ difference})} min ( S P j , 1 ​ , S P j , 2 ​ ) ∣S P j , Branch 1 ​ − S P j , Branch 2 ​ ∣ ​ ≤ 0.05 ( ≤ 5% difference )

If the difference exceeds 5%, the branch with the lower resistance must be corrected by:

Decreasing its duct diameter (which increases velocity, velocity pressure, and friction loss).

Introducing an engineered restriction (e.g., adding an extra bend or slight length adjustment).

Increasing the design airflow through that branch until pressures match.

  • 4. Worked Step-by-Step Calculation Examples
  • Worked Example 9.2.1: Sizing Duct Diameter for Minimum Transport Velocity

Problem: A local exhaust hood captures dry silica grinding dust from an abrasive cut-off saw. The hood design requires a capture airflow of Q = 1350 cfm. Silica dust requires a minimum transport velocity of Vtr = 3800 fpm.

Calculate the theoretical maximum duct cross-sectional area (Ad) and round duct diameter (D).

Select the nearest standard commercial round duct diameter (available in 1-inch increments: 7 in, 8 in, 9 in) that guarantees velocity ≥ Vtr.

Calculate the actual operating duct velocity (Vactual) and velocity pressure (VPd) with the selected duct size.

Solution Steps:

Calculate theoretical duct area and diameter: A d = Q V t r = 1350 cfm 3800 fpm = 0.3553 ft 2 A_d = \frac{Q}{V_{tr}} = \frac{1350\text{ cfm}}{3800\text{ fpm}} = 0.3553\text{ ft}^2 A d ​ = V t r ​ Q ​ = 3800 fpm 1350 cfm ​ = 0.3553 ft 2 D = 4 ⋅ A d π × 12 = 4 × 0.3553 3.14159 × 12 = 0.4524 × 12 = 0.6726 × 12 = 8.07 inches D = \sqrt{\frac{4 \cdot A_d}{\pi}} \times 12 = \sqrt{\frac{4 \times 0.3553}{3.14159}} \times 12 = \sqrt{0.4524} \times 12 = 0.6726 \times 12 = 8.07\text{ inches} D = π 4 ⋅ A d ​ ​ ​ × 12 = 3.14159 4 × 0.3553 ​ ​ × 12 = 0.4524 ​ × 12 = 0.6726 × 12 = 8.07 inches

Evaluate standard commercial duct sizes:

Option A: 9-inch duct (D = 9 in = 0.75 ft): A 9 = π ⋅ ( 0.75 ) 2 4 = 0.4418 ft 2 ⟹ V = 1350 0.4418 = 3056 fpm A_9 = \frac{\pi \cdot (0.75)^2}{4} = 0.4418\text{ ft}^2 \implies V = \frac{1350}{0.4418} = 3056\text{ fpm} A 9 ​ = 4 π ⋅ ( 0.75 ) 2 ​ = 0.4418 ft 2 ⟹ V = 0.4418 1350 ​ = 3056 fpm Evaluation: 3056 fpm < 3800 fpm — UNACCEPTABLE. Silica dust will settle and plug the duct!

Option B: 8-inch duct (D = 8 in = 0.6667 ft): A 8 = π ⋅ ( 0.6667 ) 2 4 = 0.3491 ft 2 ⟹ V = 1350 0.3491 = 3867 fpm A_8 = \frac{\pi \cdot (0.6667)^2}{4} = 0.3491\text{ ft}^2 \implies V = \frac{1350}{0.3491} = 3867\text{ fpm} A 8 ​ = 4 π ⋅ ( 0.6667 ) 2 ​ = 0.3491 ft 2 ⟹ V = 0.3491 1350 ​ = 3867 fpm Evaluation: 3867 fpm > 3800 fpm — PERFECT. Meets transport velocity criterion.

Calculate actual operating parameters for 8-inch duct: V actual = 3867 fpm V_{\text{actual}} = 3867\text{ fpm} V actual ​ = 3867 fpm V P d = ( V actual 4005 ) 2 = ( 3867 4005 ) 2 = ( 0.9655 ) 2 = 0.9322 in. w.g. VP_d = \left(\frac{V_{\text{actual}}}{4005}\right)^2 = \left(\frac{3867}{4005}\right)^2 = (0.9655)^2 = 0.9322\text{ in. w.g.} V P d ​ = ( 4005 V actual ​ ​ ) 2 = ( 4005 3867 ​ ) 2 = ( 0.9655 ) 2 = 0.9322 in. w.g.

Result: An 8-inch diameter duct must be selected, establishing an actual transport velocity of 3867 fpm (VPd = 0.932 in. w.g.).

Worked Example 9.2.2: Total Pressure Loss Across a Duct Branch Run

Problem: An LEV branch carrying Q = 1200 cfm of air laden with limestone dust through a 7.5-inch diameter round duct (Ad = 0.3068 ft², Vd = 3911 fpm, VPd = 0.9536 in. w.g.) comprises the following components:

  • Tapered intake hood (Fh = 0.15)
  • 60 feet of straight galvanized duct (friction loss rate from ACGIH chart = 2.80 in. w.g. / 100 ft)
  • Two 90° stamped elbows (R/D = 2.0, Kelbow = 0.19 each)
  • One 30° branch entry fitting into the main (Kbranch = 0.18)

Calculate the total static pressure required at the branch junction (SPjunction).

Solution Steps:

Calculate Hood Static Pressure (SPh): h e = F h × V P d = 0.15 × 0.9536 = 0.1430 in. w.g. h_e = F_h \times VP_d = 0.15 \times 0.9536 = 0.1430\text{ in. w.g.} h e ​ = F h ​ × V P d ​ = 0.15 × 0.9536 = 0.1430 in. w.g. ∣ S P h ∣ = V P d + h e = 0.9536 + 0.1430 = 1.0966 in. w.g. |SP_h| = VP_d + h_e = 0.9536 + 0.1430 = 1.0966\text{ in. w.g.} ∣ S P h ​ ∣ = V P d ​ + h e ​ = 0.9536 + 0.1430 = 1.0966 in. w.g.

Calculate Straight Duct Friction Loss (hfriction): h friction = ( 2.80 in. w.g. 100 ft ) × 60 ft = 1.6800 in. w.g. h_{\text{friction}} = \left(\frac{2.80\text{ in. w.g.}}{100\text{ ft}}\right) \times 60\text{ ft} = 1.6800\text{ in. w.g.} h friction ​ = ( 100 ft 2.80 in. w.g. ​ ) × 60 ft = 1.6800 in. w.g.

Calculate Dynamic Fitting Losses (helbows + hbranch): h elbows = 2 × ( K elbow × V P d ) = 2 × ( 0.19 × 0.9536 ) = 2 × 0.1812 = 0.3624 in. w.g. h_{\text{elbows}} = 2 \times (K_{\text{elbow}} \times VP_d) = 2 \times (0.19 \times 0.9536) = 2 \times 0.1812 = 0.3624\text{ in. w.g.} h elbows ​ = 2 × ( K elbow ​ × V P d ​ ) = 2 × ( 0.19 × 0.9536 ) = 2 × 0.1812 = 0.3624 in. w.g. h branch = K branch × V P d = 0.18 × 0.9536 = 0.1716 in. w.g. h_{\text{branch}} = K_{\text{branch}} \times VP_d = 0.18 \times 0.9536 = 0.1716\text{ in. w.g.} h branch ​ = K branch ​ × V P d ​ = 0.18 × 0.9536 = 0.1716 in. w.g. h fittings, total = 0.3624 + 0.1716 = 0.5340 in. w.g. h_{\text{fittings, total}} = 0.3624 + 0.1716 = 0.5340\text{ in. w.g.} h fittings, total ​ = 0.3624 + 0.1716 = 0.5340 in. w.g.

Calculate Total Branch Static Pressure at Junction (|SPj|): ∣ S P j ∣ = ∣ S P h ∣ + h friction + h fittings, total |SP_j| = |SP_h| + h_{\text{friction}} + h_{\text{fittings, total}} ∣ S P j ​ ∣ = ∣ S P h ​ ∣ + h friction ​ + h fittings, total ​ ∣ S P j ∣ = 1.0966 + 1.6800 + 0.5340 = 3.3106 in. w.g. ⟹ S P j = − 3.31 in. w.g. |SP_j| = 1.0966 + 1.6800 + 0.5340 = 3.3106\text{ in. w.g.}\implies SP_j = -3.31\text{ in. w.g.} ∣ S P j ​ ∣ = 1.0966 + 1.6800 + 0.5340 = 3.3106 in. w.g. ⟹ S P j ​ = − 3.31 in. w.g.

Result: The total suction static pressure required at the junction to pull the design airflow through this branch is -3.31 in. w.g.

Worked Example 9.2.3: Static Pressure Balance by Design at a Junction

Problem: Two LEV branches merge at Junction J:

Branch 1 (Lead oxide hood): Design flow Q1 = 800 cfm. Sized with a 6-inch duct (V1 = 4074 fpm). Calculated static pressure at the junction is SP(j,1) = -3.45 in. w.g.

Branch 2 (Solder pot hood): Design flow Q2 = 1100 cfm. Initial layout calculation with an 8-inch duct (V2 = 3151 fpm) yields a calculated junction static pressure of SP(j,2) = -2.80 in. w.g.

Evaluate whether the system meets the 5% Balance by Design criterion.

If unbalanced, calculate the actual airflow that would be pulled through Branch 2 if fabricated as initially sized.

Propose the engineering redesign required to balance the junction without blast gates.

Solution Steps:

Check 5% Balance Criterion: Δ S P = ∣ S P j , 1 − S P j , 2 ∣ min ⁡ ( S P j , 1 , S P j , 2 ) = ∣ 3.45 − 2.80 ∣ 2.80 = 0.65 2.80 = 0.2321 ( 23.2 % > 5 % ) \Delta SP = \frac{|SP_{j,1} - SP_{j,2}|}{\min(SP_{j,1}, SP_{j,2})} = \frac{|3.45 - 2.80|}{2.80} = \frac{0.65}{2.80} = 0.2321 \quad (23.2\% > 5\%) Δ SP = min ( S P j , 1 ​ , S P j , 2 ​ ) ∣ S P j , 1 ​ − S P j , 2 ​ ∣ ​ = 2.80 ∣3.45 − 2.80∣ ​ = 2.80 0.65 ​ = 0.2321 ( 23.2% > 5% )

Status: UNBALANCED. Branch 2 has significantly lower resistance than Branch 1.

Calculate actual self-equilibrating airflow in Branch 2: Because the system will naturally balance to the higher static pressure (-3.45 in. w.g.), Branch 2 will draw excess air: Q actual, 2 = Q design, 2 × S P j , 1 S P j , 2 = 1100 cfm × 3.45 2.80 = 1100 × 1.2321 = 1100 × 1.110 = 1221 cfm Q_{\text{actual, 2}} = Q_{\text{design, 2}} \times \sqrt{\frac{SP_{j,1}}{SP_{j,2}}} = 1100\text{ cfm} \times \sqrt{\frac{3.45}{2.80}} = 1100 \times \sqrt{1.2321} = 1100 \times 1.110 = 1221\text{ cfm} Q actual, 2 ​ = Q design, 2 ​ × S P j , 2 ​ S P j , 1 ​ ​ ​ = 1100 cfm × 2.80 3.45 ​ ​ = 1100 × 1.2321 ​ = 1100 × 1.110 = 1221 cfm

Consequence: Branch 2 draws 1221 cfm instead of 1100 cfm, which steals capacity from the main fan and may cause Branch 1 to drop below its required transport velocity!

Engineering Redesign for Static Pressure Balance:

Redesign Branch 2 using a 7-inch duct instead of an 8-inch duct (A7 = 0.2673 ft², V = 1100 / 0.2673 = 4115 fpm).

Recalculating friction and fitting losses in Branch 2 with the 7-inch duct increases its junction loss to SP(j,2)' = -3.42 in. w.g.

Re-evaluating balance: Δ SP' = (|3.45 - 3.42|)/3.42 = 0.03/3.42 = 0.0088 = 0.88% ≤ 5%.

Result: Resizing Branch 2 to a 7-inch duct establishes aerodynamic balance within 0.88% , ensuring stable design airflow through both hoods without blast gates.