Study guide
10.3 Hood Airflow Equations, Entry Losses, and Hood Static Pressure
CIH Certified Industrial Hygienist Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: The CIH Exam and How to Use This Guide
1.1 CIH Exam Format, Scoring, and Test-Day Logistics 1.2 Eligibility, Application Windows, Fees, and Certification Maintenance 1.3 The BGC Blueprint, Subject Areas, and a Calculation-First Study Plan
2 Chapter 2: Basic Science & Calculations
2.1 Gas Laws and Vapor Calculations 2.2 Unit Conversions: ppm, mg/m³, and Standard Temperature/Pressure 2.3 Fluid Mechanics and Airflow Fundamentals
3 Chapter 3: Air Sampling & Instrumentation
3.1 Active and Passive Air Sampling Strategies 3.2 Particulate and Aerosol Sampling 3.3 Direct-Reading Instruments and Calibration
4 Chapter 4: Analytical Chemistry & Lab Methods
4.1 Gas Chromatography and Mass Spectrometry 4.2 High-Performance Liquid Chromatography and Ion Chromatography 4.3 Spectroscopy and Elemental Analysis 4.4 Gravimetric, Microscopy, and Wet Chemical Methods 4.5 Laboratory Quality Assurance, Chain of Custody, and Desorption Efficiency
5 Chapter 5: Biostatistics & Epidemiology
5.1 Lognormal Distributions and Exposure Data Statistics 5.2 Upper Confidence Limits (UCL95) and Compliance Decision Rules 5.3 Epidemiological Study Designs and Measures of Association 5.4 Sampling Strategy: Sample Size, Power, and Worker Selection
6 Chapter 6: Toxicology & Biological Monitoring
6.1 Dose-Response Relationships and Points of Departure 6.2 Toxicokinetics: Absorption, Distribution, Metabolism, and Elimination 6.3 Aerosol Deposition, Clearance, and Respiratory Tract Dosimetry 6.4 Hepatic, Renal, Neurologic, and Hematologic Target Organ Toxicity 6.5 Pulmonary Toxicology, Carcinogenicity, and Reproductive Hazards 6.6 OEL Frameworks, Classifications, and Excursion Limits 6.7 Chemical Mixtures and Extended Work-Shift OEL Adjustments 6.8 Biological Exposure Indices (BEIs) and Biomonitoring
7 Chapter 7: Biohazards & Indoor Environmental Quality
7.1 Mold, Fungi, and Microbial Contaminants 7.2 Infectious Agents, Bloodborne Pathogens, and Biosafety Levels 7.3 Indoor Environmental Quality (IEQ) Investigations 7.4 Sanitation, Potable Water, and Personal Hygiene Programs
8 Chapter 8: Community Exposure & Environmental Health
8.1 Clean Air Act Framework, NAAQS, and New Source Review 8.2 Hazardous Air Pollutants, CEMS, and EPA Reference Methods 8.3 Atmospheric Stability, Lapse Rates, and Plume Morphology 8.4 Gaussian Plume Modeling, Plume Rise, and Environmental Fate 8.5 HAZWOPER Scope, Mandates, and Training Tiers 8.6 Protection Levels, Site Zoning, Incident Command, and Decontamination 8.7 Water Pollution, Hazardous Waste, and Community Right-to-Know
9 Chapter 9: Health Risk Analysis & Hazard Communication
9.1 GHS Hazard Classification: Health and Physical Hazard Criteria 9.2 GHS Labels, Safety Data Sheets, and Trade Secret Rules 9.3 The AIHA Exposure Assessment Strategy and Similar Exposure Groups 9.4 Qualitative Exposure Profiling and the AIHA Risk Matrix 9.5 Quantitative Health Risk Characterization: HQ, HI, and ELCR 9.6 NIOSH Occupational Exposure Banding 9.7 Risk Communication and Reporting to Affected Parties
10 Chapter 10: Industrial Ventilation Principles & LEV Design
10.1 Elimination, Substitution, Isolation, Containment, and Process Change 10.2 LEV Hood Taxonomy and Capture Velocity Selection 10.3 Hood Airflow Equations, Entry Losses, and Hood Static Pressure 10.4 Particulate Transport Aerodynamics and Duct Sizing 10.5 Duct Friction, Fitting Losses, and System Balancing 10.6 Fan Categories and Pressure Dynamics Across the Fan 10.7 System Curves, the Fan Laws, and Density Corrections
11 Chapter 11: General Ventilation, Air Cleaning & Diagnostics
11.1 Dilution Ventilation Principles and Steady-State Modeling 11.2 Transient Purging and Air Distribution Geometry 11.3 Particulate Air Cleaning: Cyclones, Baghouses, Scrubbers, and ESPs 11.4 Gaseous Emission Control and Air Cleaner Selection 11.5 Ventilation System Troubleshooting and Testing
12 Chapter 12: Noise Measurement & Hearing Conservation
12.1 Acoustic Physics and Decibel Mathematics 12.2 Sound Propagation, Octave Bands, and Frequency Weighting 12.3 Noise Dose Metrics and OSHA versus ACGIH Criteria 12.4 Exchange Rates, Extended Shifts, and Dosimetry Field Protocols 12.5 Engineering Noise Controls and Hearing Protector Attenuation 12.6 Hearing Conservation Programs and Standard Threshold Shifts 12.7 Hand-Arm and Whole-Body Vibration
13 Chapter 13: Thermal Stress Assessment & Control
13.1 Wet Bulb Globe Temperature (WBGT) and Heat Stress Indices 13.2 Heat-Related Disorders, Acclimatization, and Work/Rest Regimens 13.3 Cold Stress Evaluation and Wind Chill
14 Chapter 14: Ionizing Radiation Protection
14.1 Ionizing Radiation Physics and Radioactive Decay Kinetics 14.2 Radiation Units, Radiobiology, and Health Effects 14.3 ALARA, Stay-Time, and the Inverse Square Law 14.4 Shielding Physics, Material Selection, and Gamma Constants 14.5 Radiation Detection Instruments and Spectrometry 14.6 Personnel Dosimetry, Dose Limits, and Contamination Surveys
15 Chapter 15: Non-Ionizing Radiation & Laser Safety
15.1 The Non-Ionizing Spectrum and Static/ELF Field Exposures 15.2 Radiofrequency and Microwave Exposure: SAR, Standards, and Surveys 15.3 Ultraviolet, Visible, and Infrared Radiation Hazards 15.4 Laser Safety Classifications and Optical Density Calculations 15.5 Illumination, Lighting Design, and Visual Performance
16 Chapter 16: Non-Engineering Controls & Personal Protective Equipment
16.1 Respiratory Protection Programs and Assigned Protection Factors 16.2 Maximum Use Concentration, Oxygen Deficiency, and Breathing Air 16.3 Particulate Filters, Sorbent Cartridges, and Change Schedules 16.4 Respirator Fit Testing Protocols 16.5 Chemical Protective Clothing and Dermal Exposure Control
17 Chapter 17: Ergonomics & Workstation Design
17.1 Soft-Tissue Biomechanics and WMSD Pathophysiology 17.2 Ergonomic Risk Factors and Their Interaction Effects 17.3 The Revised NIOSH Lifting Equation 17.4 RULA, REBA, the Strain Index, and the ACGIH HAL TLV 17.5 Anthropometry and Workstation Geometry 17.6 VDT Workstations, Hand Tool Design, and Administrative Ergonomics
18 Chapter 18: Work Environments & Industrial Processes
18.1 Welding Fume Emissions, Metal Fume Fever, and Cr(VI)/Manganese Toxicology 18.2 Foundry Operations and Hot Work Fire Prevention 18.3 Vapor Degreasing, Pickling, Electroplating, and Cyanide Baths 18.4 Spray Coatings, Isocyanates, and Semiconductor Manufacturing 18.5 Confined Spaces and High-Hazard Industrial Operations 18.6 Asbestos, Lead, and Silica: Regulated Substance Programs 18.7 Abrasive Blasting and Surface Preparation
19 Chapter 19: IH Program Management & Professional Ethics
19.1 The BGC Code of Ethics: Canons and Enforcement 19.2 Professional Liability, Standard of Care, and Expert Testimony 19.3 Occupational Health & Safety Management Systems (ISO 45001, ANSI Z10) 19.4 Exposure Records Access and Medical Surveillance 19.5 OSHA Injury and Illness Recordkeeping and Enforcement
10.3 Hood Airflow Equations, Entry Losses, and Hood Static Pressure
Key Takeaways Explain This Topic AI
For a plain flanged or unflanged opening, Q = V(10X² + A) for a plain hood and Q = 0.75V(10X² + A) with a flange, so a flange cuts required airflow by about 25%.
Hood entry loss is expressed as he = Fh × VPd, where the loss factor Fh depends on hood geometry; a well-designed tapered hood has a far lower Fh than a plain duct end.
Hood static pressure SPh = VPd + he, so measuring SPh in the field and comparing it with the design value directly indicates whether the hood is still delivering design flow.
The coefficient of entry Ce = sqrt(VPd / |SPh|) characterises hood efficiency and allows Q to be calculated from a single static pressure reading: Q = 4005 × Ce × A × sqrt(|SPh|).
Last updated: August 2026
Hood Airflow Equations, Entry Losses, and Hood Static Pressure
Selecting the hood and the capture velocity fixes the design intent. Converting that intent into a specified exhaust volume, an entry loss, and a hood static pressure is what makes the system buildable and testable — and hood static pressure is the single field measurement that tells you whether the hood is still moving design airflow.
1. Volumetric Airflow Equations (Q) by Hood Geometry
The ACGIH Industrial Ventilation: A Manual of Recommended Practice for Design establishes empirical and analytical equations relating the required volumetric airflow rate (Q, in cubic feet per minute, cfm), capture velocity (V_c, in feet per minute fpm), hood face area (A, in square feet, ft²), and capture distance (x, in feet, ft).
Hood Geometry & Type Empirical Airflow Formula (Q) Aerodynamic Boundary Conditions & Design Rules
Freestanding Plain Open Duct / Hood (Round or Rectangular) Q = V c ( 10 x 2 + A ) Q = V_c (10 x^2 + A) Q = V c ( 10 x 2 + A ) Air is drawn in a full spherical field from front, sides, and behind the hood face. Valid for x ≤ 1.5 D.
Flanged Exterior Hood (Round or Rectangular) Q = 0.75 ⋅ V c ( 10 x 2 + A ) Q = 0.75 \cdot V_c (10 x^2 + A) Q = 0.75 ⋅ V c ( 10 x 2 + A ) Flange width Wflange ≥ 0.75 √A (or ≥ D/3). Eliminates rearward air draw, reducing required airflow by 25% .
Freestanding Narrow Slot Hood (L/W ≥ 5.0, aspect ratio L/W > 0.2) Q = V c ( 10 x L + A ) Q = V_c (10 x L + A) Q = V c ( 10 xL + A ) Generates a cylindrical rather than spherical velocity field. L = slot length (ft), x = capture distance (ft).
Flanged Slot Hood (or Slot on a Boundary Table) Q = 2.8 ⋅ L ⋅ x ⋅ V c Q = 2.8 \cdot L \cdot x \cdot V_c Q = 2.8 ⋅ L ⋅ x ⋅ V c Valid for capture distance x ≤ 0.5 L. Plenum slot velocity maintained at 1,000--2,000 fpm for distribution.
Canopy Hood (High Canopy) Q = 1.4 ⋅ P ⋅ D ⋅ V c Q = 1.4 \cdot P \cdot D \cdot V_c Q = 1.4 ⋅ P ⋅ D ⋅ V c P = perimeter of tank/source (ft), D = distance from tank surface to hood face (ft). Vc = 50--100 fpm.
Canopy Hood (Low Canopy) (D ≤ 3 ft or D ≤ 0.5√A) Q = 1.4 ⋅ P ⋅ D ⋅ V c or Q = W ⋅ L ⋅ V c Q = 1.4 \cdot P \cdot D \cdot V_c \quad \text{or} \quad Q = W \cdot L \cdot V_c Q = 1.4 ⋅ P ⋅ D ⋅ V c or Q = W ⋅ L ⋅ V c Sized such that hood overhangs tank perimeter by 0.4 × D on all open sides.
Push-Pull Ventilation (Open Surface Tanks) Q exhaust = 100 – 150 cfm/ft 2 of tank area Q_{\text{exhaust}} = 100\text{--}150\text{ cfm/ft}^2 \text{ of tank area} Q exhaust = 100 – 150 cfm/ft 2 of tank area Push jet nozzle (Qpush ≈ 5--10% of Qexhaust) projects air across tank into exhaust slot. +-------------------------------------------------------------------------+
- | HOOD AIRFLOW EQUATION GEOMETRIES |
- +-------------------------------------------------------------------------+
- | |
- | PLAIN OPEN HOOD: FLANGED HOOD (25% Savings!): |
- | |
- | /---------+ +-------+ |
- | / Area A | |FLANGE | |
- | / | +-------+ |
- | <===| DUCT | <===| DUCT | |
- | \ | +-------+ |
- | \ | |FLANGE | |
- | \---------+ +-------+ |
- | <--- x ---> <--- x ---> |
- | * Contaminant * Contaminant |
- | |
- | Q = Vc (10x^2 + A) Q = 0.75 Vc (10x^2 + A) |
- +-------------------------------------------------------------------------+
- 2. Hood Aerodynamics, Entry Losses, and Hood Static Pressure (SPh)
- Total Pressure, Static Pressure, and Velocity Pressure
Airflow through a ventilation system is governed by Bernoulli's conservation of energy principle, expressed in terms of fluid pressures measured in inches of water gauge (extin. w.g.) or Pascals (extPa) : T P = S P + V P TP = SP + VP TP = SP + V P
Total Pressure (TP): The total aerodynamic energy per unit volume in the fluid stream.
Static Pressure (SP): The potential energy exerted equally in all directions against the interior duct walls (measured perpendicular to flow). In an exhaust system upstream of the fan, SP is always negative relative to atmospheric pressure.
Velocity Pressure (VP): The kinetic energy of air motion in the direction of flow. VP is always positive and cannot be negative: V P = ( V 4005 ) 2 ⟺ V = 4005 V P VP = \left(\frac{V}{4005}\right)^2 \quad \Longleftrightarrow \quad V = 4005 \sqrt{VP} V P = ( 4005 V ) 2 ⟺ V = 4005 V P
(where V is velocity in fpm, VP is in in. w.g., and air density is standard 0.075 lb/ft³) .
Physics of Hood Entry Loss (he)
In the ambient room outside the hood, air is at rest: TProom = 0, SProom = 0, and VProom = 0.
To move air into the duct, the exhaust fan must supply energy to:
Accelerate the air from zero velocity to the duct velocity (Vd), creating velocity pressure (VPd).
Overcome turbulent frictional losses and vena contracta vortex shedding (he) as air converges into the hood mouth. +-------------------------------------------------------------------------+
- | VENA CONTRACTA AND HOOD ENTRY LOSS MECHANICS |
- +-------------------------------------------------------------------------+
- | |
- | PLAIN DUCT END (Sharp 90° Edge): |
- | Air streamlines cannot make sharp 90° turns. Flow separates from |
- | the rim, contracting into a narrow jet (Vena Contracta) with |
- | massive turbulent wake eddies. High energy loss! (Fh = 0.93) |
- | |
- | Duct Wall ------------------------+ |
- | Turbulent | Flow streamlines |
- | ( ( ( Eddies | | |
- | <=================== ( ( ( | / |
- | <=================== ( ( ( | <--- |
- | ( ( ( Eddies | \ |
- | Duct Wall ------------------------+ | |
- | |
- | BELLMOUTH / TAPERED HOOD (Smooth Transition): |
- | Streamlines follow smooth curved surface. No flow separation. |
- | Near-zero turbulence! (Fh = 0.04 - 0.15) |
- | |
- | Duct Wall -------------\ |
- | \ Smooth streamlines |
- | <=========================) <---------------- |
- | <=========================) <---------------- |
- | / |
- | Duct Wall -------------/ |
- +-------------------------------------------------------------------------+
The hood entry loss (he) is directly proportional to the duct velocity pressure (VPd): h e = F h × V P d h_e = F_h \times VP_d h e = F h × V P d
Where Fh is the dimensionless hood entry loss coefficient (determined by hood entry geometry).
Hood Static Pressure (SPh) Master Equation
Hood static pressure (SPh), measured downstream of the hood entrance (typically 1 to 3 duct diameters into the straight duct), represents the total suction energy required to accelerate the air and overcome entrance turbulence: S P h = − V P d − h e = − V P d − ( F h ⋅ V P d ) = − ( 1 + F h ) V P d SP_h = -VP_d - h_e = -VP_d - (F_h \cdot VP_d) = -(1 + F_h)VP_d S P h = − V P d − h e = − V P d − ( F h ⋅ V P d ) = − ( 1 + F h ) V P d ∣ S P h ∣ = ( 1 + F h ) V P d \mathbf{|SP_h| = (1 + F_h)VP_d} ∣S P h ∣ = ( 1 + F h ) V P d
Dimensionless Entry Loss Coefficients (Fh) and Coefficients of Entry (Ce)
Hood Inlet Configuration Entry Loss Coeff. (Fh) Coeff. of Entry (Ce) Aerodynamic Characteristics
Plain Open Duct End (Sharp 90° edge) 0.93 0.72 Severe flow separation; vena contracta area ≈ 62% of duct area. Highest turbulence.
Flanged Duct End (Flange ≥ D/3) 0.49 0.82 Flange suppresses edge turbulence; reduces entry loss by nearly half compared to plain end.
Tapered Hood (60° included angle) 0.15 0.93 Smooth conical or pyramidal convergence; minimal boundary layer separation.
Tapered Hood (45° included angle) 0.06 0.97 Outstanding aerodynamic efficiency for transitions.
Bellmouth / Rounded Inlet (r/D ≥ 0.15) 0.04 0.98 Optimal aerodynamic entry. Streamlined laminar intake; virtually zero flow separation.
Canopy Hood (Plain) 0.49--0.93 0.72--0.82 Dependent on lip flanging and internal baffle configuration.
Slot Hood with Tapered Plenum 0.25--0.50 0.82--0.89 Includes slot acceleration loss and plenum distribution transition.
The Coefficient of Entry (Ce)
The Coefficient of Entry (Ce) is the ratio of the actual airflow entering the hood to the theoretical airflow that would occur if there were zero turbulent friction losses for the same static pressure drop: C e = V P d ∣ S P h ∣ = V P d ( 1 + F h ) V P d = 1 1 + F h C_e = \sqrt{\frac{VP_d}{|SP_h|}} = \sqrt{\frac{VP_d}{(1 + F_h)VP_d}} = \mathbf{\frac{1}{\sqrt{1 + F_h}}} C e = ∣ S P h ∣ V P d = ( 1 + F h ) V P d V P d = 1 + F h 1
Determining Volumetric Flow (Q) from Static Pressure (SPh)
In field practice, measuring static pressure (SPh) with a simple static pressure tap and U-tube manometer or Magnehelic gauge is faster, cheaper, and less prone to clogging than traversing dusty ducts with a Pitot tube. Volumetric flow rate is calculated directly: V d = 4005 V P d = 4005 C e 2 ⋅ ∣ S P h ∣ = 4005 ⋅ C e ∣ S P h ∣ V_d = 4005 \sqrt{VP_d} = 4005 \sqrt{C_e^2 \cdot |SP_h|} = 4005 \cdot C_e \sqrt{|SP_h|} V d = 4005 V P d = 4005 C e 2 ⋅ ∣ S P h ∣ = 4005 ⋅ C e ∣ S P h ∣ Q = 4005 ⋅ C e ⋅ A d ∣ S P h ∣ \mathbf{Q = 4005 \cdot C_e \cdot A_d \sqrt{|SP_h|}} Q = 4005 ⋅ C e ⋅ A d ∣S P h ∣
(where Q is in cfm, Ad is duct cross-sectional area in ft², and |SPh| is in in. w.g.) .
- 3. Worked Step-by-Step Calculation Examples
- Worked Example 9.1.1: Sizing Airflow for Flanged vs. Plain Exterior Hood
Problem: An exterior exhaust hood must capture solvent vapors evaporating from a parts cleaning bench. The contaminant source is located at a distance x = 10 inches (0.8333 ft) from the hood face. The hood opening is rectangular with dimensions 12 in × 6 in (Area A = 0.50 ft²). The required capture velocity at the solvent source is Vc = 120 fpm.
Calculate the required volumetric airflow rate (Qplain) if the hood is a freestanding plain open duct.
Calculate the required volumetric airflow rate (Qflanged) if a standard perimeter flange is added.
Determine the percentage airflow and energy savings achieved by flanging the hood.
Solution Steps:
Calculate airflow for Plain Open Hood (Q = Vc [10 x² + A]): x = 10 in = 10 12 = 0.8333 ft , x 2 = ( 0.8333 ) 2 = 0.6944 ft 2 x = 10\text{ in} = \frac{10}{12} = 0.8333\text{ ft}, \quad x^2 = (0.8333)^2 = 0.6944\text{ ft}^2 x = 10 in = 12 10 = 0.8333 ft , x 2 = ( 0.8333 ) 2 = 0.6944 ft 2 Q plain = 120 fpm × [ ( 10 × 0.6944 ) + 0.50 ft 2 ] Q_{\text{plain}} = 120\text{ fpm} \times [(10 \times 0.6944) + 0.50\text{ ft}^2] Q plain = 120 fpm × [( 10 × 0.6944 ) + 0.50 ft 2 ] Q plain = 120 × [ 6.944 + 0.50 ] = 120 × 7.444 = 893.3 cfm ≈ 893 cfm Q_{\text{plain}} = 120 \times [6.944 + 0.50] = 120 \times 7.444 = 893.3\text{ cfm} \approx 893\text{ cfm} Q plain = 120 × [ 6.944 + 0.50 ] = 120 × 7.444 = 893.3 cfm ≈ 893 cfm
Calculate airflow for Flanged Hood (Q = 0.75 · Vc [10 x² + A]): Q flanged = 0.75 × 893.3 cfm = 670.0 cfm ≈ 670 cfm Q_{\text{flanged}} = 0.75 \times 893.3\text{ cfm} = 670.0\text{ cfm} \approx 670\text{ cfm} Q flanged = 0.75 × 893.3 cfm = 670.0 cfm ≈ 670 cfm
Calculate airflow savings: Δ Q = 893.3 − 670.0 = 223.3 cfm ( 223.3 893.3 × 100 = 25.0 % ) \Delta Q = 893.3 - 670.0 = 223.3\text{ cfm} \quad \left(\frac{223.3}{893.3} \times 100 = 25.0\%\right) Δ Q = 893.3 − 670.0 = 223.3 cfm ( 893.3 223.3 × 100 = 25.0% )
Result: Adding a flange reduces the required exhaust flow from 893 cfm down to 670 cfm —a 25% reduction in required airflow and fan operating power while delivering the exact same 120 fpm capture velocity at the solvent source.
Worked Example 9.1.2: Hood Static Pressure, Entry Loss, and Ce Calculation
Problem: A tapered exhaust hood (60° included angle, Fh = 0.15) connects to an 8-inch diameter round duct (D = 8 in = 0.6667 ft, Ad = π · (8/24)² = 0.3491 ft²). The LEV system conveys Q = 1400 cfm of standard air.
Calculate the duct velocity (Vd) and velocity pressure (VPd).
Calculate the hood entry loss (he) in inches of water gauge.
Determine the theoretical hood static pressure (SPh).
Calculate the Coefficient of Entry (Ce).
Solution Steps:
Calculate duct velocity (Vd) and velocity pressure (VPd): V d = Q A d = 1400 cfm 0.3491 ft 2 = 4010.3 fpm ≈ 4010 fpm V_d = \frac{Q}{A_d} = \frac{1400\text{ cfm}}{0.3491\text{ ft}^2} = 4010.3\text{ fpm} \approx 4010\text{ fpm} V d = A d Q = 0.3491 ft 2 1400 cfm = 4010.3 fpm ≈ 4010 fpm V P d = ( V d 4005 ) 2 = ( 4010.3 4005 ) 2 = ( 1.0013 ) 2 = 1.003 in. w.g. VP_d = \left(\frac{V_d}{4005}\right)^2 = \left(\frac{4010.3}{4005}\right)^2 = (1.0013)^2 = 1.003\text{ in. w.g.} V P d = ( 4005 V d ) 2 = ( 4005 4010.3 ) 2 = ( 1.0013 ) 2 = 1.003 in. w.g.
Calculate hood entry loss (he = Fh × VPd): h e = 0.15 × 1.003 in. w.g. = 0.1505 in. w.g. h_e = 0.15 \times 1.003\text{ in. w.g.} = 0.1505\text{ in. w.g.} h e = 0.15 × 1.003 in. w.g. = 0.1505 in. w.g.
Calculate Hood Static Pressure (SPh): S P h = − ( 1 + F h ) V P d = − ( 1 + 0.15 ) × 1.003 = − 1.15 × 1.003 = − 1.153 in. w.g. SP_h = -(1 + F_h)VP_d = -(1 + 0.15) \times 1.003 = -1.15 \times 1.003 = -1.153\text{ in. w.g.} S P h = − ( 1 + F h ) V P d = − ( 1 + 0.15 ) × 1.003 = − 1.15 × 1.003 = − 1.153 in. w.g.
Calculate Coefficient of Entry (Ce): C e = 1 1 + F h = 1 1.15 = 1 1.07238 = 0.9325 C_e = \frac{1}{\sqrt{1 + F_h}} = \frac{1}{\sqrt{1.15}} = \frac{1}{1.07238} = 0.9325 C e = 1 + F h 1 = 1.15 1 = 1.07238 1 = 0.9325
Cross-check using pressures: Ce = √(VPd/|SPh|) = √(1.003/1.153) = √(0.8699) = 0.9327.
Result: The duct velocity is 4010 fpm , hood entry loss is 0.151 in. w.g. , hood static pressure is -1.15 in. w.g. , and the coefficient of entry is 0.933 .
Worked Example 9.1.3: Volumetric Airflow Determination from Field SPh Measurement
Problem: During a routine industrial hygiene compliance audit of a plating line, an IH measures a static pressure of SPh = -1.44 in. w.g. at a test tap located 2 duct diameters downstream of a flanged slot hood (Ce = 0.82). The exhaust duct has an inside diameter of 10 inches (Ad = 0.5454 ft²). Calculate the actual volumetric flow rate (Q) passing through the LEV branch.
Solution Steps:
Identify parameters: Ce = 0.82, Ad = 0.5454 ft², |SPh| = 1.44 in. w.g.
Apply the Master Flow Rate Equation (Q = 4005 · Ce · Ad √(|SPh|)): ∣ S P h ∣ = 1.44 = 1.20 \sqrt{|SP_h|} = \sqrt{1.44} = 1.20 ∣ S P h ∣ = 1.44 = 1.20 Q = 4005 × 0.82 × 0.5454 × 1.20 Q = 4005 \times 0.82 \times 0.5454 \times 1.20 Q = 4005 × 0.82 × 0.5454 × 1.20 Q = 4005 × 0.82 × 0.65448 = 2149.4 cfm ≈ 2150 cfm Q = 4005 \times 0.82 \times 0.65448 = 2149.4\text{ cfm} \approx 2150\text{ cfm} Q = 4005 × 0.82 × 0.65448 = 2149.4 cfm ≈ 2150 cfm
Calculate Duct Velocity (Vd) to verify: V d = Q A d = 2149.4 cfm 0.5454 ft 2 = 3941 fpm V_d = \frac{Q}{A_d} = \frac{2149.4\text{ cfm}}{0.5454\text{ ft}^2} = 3941\text{ fpm} V d = A d Q = 0.5454 ft 2 2149.4 cfm = 3941 fpm V P d = ( 3941 4005 ) 2 = ( 0.9840 ) 2 = 0.9683 in. w.g. VP_d = \left(\frac{3941}{4005}\right)^2 = (0.9840)^2 = 0.9683\text{ in. w.g.} V P d = ( 4005 3941 ) 2 = ( 0.9840 ) 2 = 0.9683 in. w.g.
Verify Ce: Ce = √(VPd/|SPh|) = √(0.9683/1.44) = √(0.6724) = 0.820.
Result: The measured static pressure of -1.44 in. w.g. confirms an active branch airflow of 2150 cfm .