10.7 System Curves, the Fan Laws, and Density Corrections

CIH Certified Industrial Hygienist Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: The CIH Exam and How to Use This Guide

1.1 CIH Exam Format, Scoring, and Test-Day Logistics 1.2 Eligibility, Application Windows, Fees, and Certification Maintenance 1.3 The BGC Blueprint, Subject Areas, and a Calculation-First Study Plan

2 Chapter 2: Basic Science & Calculations

2.1 Gas Laws and Vapor Calculations 2.2 Unit Conversions: ppm, mg/m³, and Standard Temperature/Pressure 2.3 Fluid Mechanics and Airflow Fundamentals

3 Chapter 3: Air Sampling & Instrumentation

3.1 Active and Passive Air Sampling Strategies 3.2 Particulate and Aerosol Sampling 3.3 Direct-Reading Instruments and Calibration

4 Chapter 4: Analytical Chemistry & Lab Methods

4.1 Gas Chromatography and Mass Spectrometry 4.2 High-Performance Liquid Chromatography and Ion Chromatography 4.3 Spectroscopy and Elemental Analysis 4.4 Gravimetric, Microscopy, and Wet Chemical Methods 4.5 Laboratory Quality Assurance, Chain of Custody, and Desorption Efficiency

5 Chapter 5: Biostatistics & Epidemiology

5.1 Lognormal Distributions and Exposure Data Statistics 5.2 Upper Confidence Limits (UCL95) and Compliance Decision Rules 5.3 Epidemiological Study Designs and Measures of Association 5.4 Sampling Strategy: Sample Size, Power, and Worker Selection

6 Chapter 6: Toxicology & Biological Monitoring

6.1 Dose-Response Relationships and Points of Departure 6.2 Toxicokinetics: Absorption, Distribution, Metabolism, and Elimination 6.3 Aerosol Deposition, Clearance, and Respiratory Tract Dosimetry 6.4 Hepatic, Renal, Neurologic, and Hematologic Target Organ Toxicity 6.5 Pulmonary Toxicology, Carcinogenicity, and Reproductive Hazards 6.6 OEL Frameworks, Classifications, and Excursion Limits 6.7 Chemical Mixtures and Extended Work-Shift OEL Adjustments 6.8 Biological Exposure Indices (BEIs) and Biomonitoring

7 Chapter 7: Biohazards & Indoor Environmental Quality

7.1 Mold, Fungi, and Microbial Contaminants 7.2 Infectious Agents, Bloodborne Pathogens, and Biosafety Levels 7.3 Indoor Environmental Quality (IEQ) Investigations 7.4 Sanitation, Potable Water, and Personal Hygiene Programs

8 Chapter 8: Community Exposure & Environmental Health

8.1 Clean Air Act Framework, NAAQS, and New Source Review 8.2 Hazardous Air Pollutants, CEMS, and EPA Reference Methods 8.3 Atmospheric Stability, Lapse Rates, and Plume Morphology 8.4 Gaussian Plume Modeling, Plume Rise, and Environmental Fate 8.5 HAZWOPER Scope, Mandates, and Training Tiers 8.6 Protection Levels, Site Zoning, Incident Command, and Decontamination 8.7 Water Pollution, Hazardous Waste, and Community Right-to-Know

9 Chapter 9: Health Risk Analysis & Hazard Communication

9.1 GHS Hazard Classification: Health and Physical Hazard Criteria 9.2 GHS Labels, Safety Data Sheets, and Trade Secret Rules 9.3 The AIHA Exposure Assessment Strategy and Similar Exposure Groups 9.4 Qualitative Exposure Profiling and the AIHA Risk Matrix 9.5 Quantitative Health Risk Characterization: HQ, HI, and ELCR 9.6 NIOSH Occupational Exposure Banding 9.7 Risk Communication and Reporting to Affected Parties

10 Chapter 10: Industrial Ventilation Principles & LEV Design

10.1 Elimination, Substitution, Isolation, Containment, and Process Change 10.2 LEV Hood Taxonomy and Capture Velocity Selection 10.3 Hood Airflow Equations, Entry Losses, and Hood Static Pressure 10.4 Particulate Transport Aerodynamics and Duct Sizing 10.5 Duct Friction, Fitting Losses, and System Balancing 10.6 Fan Categories and Pressure Dynamics Across the Fan 10.7 System Curves, the Fan Laws, and Density Corrections

11 Chapter 11: General Ventilation, Air Cleaning & Diagnostics

11.1 Dilution Ventilation Principles and Steady-State Modeling 11.2 Transient Purging and Air Distribution Geometry 11.3 Particulate Air Cleaning: Cyclones, Baghouses, Scrubbers, and ESPs 11.4 Gaseous Emission Control and Air Cleaner Selection 11.5 Ventilation System Troubleshooting and Testing

12 Chapter 12: Noise Measurement & Hearing Conservation

12.1 Acoustic Physics and Decibel Mathematics 12.2 Sound Propagation, Octave Bands, and Frequency Weighting 12.3 Noise Dose Metrics and OSHA versus ACGIH Criteria 12.4 Exchange Rates, Extended Shifts, and Dosimetry Field Protocols 12.5 Engineering Noise Controls and Hearing Protector Attenuation 12.6 Hearing Conservation Programs and Standard Threshold Shifts 12.7 Hand-Arm and Whole-Body Vibration

13 Chapter 13: Thermal Stress Assessment & Control

13.1 Wet Bulb Globe Temperature (WBGT) and Heat Stress Indices 13.2 Heat-Related Disorders, Acclimatization, and Work/Rest Regimens 13.3 Cold Stress Evaluation and Wind Chill

14 Chapter 14: Ionizing Radiation Protection

14.1 Ionizing Radiation Physics and Radioactive Decay Kinetics 14.2 Radiation Units, Radiobiology, and Health Effects 14.3 ALARA, Stay-Time, and the Inverse Square Law 14.4 Shielding Physics, Material Selection, and Gamma Constants 14.5 Radiation Detection Instruments and Spectrometry 14.6 Personnel Dosimetry, Dose Limits, and Contamination Surveys

15 Chapter 15: Non-Ionizing Radiation & Laser Safety

15.1 The Non-Ionizing Spectrum and Static/ELF Field Exposures 15.2 Radiofrequency and Microwave Exposure: SAR, Standards, and Surveys 15.3 Ultraviolet, Visible, and Infrared Radiation Hazards 15.4 Laser Safety Classifications and Optical Density Calculations 15.5 Illumination, Lighting Design, and Visual Performance

16 Chapter 16: Non-Engineering Controls & Personal Protective Equipment

16.1 Respiratory Protection Programs and Assigned Protection Factors 16.2 Maximum Use Concentration, Oxygen Deficiency, and Breathing Air 16.3 Particulate Filters, Sorbent Cartridges, and Change Schedules 16.4 Respirator Fit Testing Protocols 16.5 Chemical Protective Clothing and Dermal Exposure Control

17 Chapter 17: Ergonomics & Workstation Design

17.1 Soft-Tissue Biomechanics and WMSD Pathophysiology 17.2 Ergonomic Risk Factors and Their Interaction Effects 17.3 The Revised NIOSH Lifting Equation 17.4 RULA, REBA, the Strain Index, and the ACGIH HAL TLV 17.5 Anthropometry and Workstation Geometry 17.6 VDT Workstations, Hand Tool Design, and Administrative Ergonomics

18 Chapter 18: Work Environments & Industrial Processes

18.1 Welding Fume Emissions, Metal Fume Fever, and Cr(VI)/Manganese Toxicology 18.2 Foundry Operations and Hot Work Fire Prevention 18.3 Vapor Degreasing, Pickling, Electroplating, and Cyanide Baths 18.4 Spray Coatings, Isocyanates, and Semiconductor Manufacturing 18.5 Confined Spaces and High-Hazard Industrial Operations 18.6 Asbestos, Lead, and Silica: Regulated Substance Programs 18.7 Abrasive Blasting and Surface Preparation

19 Chapter 19: IH Program Management & Professional Ethics

19.1 The BGC Code of Ethics: Canons and Enforcement 19.2 Professional Liability, Standard of Care, and Expert Testimony 19.3 Occupational Health & Safety Management Systems (ISO 45001, ANSI Z10) 19.4 Exposure Records Access and Medical Surveillance 19.5 OSHA Injury and Illness Recordkeeping and Enforcement

10.7 System Curves, the Fan Laws, and Density Corrections

Key Takeaways Explain This Topic AI

The system resistance curve is parabolic — pressure loss varies with the square of flow — and the operating point is where it intersects the fan curve.

The fan laws at constant density and diameter: flow varies directly with speed, pressure with the square of speed, and power with the cube of speed, so a 10% speed increase raises power by about 33%.

Fan laws apply to the fan, not to the contaminant: raising fan speed raises flow but does not change the system resistance curve.

Fans are constant-volume devices: a fan moves the same cfm regardless of air density, but the pressure it develops and the power it draws vary directly with density, so hot or high-altitude air reduces both.

Last updated: August 2026

System Curves, the Fan Laws, and Density Corrections

Once the fan type is chosen, three questions decide whether the installation works: where the fan curve crosses the system resistance curve, what happens to flow and power when speed changes, and how non-standard air density distorts both.

  • 1. System Characteristic Resistance Curves & Operating Point
  • The System Characteristic Parabolic Curve

In any duct system, total pressure loss is dominated by turbulent fluid friction and dynamic fitting losses, which scale with the square of volumetric flow rate (Q²): S P system = k × Q 2 \mathbf{SP_{\text{system}} = k \times Q^2} S P system ​ = k × Q 2

Where k is the system resistance coefficient determined by duct diameter, length, elbow count, hood entry losses, and air cleaner resistance.

The Fan Operating Point

A fan manufacturer provides a Fan Characteristic Curve plotting developed static pressure (SP) versus airflow (Q) at a constant rotational speed (RPM). When the System Resistance Curve is plotted on the same axes, the intersection defines the Fan Operating Point : +-------------------------------------------------------------------------+

  • | FAN CURVE & SYSTEM OPERATING POINT |
  • +-------------------------------------------------------------------------+
  • | Static Pressure (in. w.g.) |
  • | ^ |
  • | | FAN PERFORMANCE CURVE (Constant RPM) |
  • | | *'''--. |
  • | | '--. System Curve 2 (Plugged Duct / Dirty Filters) |
  • | SP2|------------------*--. / |
  • | | /| '--. / System Curve 1 (Clean / Design) |
  • | SP1|----------------/-+-------*--. / |
  • | | / | /| '--/ |
  • | | / | / | |
  • | 0 +-------------+----+----+--+-------------------------------------> |
  • | 0 Q2 Q1 Airflow Q (cfm) |
  • +-------------------------------------------------------------------------+
  • System Dynamics and Deviations

Duct Plugging or Loaded Air Filters: Increases the system resistance coefficient (k2 > k1), steepening the parabolic system curve. The operating point shifts up and to the left, resulting in lower airflow (Q2 < Q1) and higher static pressure (SP2 > SP1) .

Drive Belt Slippage or Speed Reduction: Shifts the entire fan characteristic curve downward, reducing both delivered airflow and developed static pressure.

2. The Three Fundamental Fan Laws

The Fan Laws are mathematical similitude relationships governing changes in fan rotational speed (RPM), impeller diameter (D), and fluid density (ρ). For a fixed ventilation duct system and fixed fan size (D1 = D2), changing the fan rotational speed modulates flow, pressure, and power according to three exact laws: +-------------------------------------------------------------------------+

  • | THE THREE FUNDAMENTAL FAN LAWS |
  • +-------------------------------------------------------------------------+
  • | |
  • | FAN LAW 1 (Airflow is Linear): |
  • | Q2 = Q1 * (RPM2 / RPM1) |
  • | * Increasing RPM by 10% increases volumetric airflow by 10%. |
  • | |
  • | FAN LAW 2 (Pressure is Quadratic): |
  • | SP2 = SP1 * (RPM2 / RPM1)^2 |
  • | * Increasing RPM by 10% increases static pressure by 21% (1.10^2). |
  • | |
  • | FAN LAW 3 (Brake Horsepower is Cubic): |
  • | BHP2 = BHP1 * (RPM2 / RPM1)^3 |
  • | * Increasing RPM by 10% increases required power by 33.1% (1.10^3)! |
  • | * Increasing RPM by 50% increases power by 237.5% (1.50^3 = 3.375x)!|
  • +-------------------------------------------------------------------------+

Exam Critical Warning: Fan Law 3 is the most common mathematical trap on the CIH exam. Because brake horsepower scales with the cube of the speed ratio ([RPM2 / RPM1]³), attempting to solve an LEV airflow deficiency by simply speeding up the fan sheave will dramatically overload and burn out the electric motor unless the motor horsepower is upsized accordingly!

  • 3. Brake Horsepower (BHP) and Mechanical Efficiency
  • Air Horsepower (AHP)

Air Horsepower is the theoretical fluid aerodynamic power required to move a given volume of air against a specified total or static pressure drop: A H P = Q × F T P 6356 or A H P static = Q × F S P 6356 \mathbf{AHP = \frac{Q \times FTP}{6356} \quad \text{or} \quad AHP_{\text{static}} = \frac{Q \times FSP}{6356}} AHP = 6356 Q × FTP ​ or AH P static ​ = 6356 Q × FSP ​

(where Q is in cfm, FTP and FSP are in in. w.g., and 6356 is the imperial conversion factor derived from 33,000 ft·lbf/min / [5.1922 lbf/ft² / in. w.g.]) .

Brake Horsepower (BHP)

Brake Horsepower (BHP) is the actual mechanical shaft power that must be delivered to the fan shaft by the motor, incorporating the fan's mechanical efficiency (η): B H P = Q × F T P 6356 × η total = Q × F S P 6356 × η static \mathbf{BHP = \frac{Q \times FTP}{6356 \times \eta_{\text{total}}} = \frac{Q \times FSP}{6356 \times \eta_{\text{static}}}} BHP = 6356 × η total ​ Q × FTP ​ = 6356 × η static ​ Q × FSP ​

Motor Electrical Input Horsepower (MHP)

To determine the actual electrical motor rating required, mechanical drive transmission losses (V-belts, ηdrive ≈ 0.90--0.95) and electric motor electrical efficiency (ηmotor ≈ 0.85--0.95) must be incorporated: M H P = B H P η drive × η motor MHP = \frac{BHP}{\eta_{\text{drive}} \times \eta_{\text{motor}}} M H P = η drive ​ × η motor ​ B H P ​

  • 4. Non-Standard Air Density Corrections
  • Standard Air Properties

Fan catalog rating tables are published based on Standard Air Density :

ρ0 = 0.075 lb/ft³ at standard sea level temperature of 70°F (530°R) and barometric pressure of 29.92 in. Hg (760 mmHg) .

Air Density Correction Factor (d)

When an LEV system operates at elevated temperatures (e.g., furnace exhaust at 300°F) or high elevations (e.g., Denver, CO at 5,280 ft where PB ≈ 24.8 in. Hg), the actual air density (ρactual) decreases. The dimensionless Density Correction Factor (d) is: d = ρ actual ρ 0 = ( 530 460 + T ( ∘ F ) ) × ( P B ( in. Hg ) 29.92 ) d = \frac{\rho_{\text{actual}}}{\rho_0} = \left(\frac{530}{460 + T(^\circ\text{F})}\right) \times \left(\frac{P_B(\text{in. Hg})}{29.92}\right) d = ρ 0 ​ ρ actual ​ ​ = ( 460 + T ( ∘ F ) 530 ​ ) × ( 29.92 P B ​ ( in. Hg ) ​ )

Aerodynamic Principles of Density Shifts

A fan is a constant volumetric displacement machine. At a given RPM, an industrial fan will move the exact same volumetric flow rate (Q, in cfm) regardless of air density!

Developed pressure and required shaft power are directly proportional to air density (d): S P actual = S P standard × d SP_{\text{actual}} = SP_{\text{standard}} \times d S P actual ​ = S P standard ​ × d B H P actual = B H P standard × d BHP_{\text{actual}} = BHP_{\text{standard}} \times d B H P actual ​ = B H P standard ​ × d

Cold Startup Power Hazard

When designing an LEV system for a hot process (e.g., 400°F, where d ≈ 0.61), the fan requires much less power during steady-state hot operation (BHPhot = BHPstd × 0.61).

However, during morning cold startup when the system contains dense ambient air (70°F, d = 1.0), the fan will demand 1 / 0.61 = 1.64 times more power . If the electric motor was sized solely for the hot operating condition, the motor will trip thermal overloads or burn out during startup unless throttled by an inlet damper!

  • 5. Worked Step-by-Step Calculation Examples
  • Worked Example 9.3.1: Applying the Fan Laws to a Speed Increase

Problem: An existing industrial exhaust fan operates at a rotational speed of 1200 RPM, delivering a volumetric flow rate Q1 = 6000 cfm against a static pressure SP1 = 4.0 in. w.g. while consuming BHP1 = 6.0 hp of shaft power.

To accommodate a new welding booth, the airflow must be increased by 25% to Q2 = 7500 cfm.

Calculate the required new fan rotational speed (RPM2).

Calculate the resulting new system static pressure (SP2).

Calculate the required new Brake Horsepower (BHP2).

Determine the percentage increase in motor horsepower required.

Solution Steps:

Calculate new speed (RPM2) using Fan Law 1 (Q2 = Q1 [RPM2 / RPM1]): R P M 2 R P M 1 = Q 2 Q 1 = 7500 cfm 6000 cfm = 1.25 \frac{RPM_2}{RPM_1} = \frac{Q_2}{Q_1} = \frac{7500\text{ cfm}}{6000\text{ cfm}} = 1.25 RP M 1 ​ RP M 2 ​ ​ = Q 1 ​ Q 2 ​ ​ = 6000 cfm 7500 cfm ​ = 1.25 R P M 2 = 1200 RPM × 1.25 = 1500 RPM RPM_2 = 1200\text{ RPM} \times 1.25 = 1500\text{ RPM} RP M 2 ​ = 1200 RPM × 1.25 = 1500 RPM

Calculate new static pressure (SP2) using Fan Law 2 (SP2 = SP1 [RPM2 / RPM1]²): S P 2 = 4.0 in. w.g. × ( 1.25 ) 2 = 4.0 × 1.5625 = 6.25 in. w.g. SP_2 = 4.0\text{ in. w.g.} \times (1.25)^2 = 4.0 \times 1.5625 = 6.25\text{ in. w.g.} S P 2 ​ = 4.0 in. w.g. × ( 1.25 ) 2 = 4.0 × 1.5625 = 6.25 in. w.g.

Calculate new Brake Horsepower (BHP2) using Fan Law 3 (BHP2 = BHP1 [RPM2 / RPM1]³): B H P 2 = 6.0 hp × ( 1.25 ) 3 = 6.0 × 1.953125 = 11.72 hp BHP_2 = 6.0\text{ hp} \times (1.25)^3 = 6.0 \times 1.953125 = 11.72\text{ hp} B H P 2 ​ = 6.0 hp × ( 1.25 ) 3 = 6.0 × 1.953125 = 11.72 hp

Calculate percentage power increase: Δ % = 11.72 − 6.0 6.0 × 100 = 95.33 % \Delta \% = \frac{11.72 - 6.0}{6.0} \times 100 = 95.33\% Δ% = 6.0 11.72 − 6.0 ​ × 100 = 95.33%

Result: Increasing airflow by 25% requires running the fan at 1500 RPM , increases static pressure to 6.25 in. w.g. , and nearly doubles required power to 11.72 hp (+95.3%), requiring the existing motor to be replaced with a standard 15 hp motor.

Worked Example 9.3.2: Calculating Brake Horsepower and Electrical Operating Power

Problem: A backward-inclined centrifugal exhaust fan delivers Q = 8500 cfm against a Fan Total Pressure FTP = 5.5 in. w.g. Standard air conditions apply. The fan has a total mechanical efficiency ηtotal = 78% (0.78), the V-belt drive efficiency is ηdrive = 92% (0.92), and the motor electrical efficiency is ηmotor = 90% (0.90).

Calculate the Air Horsepower (AHP).

Calculate the required fan shaft Brake Horsepower (BHP).

Calculate the total electrical input motor power (MHP) and select the appropriate standard NEMA motor size (10 hp, 15 hp, 20 hp).

Solution Steps:

Calculate Air Horsepower (AHP): A H P = Q × F T P 6356 = 8500 cfm × 5.5 in. w.g. 6356 = 46750 6356 = 7.355 hp AHP = \frac{Q \times FTP}{6356} = \frac{8500\text{ cfm} \times 5.5\text{ in. w.g.}}{6356} = \frac{46750}{6356} = 7.355\text{ hp} A H P = 6356 Q × FTP ​ = 6356 8500 cfm × 5.5 in. w.g. ​ = 6356 46750 ​ = 7.355 hp

Calculate Brake Horsepower (BHP): B H P = A H P η total = 7.355 hp 0.78 = 9.429 hp ≈ 9.43 hp BHP = \frac{AHP}{\eta_{\text{total}}} = \frac{7.355\text{ hp}}{0.78} = 9.429\text{ hp} \approx 9.43\text{ hp} B H P = η total ​ A H P ​ = 0.78 7.355 hp ​ = 9.429 hp ≈ 9.43 hp

Calculate total electrical motor horsepower (MHP): M H P = B H P η drive × η motor = 9.429 0.92 × 0.90 = 9.429 0.828 = 11.388 hp MHP = \frac{BHP}{\eta_{\text{drive}} \times \eta_{\text{motor}}} = \frac{9.429}{0.92 \times 0.90} = \frac{9.429}{0.828} = 11.388\text{ hp} M H P = η drive ​ × η motor ​ B H P ​ = 0.92 × 0.90 9.429 ​ = 0.828 9.429 ​ = 11.388 hp

NEMA Motor Selection: A 10 hp motor is undersized (11.39 hp > 10 hp). The next standard NEMA commercial motor rating is 15 hp .

Result: The aerodynamic Air Horsepower is 7.36 hp , required shaft Brake Horsepower is 9.43 hp , and a 15 hp standard motor is required.

Worked Example 9.3.3: High-Temperature and Elevation Air Density Corrections

Problem: A hot flue gas LEV system exhausts gas at T = 300°F from an industrial smelter located at an elevation of 5000 ft (barometric pressure PB = 24.9 in. Hg). The required actual operating volumetric flow is Q = 10,000 cfm against an actual operating static pressure of SPactual = 4.5 in. w.g.

Calculate the density correction factor (d).

Determine the equivalent standard static pressure (SPstd) required to select the fan from a manufacturer's standard air catalog.

If the catalog specifies BHPstd = 16.8 hp at standard conditions, calculate the actual operating horsepower (BHPhot) and the cold startup horsepower (BHPcold at 70°F and 5000 ft).

Solution Steps:

Calculate Density Correction Factor (d): d = ( 530 460 + 300 ) × ( 24.9 in. Hg 29.92 in. Hg ) = ( 530 760 ) × 0.83222 = 0.69737 × 0.83222 = 0.5803 d = \left(\frac{530}{460 + 300}\right) \times \left(\frac{24.9\text{ in. Hg}}{29.92\text{ in. Hg}}\right) = \left(\frac{530}{760}\right) \times 0.83222 = 0.69737 \times 0.83222 = 0.5803 d = ( 460 + 300 530 ​ ) × ( 29.92 in. Hg 24.9 in. Hg ​ ) = ( 760 530 ​ ) × 0.83222 = 0.69737 × 0.83222 = 0.5803

Calculate Catalog Equivalent Static Pressure (SPstd): S P std = S P actual d = 4.5 in. w.g. 0.5803 = 7.755 in. w.g. ≈ 7.76 in. w.g. SP_{\text{std}} = \frac{SP_{\text{actual}}}{d} = \frac{4.5\text{ in. w.g.}}{0.5803} = 7.755\text{ in. w.g.} \approx 7.76\text{ in. w.g.} S P std ​ = d S P actual ​ ​ = 0.5803 4.5 in. w.g. ​ = 7.755 in. w.g. ≈ 7.76 in. w.g.

(The fan is selected from the catalog to deliver 10,000 cfm at 7.76 in. w.g.)

Calculate Operating Power and Cold Startup Power:

Operating Hot Power (BHPhot): B H P hot = B H P std × d = 16.8 hp × 0.5803 = 9.749 hp ≈ 9.75 hp BHP_{\text{hot}} = BHP_{\text{std}} \times d = 16.8\text{ hp} \times 0.5803 = 9.749\text{ hp} \approx 9.75\text{ hp} B H P hot ​ = B H P std ​ × d = 16.8 hp × 0.5803 = 9.749 hp ≈ 9.75 hp

Cold Startup Power (BHPcold at 70°F, 5000 ft): d cold = ( 530 460 + 70 ) × ( 24.9 29.92 ) = 1.00 × 0.83222 = 0.8322 d_{\text{cold}} = \left(\frac{530}{460 + 70}\right) \times \left(\frac{24.9}{29.92}\right) = 1.00 \times 0.83222 = 0.8322 d cold ​ = ( 460 + 70 530 ​ ) × ( 29.92 24.9 ​ ) = 1.00 × 0.83222 = 0.8322 B H P cold = B H P std × d cold = 16.8 hp × 0.8322 = 13.98 hp BHP_{\text{cold}} = BHP_{\text{std}} \times d_{\text{cold}} = 16.8\text{ hp} \times 0.8322 = 13.98\text{ hp} B H P cold ​ = B H P std ​ × d cold ​ = 16.8 hp × 0.8322 = 13.98 hp

Result: The density factor is 0.580 . While the fan only draws 9.75 hp during normal hot operations, it will draw 13.98 hp during a cold morning startup . A 15 hp motor must be installed to prevent tripping on cold startup.