9.1 Conductor Properties, Insulation Types & NEC Table 310.16

Colorado Journeyman Electrician Study Guide Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Colorado Electrical Licensing Laws, DORA Rules & Exam Logistics

1.1 Colorado Electrical Board, Licensure Tiers & Application Process 1.2 Senate Bill 25-165, Apprentice Supervision & Colorado Board Rules 1.3 Permitting, Inspection Procedures, Violations & Penalties 1.4 The Colorado PSI Exam: Open-Book Format, Time Management & Code Navigation

2 Chapter 2: Electrical Theory, Mathematics & Fundamental Concepts

2.1 Ohm's Law, Joule's Law & DC Circuit Analysis 2.2 AC Fundamentals: Inductance, Capacitance & Power Factor 2.3 Three-Phase Electrical Systems: Wye & Delta Configurations 2.4 Voltage Drop Principles & Single/Three-Phase Formulas

3 Chapter 3: General Installation Requirements — NEC Articles 90 & 110

3.1 NEC Structure, Arrangement & Article 90 Fundamentals 3.2 Key Article 100 Definitions for the Exam 3.3 Equipment Examination, Listing & Termination Temperature Limits 3.4 Working Space, Dedicated Electrical Space & Guarding

4 Chapter 4: Branch Circuits & Feeders — NEC Articles 210, 215 & 225

4.1 Branch-Circuit Ratings, Conductor Sizing & Multiwire Branch Circuits 4.2 Dwelling Unit Required Outlets & Receptacle Placement 4.3 Ground-Fault Circuit-Interrupter (GFCI) Protection 4.4 Arc-Fault Circuit-Interrupter (AFCI) Protection & Feeder Rules

5 Chapter 5: Services & Overcurrent Protection — NEC Articles 230, 240 & 242

5.1 Service Conductors, Clearances & Overhead/Underground Drops 5.2 Service Disconnecting Means, Ratings & Surge Protection 5.3 Overcurrent Protection Fundamentals & Standard Ratings 5.4 Feeder & Transformer Tap Rules

6 Chapter 6: Grounding and Bonding — NEC Article 250 Part I (Systems & Electrodes)

6.1 Grounding vs. Bonding: Principles, Functions & Article 250 Architecture 6.2 Grounded Conductors, Main Bonding Jumpers & System Bonding Jumpers 6.3 The Grounding Electrode System 6.4 Grounding Electrode Conductor (GEC) Sizing & Installation

7 Chapter 7: Grounding and Bonding — NEC Article 250 Part II (Equipment & Special Systems)

7.1 Equipment Grounding Conductors (EGC) Types & Identification 7.2 Sizing the Equipment Grounding Conductor 7.3 Separately Derived Systems 7.4 Grounding & Bonding at Separate Buildings or Structures

8 Chapter 8: Wiring Methods & Materials — NEC Chapter 3

8.1 General Wiring Requirements & Underground Installations 8.2 Nonmetallic and Armored Cable Assemblies 8.3 Metallic and Nonmetallic Raceways 8.4 Cable Trays, Wireways, Auxiliary Gutters & Surface Raceways

9 Chapter 9: Conductors, Ampacity & Wire Sizing — NEC Article 310

9.1 Conductor Properties, Insulation Types & NEC Table 310.16 9.2 Temperature Correction Factors 9.3 Conductor Bundling & Adjustment Factors 9.4 Comprehensive Conductor Sizing & Terminal Temperature Coordination

10 Chapter 10: Box Fill, Conduit Fill & Pull Box Calculations

10.1 Outlet and Device Box Fill Calculations — NEC 314.16(A) & (B) 10.2 Conduit Fill Calculations — Chapter 9 Tables 1, 4, 5 & Annex C 10.3 Pull and Junction Box Sizing for Conductors 4 AWG and Larger — NEC 314.28 10.4 Practical Enclosure & Raceway Sizing Exam Scenarios

11 Chapter 11: Load Calculations — Dwellings & Commercial Buildings — NEC Article 120

11.1 General Lighting, Small Appliance & Laundry Loads 11.2 Fixed Appliances, Dryers & Cooking Equipment Calculations 11.3 Standard vs. Optional Calculation Methods for Single-Family Dwellings 11.4 Commercial & Multifamily Load Calculations

12 Chapter 12: Motors, Motor Circuits & Controllers — NEC Article 430

12.1 Motor Nameplate vs. NEC Tables & Motor Full-Load Current 12.2 Sizing Motor Branch-Circuit Conductors & Overload Protection 12.3 Motor Branch-Circuit Short-Circuit & Ground-Fault Protection 12.4 Motor Feeders, Disconnecting Means & Controllers

13 Chapter 13: Transformers, Distribution & Utilization Equipment

13.1 Transformer Overcurrent Protection & Installation — NEC Article 450 13.2 Panelboards, Switchboards & Switchgear — NEC Article 408 13.3 Luminaires, Appliances & Fixed Electric Space Heating 13.4 Generators, Transfer Switches & Standby Systems

14 Chapter 14: Special Occupancies, Renewable Energy & Modern Technologies

14.1 Hazardous (Classified) Locations — NEC Articles 500-516 14.2 Health Care Facilities & Places of Assembly — NEC Articles 517 & 518 14.3 Swimming Pools, Spas, Hot Tubs & Fountains — NEC Article 680 14.4 Solar Photovoltaic (PV) Systems & Energy Storage — NEC Articles 690, 705 & 706

9.1 Conductor Properties, Insulation Types & NEC Table 310.16

Key Takeaways Explain This Topic AI

Copper possesses roughly 1.64 times the electrical conductivity of aluminum, requiring aluminum conductors to be sized approximately two AWG gauges larger to carry an equivalent ampacity.

NEC 310.3(C) mandates that all conductors 8 AWG and larger installed in raceways must be stranded to provide pull flexibility and prevent mechanical stress or insulation damage.

Conductor insulation letter markings define physical operating capabilities: 'T' for thermoplastic, 'H' for 75°C heat resistance, 'HH' for 90°C high-heat resistance, 'W' for moisture resistance, 'N' for nylon outer jacket, and '-2' for 90°C rating in both wet and dry locations.

NEC Table 310.16 is organized into three temperature rating columns (60°C, 75°C, and 90°C), with equipment termination limits governed by NEC 110.14(C) generally restricting final ampacity to the 75°C column.

Conductors with 90°C insulation (such as THHN, THWN-2, and XHHW-2) are universally installed because their higher temperature rating serves as the starting point for derating adjustments, preventing unnecessary conductor up-sizing.

Last updated: September 2026

9.1 Conductor Properties, Insulation Types & NEC Table 310.16

Exam Fast Fact: On the Colorado Journeyman Electrician examination, questions involving NEC Table 310.16 are among the most frequent and heavily weighted. Candidates routinely lose points by confusing conductor insulation temperature ratings with equipment terminal ratings under NEC 110.14(C) . Remember this fundamental rule: Conductors with 90°C insulation may be derated from the 90°C column, but the final allowable ampacity can never exceed the temperature rating of the equipment termination lugs (typically 75°C).

Conductors are the circulatory system of any electrical installation, carrying current from service equipment and transformers to distribution panelboards, branch circuits, and utilization equipment. Selecting the correct conductor size requires mastering conductor metallurgy, mechanical stranding requirements, insulation chemical properties, and the precise architecture of the National Electrical Code's ampacity tables.

Conductor Metallurgy: Copper vs. Aluminum vs. Copper-Clad Aluminum

The NEC recognizes three primary conductor materials for general electrical wiring in NEC Article 310 : copper, aluminum, and copper-clad aluminum. Each metal exhibits distinct electrical, thermal, and mechanical characteristics that dictate its sizing, installation techniques, and termination requirements. ELECTRICAL CONDUCTOR METALLURGY

  • │
  • ┌────────────────────────────┼────────────────────────────┐
  • ▼ ▼ ▼
  • COPPER ALUMINUM COPPER-CLAD ALUMINUM
  • K ≈ 12.9 ohms-cmil/ft • K ≈ 21.2 ohms-cmil/ft • Metallurgical bond
  • Superior ductility • 61% conductivity of Cu • 10% Cu volume minimum
  • Smaller conduit fill • High thermal expansion • Sized via Aluminum
  • High scrap/material cost • Lighter weight for feeders Table 310.16 column
  • 1. Copper (Cu)

Copper remains the industry benchmark for commercial, industrial, and residential branch-circuit wiring due to its superior electrical and physical properties:

Electrical Conductivity: Copper has an electrical resistivity constant (K) of approximately 12.9 ohms-circular mils per foot at 75°C. Its high conductivity minimizes voltage drop and resistive power losses (I²R).

Physical Dimensions: Because copper carries more current per square mil of cross-sectional area than aluminum, copper conductors require smaller trade-size raceways and enclosures, significantly reducing conduit fill calculations.

Mechanical Durability: Copper possesses high tensile strength, excellent ductility, and natural resistance to creep (gradual deformation under continuous mechanical pressure). It is easy to terminate, resists nicking, and can withstand repeated flexing without work-hardening or fracturing.

2. Aluminum (Al)

Aluminum is widely utilized in large commercial and industrial feeders, service entrance conductors, and utility distribution systems where material cost and conductor weight are paramount:

Electrical Conductivity: Electrical-grade aluminum (AA-8000 series alloy per NEC 310.3(B) ) has an electrical resistivity constant (K) of approximately 21.2 ohms-circular mils per foot at 75°C. Aluminum exhibits roughly 61% of the conductivity of copper , which means an aluminum conductor must be approximately two AWG sizes larger than a copper conductor to carry an equivalent ampacity (e.g., a 2/0 AWG aluminum conductor carries 135A at 75°C, while a 1/0 AWG copper conductor carries 150A).

Weight Advantage: Aluminum weighs approximately 30% as much as copper for an equivalent volume. On long vertical feeder runs or overhead spans, aluminum drastically reduces strain on conduit hangers, pull boxes, and building structural members.

Thermal Expansion and Creep: Aluminum expands roughly 30% more than copper when heated. Under cyclic electrical loading, thermal expansion and contraction can cause terminal connections to loosen over time if improper lugs are installed. Modern aluminum conductors use AA-8000 series aluminum alloy to resist creep, but they must always be terminated in lugs specifically listed and marked AL7CU or AL9CU .

Oxidation and Termination Compound: When exposed to atmospheric oxygen, aluminum instantly forms an insulating oxide film. To ensure long-term electrical conductivity and prevent galvanic corrosion, electricians wire-brush the bare aluminum strands and apply a listed antioxidant joint compound before torquing the lug to manufacturer specifications under NEC 110.14(D) .

3. Copper-Clad Aluminum

Copper-clad aluminum consists of an aluminum core metallurgically bonded to an outer skin of copper. The copper skin must constitute a minimum of 10% of the total cross-sectional area by volume (or 26.8% by weight):

It combines the lighter weight of aluminum with the corrosion-resistant contact surface of copper.

For ampacity determinations under NEC Table 310.16 , copper-clad aluminum conductors must be sized strictly using the aluminum ampacity columns , never the copper columns.

  • Engineering Property Copper (Cu) Aluminum (AA-8000 Alloy) Copper-Clad Aluminum
  • Resistivity (K) at 75°C ≈ 12.9 ohms-cmil/ft ≈ 21.2 ohms-cmil/ft ≈ 21.2 ohms-cmil/ft
  • Relative Conductivity 100% (Baseline) ≈ 61% ≈ 61%
  • Weight Comparison 1.0 (Heavy) ≈ 0.33 (Very Light) ≈ 0.38 (Light)
  • Thermal Expansion Rate Moderate (16.5 × 10⁻⁶/K) High (23.1 × 10⁻⁶/K) High (23.0 × 10⁻⁶/K)
  • Table 310.16 Column Copper Columns Aluminum Columns Aluminum Columns

Common Applications Branch circuits, commercial feeds Large feeders, services, switchboards Rare specialized feeder runs

Solid vs. Stranded Conductors (NEC 310.3(C))

The physical construction of the metallic core determines a conductor's mechanical flexibility, skin effect, and permitted wiring methods:

NEC 310.3(C) Mandate: "Where installed in raceways, conductors 8 AWG and larger shall be stranded." SOLID VS. STRANDED MANDATE

  • (NEC 310.3(C))
  • │
  • ┌────────────────────────┴────────────────────────┐
  • ▼ ▼
  • 14, 12, 10 AWG 8 AWG AND LARGER
  • Solid OR Stranded MUST BE STRANDED
  • Permitted in raceways • Required in all raceways
  • Solid common in NM-B cable • Solid prohibited in conduit
  • Stranded common in commercial EMT • Prevents conductor breakage
  • Why the Code Requires Stranding for 8 AWG and Larger

Attempting to pull a solid 8 AWG, 6 AWG, or larger conductor through conduit bends (such as standard EMT 90-degree elbows) creates severe mechanical stress. Solid conductors of this diameter:

Exhibit excessive stiffness, leading to damaged conduit fittings and exceeding allowable sidewall bearing pressure.

Suffer severe work-hardening and mechanical fatigue when bent, causing microscopic surface fractures that create localized high-resistance hot spots.

Can crush or shear their own insulation against raceway walls during strenuous pulls.

Stranding Classes and Fine-Stranded Conductors

Standard building wire (THHN/THWN-2, XHHW-2) utilizes Class B (concentric 7-strand or 19-strand) or Class C stranding. However, flexible cords, portable cables, and modern industrial equipment often incorporate fine-stranded conductors (Class G, H, I, K, or M welding cable and locomotive cable). Under NEC 110.14 , fine-stranded conductors cannot be terminated in standard mechanical screw lugs unless the connector is specifically listed and marked for the specific conductor stranding class, or unless listed crimp-on ferrule pins are utilized.

Decoding Conductor Insulation Designations

Electrical conductors are wrapped in polymer insulation formulated to withstand heat, voltage stress, moisture, chemicals, and mechanical abrasion. The letters stamped along the outer jacket of any listed building wire provide a precise chemical and thermal specification: INSULATION LETTER CODE KEY

  • ┌───────┬───────────────────────────────┬─────────────────────────────┐
  • │ Code │ Meaning │ Operational Significance │
  • ├───────┼───────────────────────────────┼─────────────────────────────┤
  • │ T │ Thermoplastic (PVC) │ Melts at high temperature │
  • │ H │ Heat-Resistant │ 75°C Temperature Rating │
  • │ HH │ High-Heat-Resistant │ 90°C Temperature Rating │
  • │ W │ Moisture/Water-Resistant │ Approved for Wet Locations │
  • │ N │ Nylon Outer Jacket │ Resists oil, gas, abrasion │
  • │ X │ Cross-Linked Polymer (XLPE) │ Thermoset (does not melt) │
  • │ -2 │ Continuous 90°C Wet and Dry │ 90°C in ALL environments │
  • └───────┴───────────────────────────────┴─────────────────────────────┘
  • Popular Conductor Insulation Profiles

TW: Thermoplastic, Moisture-Resistant. Rated 60°C for dry and wet locations. Found primarily in older installations and specialized chemical environments; rarely installed in modern commercial work.

THW: Thermoplastic, Heat- and Moisture-Resistant. Rated 75°C for both dry and wet locations.

THHN: Thermoplastic, High-Heat-Resistant, Nylon Jacket. Rated 90°C for dry and damp locations only . It is not rated for wet locations . The outer nylon jacket provides exceptional resistance to abrasion, mineral oils, and gasoline fumes, making it ideal for conduit pulls.

THWN: Thermoplastic, Heat- and Moisture-Resistant, Nylon Jacket. Rated 75°C for wet and dry locations .

THWN-2: Thermoplastic, High-Heat- and Moisture-Resistant, Nylon Jacket. Rated 90°C for both wet and dry locations . Virtually all commercial "THHN" wire sold today is dual-rated as THHN/THWN-2 , allowing it to be used in wet, damp, or dry locations at 90°C.

XHHW-2: Cross-linked Synthetic Polymer (XLPE), High-Heat- and Moisture-Resistant. Rated 90°C for both wet and dry locations . Unlike thermoplastic PVC, cross-linked polyethylene is a thermoset material. It does not soften or melt when subjected to high temperatures or short-circuit surges. XHHW-2 has no outer nylon jacket, making it more flexible in cold weather, easier to pull through multiple bends without jacket peeling, and highly resistant to dielectric breakdown.

UF (Underground Feeder): Moisture-resistant cable rated for direct burial. Under NEC 340.80 , the ampacity of Type UF cable must always be sized from the 60°C column of Table 310.16, even if individual conductors are labeled 90°C.

The Critical Wet Location Trap (NEC 300.5(B) and 300.9)

One of the most dangerous traps on the Colorado Journeyman exam involves raceway moisture classifications:

Underground Conduits (NEC 300.5(B)): The interior of any raceway installed underground is defined by code as a wet location . Condensation and groundwater penetration ensure underground pipes are perpetually wet.

Exterior Above-Ground Conduits (NEC 300.9): Raceways installed outdoors on exterior walls or roofs are defined as wet locations .

Exam Application: Standard single-rated THHN (which lacks the "W" designation) is prohibited from being installed in underground conduits or outdoor rooftop raceways! Only conductors with a "W" rating (such as THWN-2 or XHHW-2) are code-compliant in these wet environments.

Anatomy of NEC Table 310.16

NEC Table 310.16 (formerly designated Table 310.15(B)(16)) provides the allowable ampacities of insulated conductors rated up to and including 2000 volts. To read the table accurately, you must verify that the installation matches the table's specific baseline engineering assumptions:

Raceway, Cable, or Earth: Conductors are installed in a raceway, cable, or directly buried in earth.

Bundling Limit: Not more than three current-carrying conductors are contained within the raceway or cable.

Ambient Temperature: The ambient surrounding temperature is exactly 30°C (86°F) . STRUCTURE OF NEC TABLE 310.16

  • ┌──────────────┬───────────────────────────────┬───────────────────────────────┐
  • │ Temperature │ Copper Conductors │ Aluminum / Cu-Clad Aluminum │
  • │ Rating │ Typical Wire Types │ Typical Wire Types │
  • ├──────────────┼───────────────────────────────┼───────────────────────────────┤
  • │ 60°C (140°F) │ TW, UF │ TW, UF │
  • │ 75°C (167°F) │ RHW, THHW, THW, THWN, XHHW │ RHW, THHW, THW, THWN, XHHW │
  • │ 90°C (194°F) │ THHN, THWN-2, XHHW-2, RHW-2 │ THHN, THWN-2, XHHW-2, RHW-2 │
  • └──────────────┴───────────────────────────────┴───────────────────────────────┘
  • Core Conductor Ampacities (NEC Table 310.16 Quick Reference)

The following table compiles allowable ampacities for the most heavily tested copper and aluminum conductor sizes under baseline conditions (ambient 30°C, 3 or fewer current-carrying conductors):

Conductor Size Copper 60°C (TW, UF) Copper 75°C (THWN, XHHW) Copper 90°C (THHN, XHHW-2) Aluminum 60°C (TW, UF) Aluminum 75°C (THWN, XHHW) Aluminum 90°C (THHN, XHHW-2)

  • 14 AWG 15 A* 20 A* 25 A* — — —
  • 12 AWG 20 A* 25 A* 30 A* 15 A* 20 A* 25 A*
  • 10 AWG 30 A* 35 A* 40 A* 25 A* 30 A* 35 A*
  • 8 AWG 40 A 50 A 55 A 35 A 40 A 45 A
  • 6 AWG 55 A 65 A 75 A 40 A 50 A 60 A
  • 4 AWG 70 A 85 A 95 A 55 A 65 A 75 A
  • 3 AWG 85 A 100 A 115 A 65 A 75 A 85 A
  • 2 AWG 95 A 115 A 130 A 75 A 90 A 100 A
  • 1 AWG 110 A 130 A 145 A 85 A 100 A 115 A
  • 1/0 AWG 125 A 150 A 170 A 100 A 120 A 135 A
  • 2/0 AWG 145 A 175 A 195 A 115 A 135 A 150 A
  • 3/0 AWG 165 A 200 A 225 A 130 A 155 A 175 A
  • 4/0 AWG 195 A 230 A 260 A 150 A 180 A 205 A
  • 250 kcmil 215 A 255 A 290 A 170 A 205 A 230 A
  • 350 kcmil 260 A 310 A 350 A 210 A 250 A 280 A
  • 500 kcmil 320 A 380 A 430 A 260 A 310 A 350 A

The Small Conductor Rule ( Asterisk in Table 310.16): * Notice that although 14 AWG copper has a 75°C ampacity of 20A and a 90°C ampacity of 25A, NEC 240.4(D) strictly caps the maximum overcurrent protection for 14 AWG at 15 amperes . Similarly, 12 AWG copper is capped at 20 amperes , and 10 AWG copper is capped at 30 amperes . For aluminum, 12 AWG is capped at 15 amperes , and 10 AWG is capped at 25 amperes .

The 90°C Insulation and 75°C Terminal Coordination Principle

One of the greatest puzzles for apprentice electricians is understanding why commercial contractors exclusively purchase 90°C-rated wire (such as THHN/THWN-2) when virtually all commercial circuit breakers, switches, and panelboards have terminal lugs rated for only 75°C .

Terminal Temperature Limitations (NEC 110.14(C))

Under NEC 110.14(C)(1) , equipment termination provisions are coordinated with conductor ampacities as follows:

Circuits Rated 100A or Less (or 14 AWG through 1 AWG): Equipment terminals are rated for 60°C , unless the equipment is specifically listed and marked for 75°C conductors. (Almost all modern commercial circuit breakers and disconnects are dual-marked 60°C/75°C).

Circuits Rated Over 100A (or Conductors Larger than 1 AWG): Equipment terminals are rated for 75°C .

90°C Equipment Terminals: Virtually non-existent in standard distribution equipment. Circuit breakers and distribution panelboards are tested and listed by Underwriters Laboratories (UL 489 and UL 67) with maximum heat dissipation calibrated to 75°C terminations.

If equipment terminals are rated at 75°C, operating a conductor at 90°C would conduct excessive heat directly into the breaker's internal bimetallic mechanism, causing nuisance tripping or terminal failure. Therefore, the final continuous operating current flowing into the terminal can never exceed the conductor's 75°C ampacity column .

The Derating Advantage: Why We Use 90°C Conductors

NEC 110.14(C) Rule: Conductors with temperature ratings higher than specified for terminations shall be permitted to be used for ampacity adjustment, correction, or both. This means you can use the higher ampacity from the 90°C column as your starting point when calculating derating factors.

Consider this mathematical comparison:

Suppose you need to install four current-carrying conductors in EMT in an ambient temperature of 40°C (104°F) to serve an 80-ampere noncontinuous load . Equipment terminals are marked 75°C.

If you select 4 AWG THW Copper (75°C base = 85A): Derated Ampacity = 85 A × 0.88 (temp) × 0.80 (bundling) = 59.8 A Result: 59.8A is far below the required 80A. You would have to upsize to 2 AWG wire, increasing material and conduit costs!

If you select 4 AWG THHN Copper (90°C base = 95A): Derated Ampacity = 95 A × 0.91 (temp) × 0.80 (bundling) = 69.2 A

With 3 AWG THHN (115A base):

Derated Ampacity = 115 A × 0.91 × 0.80 = 83.7 A

Because 83.7A does not exceed the 75°C terminal rating for 3 AWG (100A), the conductor is fully compliant!

Using 90°C wire provides a high thermal buffer. You begin derating calculations at the top of the thermal ladder (90°C), absorbing bundling and temperature penalties before the ampacity falls below the 75°C terminal ceiling.

Practical Jobsite Scenarios & Common Exam Traps

Jobsite Scenario Technical Reality & Code Mandate Common PSI Exam Trap

Underground Parking Feeder: An electrician pulls 1/0 AWG single-rated THHN copper conductors through PVC conduit buried beneath a concrete slab. Violation of NEC 300.5(B) & 310.10(C): The interior of underground conduit is defined as a wet location. Single-rated THHN is rated for dry/damp locations only. Must use dual-rated THWN-2 or XHHW-2. Assuming that because the conduit is encased in concrete or underground, moisture cannot enter.

Solid 8 AWG in EMT: An installer pulls solid 8 AWG copper conductors into EMT raceway for a 40A subpanel feed. Violation of NEC 310.3(C): Conductors 8 AWG and larger installed in raceways must be stranded to avoid pull damage and work-hardening. Believing that solid conductors are permitted in any size if the conduit is properly sized.

Terminal Rating Confusion: An apprentice calculates that 1 AWG THHN copper has an ampacity of 145A (90°C column) and protects it with a 150A breaker on a standard 75°C panelboard with no derating factors. Violation of NEC 110.14(C): With no derating factors applied, the maximum allowable ampacity is dictated by the 75°C terminal rating, which is 130A for 1 AWG Cu. The breaker cannot exceed 150A unless complying with 240.4(B). Sizing the overcurrent device directly to the 90°C column when equipment terminals are rated 75°C.

Aluminum Lug Marking: An electrician terminates 250 kcmil compact aluminum conductors into a mechanical lug stamped with 'CU ONLY'. Violation of NEC 110.14: Aluminum conductors expand and contract at higher rates than copper. Terminating aluminum in copper-only lugs causes thermal loosening, arcing, and electrical fires. Lugs must be stamped AL7CU or AL9CU. Believing all mechanical screw lugs are universal for both copper and aluminum.