10.3 Pull and Junction Box Sizing for Conductors 4 AWG and Larger — NEC 314.28

Colorado Journeyman Electrician Study Guide Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Colorado Electrical Licensing Laws, DORA Rules & Exam Logistics

1.1 Colorado Electrical Board, Licensure Tiers & Application Process 1.2 Senate Bill 25-165, Apprentice Supervision & Colorado Board Rules 1.3 Permitting, Inspection Procedures, Violations & Penalties 1.4 The Colorado PSI Exam: Open-Book Format, Time Management & Code Navigation

2 Chapter 2: Electrical Theory, Mathematics & Fundamental Concepts

2.1 Ohm's Law, Joule's Law & DC Circuit Analysis 2.2 AC Fundamentals: Inductance, Capacitance & Power Factor 2.3 Three-Phase Electrical Systems: Wye & Delta Configurations 2.4 Voltage Drop Principles & Single/Three-Phase Formulas

3 Chapter 3: General Installation Requirements — NEC Articles 90 & 110

3.1 NEC Structure, Arrangement & Article 90 Fundamentals 3.2 Key Article 100 Definitions for the Exam 3.3 Equipment Examination, Listing & Termination Temperature Limits 3.4 Working Space, Dedicated Electrical Space & Guarding

4 Chapter 4: Branch Circuits & Feeders — NEC Articles 210, 215 & 225

4.1 Branch-Circuit Ratings, Conductor Sizing & Multiwire Branch Circuits 4.2 Dwelling Unit Required Outlets & Receptacle Placement 4.3 Ground-Fault Circuit-Interrupter (GFCI) Protection 4.4 Arc-Fault Circuit-Interrupter (AFCI) Protection & Feeder Rules

5 Chapter 5: Services & Overcurrent Protection — NEC Articles 230, 240 & 242

5.1 Service Conductors, Clearances & Overhead/Underground Drops 5.2 Service Disconnecting Means, Ratings & Surge Protection 5.3 Overcurrent Protection Fundamentals & Standard Ratings 5.4 Feeder & Transformer Tap Rules

6 Chapter 6: Grounding and Bonding — NEC Article 250 Part I (Systems & Electrodes)

6.1 Grounding vs. Bonding: Principles, Functions & Article 250 Architecture 6.2 Grounded Conductors, Main Bonding Jumpers & System Bonding Jumpers 6.3 The Grounding Electrode System 6.4 Grounding Electrode Conductor (GEC) Sizing & Installation

7 Chapter 7: Grounding and Bonding — NEC Article 250 Part II (Equipment & Special Systems)

7.1 Equipment Grounding Conductors (EGC) Types & Identification 7.2 Sizing the Equipment Grounding Conductor 7.3 Separately Derived Systems 7.4 Grounding & Bonding at Separate Buildings or Structures

8 Chapter 8: Wiring Methods & Materials — NEC Chapter 3

8.1 General Wiring Requirements & Underground Installations 8.2 Nonmetallic and Armored Cable Assemblies 8.3 Metallic and Nonmetallic Raceways 8.4 Cable Trays, Wireways, Auxiliary Gutters & Surface Raceways

9 Chapter 9: Conductors, Ampacity & Wire Sizing — NEC Article 310

9.1 Conductor Properties, Insulation Types & NEC Table 310.16 9.2 Temperature Correction Factors 9.3 Conductor Bundling & Adjustment Factors 9.4 Comprehensive Conductor Sizing & Terminal Temperature Coordination

10 Chapter 10: Box Fill, Conduit Fill & Pull Box Calculations

10.1 Outlet and Device Box Fill Calculations — NEC 314.16(A) & (B) 10.2 Conduit Fill Calculations — Chapter 9 Tables 1, 4, 5 & Annex C 10.3 Pull and Junction Box Sizing for Conductors 4 AWG and Larger — NEC 314.28 10.4 Practical Enclosure & Raceway Sizing Exam Scenarios

11 Chapter 11: Load Calculations — Dwellings & Commercial Buildings — NEC Article 120

11.1 General Lighting, Small Appliance & Laundry Loads 11.2 Fixed Appliances, Dryers & Cooking Equipment Calculations 11.3 Standard vs. Optional Calculation Methods for Single-Family Dwellings 11.4 Commercial & Multifamily Load Calculations

12 Chapter 12: Motors, Motor Circuits & Controllers — NEC Article 430

12.1 Motor Nameplate vs. NEC Tables & Motor Full-Load Current 12.2 Sizing Motor Branch-Circuit Conductors & Overload Protection 12.3 Motor Branch-Circuit Short-Circuit & Ground-Fault Protection 12.4 Motor Feeders, Disconnecting Means & Controllers

13 Chapter 13: Transformers, Distribution & Utilization Equipment

13.1 Transformer Overcurrent Protection & Installation — NEC Article 450 13.2 Panelboards, Switchboards & Switchgear — NEC Article 408 13.3 Luminaires, Appliances & Fixed Electric Space Heating 13.4 Generators, Transfer Switches & Standby Systems

14 Chapter 14: Special Occupancies, Renewable Energy & Modern Technologies

14.1 Hazardous (Classified) Locations — NEC Articles 500-516 14.2 Health Care Facilities & Places of Assembly — NEC Articles 517 & 518 14.3 Swimming Pools, Spas, Hot Tubs & Fountains — NEC Article 680 14.4 Solar Photovoltaic (PV) Systems & Energy Storage — NEC Articles 690, 705 & 706

10.3 Pull and Junction Box Sizing for Conductors 4 AWG and Larger — NEC 314.28

Key Takeaways Explain This Topic AI

NEC 314.28 applies strictly to pull and junction boxes containing electrical conductors of size 4 AWG or larger operating under 1000 volts.

For straight pulls under 314.28(A)(1), the length of the box cannot be less than 8 times the trade diameter of the largest raceway entering the enclosure (L = 8 × D_largest).

For angle pulls, U-pulls, and splices under 314.28(A)(2), the distance to the opposite wall cannot be less than 6 times the trade diameter of the largest raceway entering that wall, PLUS the sum of the trade diameters of all other raceway entries on the same wall and row (L = 6 × D_largest + sum of D_other).

Under 314.28(A)(2), the center-to-center distance between raceway entries enclosing the same conductor run cannot be less than 6 times the trade diameter of the larger raceway.

When raceways enter through the removable cover of a pull box, the distance from that entry to the opposite wall must be increased to accommodate cable bending radius per NEC 314.28(A)(3) and Table 312.6(A).

Last updated: September 2026

10.3 Pull and Junction Box Sizing for Conductors 4 AWG and Larger — NEC 314.28

Exam Fast Fact: On the Colorado Journeyman Electrician examination, questions asking you to calculate the minimum dimensions of a commercial pull or junction box are guaranteed. The single most common mistake is confusing conductor size with conduit trade size. Remember this golden rule: The multiplier (8× for straight pulls, 6× for angle pulls) is multiplied by the TRADE SIZE OF THE CONDUIT, never the circular mil or AWG size of the conductor! Furthermore, when adding "other raceways" for an angle pull, you only add raceways entering on that same wall and row .

When electrical conductors reach size 4 AWG and larger , their physical rigidity makes them impossible to bend sharply without damaging their insulation, work-hardening the copper strands, or snapping mechanical lugs. Standard cubic-inch box fill calculations from NEC 314.16 no longer provide adequate physical clearance for these heavy feeders. Consequently, NEC 314.28 takes over, establishing minimum linear dimensions for boxes and conduit bodies based on raceway diameters rather than cubic-inch volume. PULL BOX CODE JURISDICTION THRESHOLD

  • │
  • ┌─────────────────────────────┴─────────────────────────────┐
  • ▼ ▼
  • CONDUCTORS 6 AWG AND SMALLER CONDUCTORS 4 AWG AND LARGER
  • NEC 314.16 APPLIES NEC 314.28 APPLIES
  • Calculated by cubic-inch volume • Calculated by linear dimensions (inches)
  • Table 314.16(A) standard volumes • Straight pulls: 8 × Conduit Diameter
  • Table 314.16(B) conductor allowances • Angle/U-pulls: 6 × Conduit + Sum of Others
  • Straight Pulls: NEC 314.28(A)(1)

A straight pull occurs where conductors enter one wall of an enclosure and exit directly through the opposite wall without turning a corner or making a splice:

NEC 314.28(A)(1) Straight Pull Mandate: "In straight pulls, the length of the box shall not be less than 8 times the trade size of the largest raceway." STRAIGHT PULL DIAGRAM

(NEC 314.28(A)(1))

  • CONDUIT ENTRY CONDUIT EXIT
  • ─────────────────┐ ┌─────────────────
  • 4" CONDUIT │ │ 4" CONDUIT
  • │ │
  • ─────────────────┤ ├─────────────────
  • 2" CONDUIT │ ═════════════════════> │ 2" CONDUIT
  • │ Conductors Pulled │
  • ─────────────────┤ Straight Through ├─────────────────
  • │ │
  • └───────────────────────────┘
  • │<────── LENGTH ≥ 8 × D ───>│
  • │ 8 × 4" = 32 Inches │

Straight Pull Formula Length of Box ≥ 8 × D largest \text{Length of Box} \ge 8 \times D_{\text{largest}} Length of Box ≥ 8 × D largest ​

Where D largest D_{\text{largest}} D largest ​ is the trade size of the largest raceway entering the enclosure.

Practical Straight Pull Rules

Ignore Smaller Conduits for Length: Even if the box receives three 2" conduits and one 4" conduit, the length is determined strictly by the 4" conduit: 8 × 4 " = 32 " 8 \times 4" = 32" 8 × 4" = 32" . The smaller conduits do NOT add to the length of a straight pull.

Width of Box: The width of the box is not mandated by the 8× formula; rather, the width must be sufficient to provide code-compliant spacing between locknuts and bushings (typically referencing standard conduit layout tables or manufacturer knockouts).

Angle Pulls, U-Pulls, and Splices: NEC 314.28(A)(2)

Where conductors make a turn inside an enclosure, leave through the same wall, or are spliced on terminal blocks, the pulling tension exerts massive sidewall bearing pressure against the inner raceway bushing. To provide adequate bending radius, NEC 314.28(A)(2) imposes a rigorous multi-part sizing formula: ANGLE PULL VS. U-PULL GEOMETRY

  • ANGLE PULL (90° Turn) U-PULL (Same Wall)
  • ┌─────────────────────────┐ ┌─────────────────────────┐
  • │ │ │ │
  • │ │ │ ╭─────────────╮ │
  • │ ╭───────────────╮ │ │ │ │ │
  • │ │ │ │ │ │ │ │
  • 4" ├────┘ │ │ │ │ │ │
  • CONDUIT│ │ │ └─────┼─────────────┼─────┘
  • 2" ├─────────╮ │ │ │ 3" CONDUIT │ 3" CONDUIT
  • CONDUIT│ │ │ │ │ (ENTRY) │ (EXIT)
  • └─────────┼──────────┼────┘
  • │ 2" │ 4"
  • CONDUIT CONDUIT
  • 1. Distance to Opposite Wall Formula

Under NEC 314.28(A)(2) , the distance between each raceway entry inside the box and the opposite wall must not be less than: Distance ≥ ( 6 × D largest ) + ∑ D other \text{Distance} \ge (6 \times D_{\text{largest}}) + \sum D_{\text{other}} Distance ≥ ( 6 × D largest ​ ) + ∑ D other ​

D largest D_{\text{largest}} D largest ​ : The trade size of the largest raceway entering that specific wall.

∑ D other \sum D_{\text{other}} ∑ D other ​ : The sum of the trade diameters of all other raceway entries on that same wall and row .

Critical Rules for Calculating Distance to Opposite Wall

Calculate Each Wall Independently: You must calculate the required dimension for the horizontal axis (Left-to-Right wall) and the vertical axis (Bottom-to-Top wall) separately. If the raceway entries on the two walls differ, the box will be rectangular.

Same Wall and Row Only: When summing the other raceways, include only those raceways entering through that specific wall. Never add conduits from the adjacent wall, perpendicular wall, or opposite wall!

Multiple Rows: If raceway entries are arranged in multiple rows on the same wall, the distance to the opposite wall is calculated for each row, adding the required offset distance between rows.

2. Minimum Distance Between Raceway Entries Enclosing the Same Conductor

In addition to the distance to the opposite wall, NEC 314.28(A)(2) mandates a minimum separation between the conduit where a conductor enters and the conduit where that same conductor exits:

NEC 314.28(A)(2) Entry Separation Mandate: "The distance between raceway entries enclosing the same conductor shall not be less than 6 times the trade size of the larger raceway." Entry Separation Distance ≥ 6 × D larger \text{Entry Separation Distance} \ge 6 \times D_{\text{larger}} Entry Separation Distance ≥ 6 × D larger ​

This distance is measured in a straight line from the center-to-center of the two conduit entries.

If a feeder enters in a 3" conduit on the left wall and turns 90 degrees to exit in a 3" conduit on the bottom wall, the diagonal center-to-center distance between those two conduits cannot be less than 6 × 3 " = 18 " 6 \times 3" = 18" 6 × 3" = 18" .

If the box dimensions calculated from the wall formula do not provide this 18-inch diagonal separation, the box size must be increased until the 6× center-to-center distance is satisfied!

U-Pulls (Entering and Exiting the Same Wall)

A U-pull occurs where conductors enter through a conduit on one wall and exit through another conduit located on that exact same wall :

Distance to Opposite Wall: Apply the standard formula: 6 × D largest + ∑ D other 6 \times D_{\text{largest}} + \sum D_{\text{other}} 6 × D largest ​ + ∑ D other ​ . For example, if two 3" conduits enter the bottom wall of a pull box in a U-pull arrangement, the distance from the bottom wall to the top wall must be at least: ( 6 × 3 " ) + 3 " = 18 " + 3 " = 21 " (6 \times 3") + 3" = 18" + 3" = \mathbf{21"} ( 6 × 3" ) + 3" = 18" + 3" = 21" .

Entry Separation on Same Wall: The center-to-center distance between the two 3" raceways on that wall must be at least: 6 × 3 " = 18 " 6 \times 3" = \mathbf{18"} 6 × 3" = 18" . This means the box must be wide enough to support two 3" locknuts spaced at least 18 inches apart center-to-center!

  • Enclosure Depth & Conduit Entries in Covers
  • Enclosure Depth (NEC 314.28(A)(2))

The depth of a pull or junction box containing conductors 4 AWG and larger must be sufficient to provide proper clearance for locknuts, bushings, and conductor bending radii. Typically, the depth must be at least equal to the diameter of the largest raceway entering plus locknut clearance, or satisfy the minimum wire-bending space requirements of NEC 312.6 .

Conduit Entries in Removable Covers (NEC 314.28(A)(3))

Where a conduit enters through the removable cover of a pull box:

The distance from that cover entry to the opposite back wall must not be less than the bending space required in NEC Table 312.6(A) for one conductor per terminal.

If conductors leave the enclosure opposite the cover entry, the depth of the box must accommodate the pulling radius without kinking the cable.

  • Step-by-Step Pull Box Sizing Examples
  • Example 1: Straight Pull Box Sizing

A commercial electrical contractor is installing feeder raceways across a mechanical room. The run enters a pull box with two 4" conduits, one 3" conduit, and one 2" conduit, all continuing straight through to the opposite wall. What is the minimum required length of the pull box? STEP-BY-STEP CALCULATION:

1. Identify Pull Type: Straight pull (entering one wall, exiting opposite wall).

2. Identify Largest Raceway: D_largest = 4 inches.

3. Apply NEC 314.28(A)(1) Formula:

Length = 8 × D_largest

Length = 8 × 4" = 32 inches.

CONCLUSION: The minimum length of the box from entry wall to exit wall is 32 inches.

(The 3" and 2" conduits have no effect on the straight pull length calculation).

Example 2: Angle Pull Box Sizing (Mixed Conduits)

A pull box contains conductors 4 AWG and larger making a 90-degree turn. The raceways enter and exit as follows:

Left Wall Entry: One 3" conduit, two 2" conduits.

Bottom Wall Exit: One 3" conduit, two 2" conduits.

What are the minimum dimensions (Height, Width, and Diagonal Entry Spacing) required for this enclosure? STEP-BY-STEP CALCULATION:

1. Width (Distance from Left Wall to Opposite Right Wall):

  • Largest conduit entering Left Wall = 3"
  • Other conduits entering Left Wall = two 2" conduits (2" + 2" = 4")
  • Formula: Distance = (6 × D_largest) + Sum(D_other)

- Width = (6 × 3") + 2" + 2" = 18" + 4" = 22 inches.

2. Height (Distance from Bottom Wall to Opposite Top Wall):

  • Largest conduit entering Bottom Wall = 3"
  • Other conduits entering Bottom Wall = two 2" conduits (2" + 2" = 4")

- Height = (6 × 3") + 2" + 2" = 18" + 4" = 22 inches.

3. Minimum Separation Between Raceways Enclosing Same Conductor:

  • Larger raceway = 3"
  • Formula: Center-to-center distance ≥ 6 × D_larger

- Distance = 6 × 3" = 18 inches.

CONCLUSION:

- Minimum Box Dimensions: 22" Wide × 22" High.

- Minimum Diagonal Separation between 3" entries: 18 inches center-to-center.