Study guide

2.4 Voltage Drop Principles & Single/Three-Phase Formulas

Colorado Journeyman Electrician Study Guide Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Colorado Electrical Licensing Laws, DORA Rules & Exam Logistics

1.1 Colorado Electrical Board, Licensure Tiers & Application Process 1.2 Senate Bill 25-165, Apprentice Supervision & Colorado Board Rules 1.3 Permitting, Inspection Procedures, Violations & Penalties 1.4 The Colorado PSI Exam: Open-Book Format, Time Management & Code Navigation

2 Chapter 2: Electrical Theory, Mathematics & Fundamental Concepts

2.1 Ohm's Law, Joule's Law & DC Circuit Analysis 2.2 AC Fundamentals: Inductance, Capacitance & Power Factor 2.3 Three-Phase Electrical Systems: Wye & Delta Configurations 2.4 Voltage Drop Principles & Single/Three-Phase Formulas

3 Chapter 3: General Installation Requirements — NEC Articles 90 & 110

3.1 NEC Structure, Arrangement & Article 90 Fundamentals 3.2 Key Article 100 Definitions for the Exam 3.3 Equipment Examination, Listing & Termination Temperature Limits 3.4 Working Space, Dedicated Electrical Space & Guarding

4 Chapter 4: Branch Circuits & Feeders — NEC Articles 210, 215 & 225

4.1 Branch-Circuit Ratings, Conductor Sizing & Multiwire Branch Circuits 4.2 Dwelling Unit Required Outlets & Receptacle Placement 4.3 Ground-Fault Circuit-Interrupter (GFCI) Protection 4.4 Arc-Fault Circuit-Interrupter (AFCI) Protection & Feeder Rules

5 Chapter 5: Services & Overcurrent Protection — NEC Articles 230, 240 & 242

5.1 Service Conductors, Clearances & Overhead/Underground Drops 5.2 Service Disconnecting Means, Ratings & Surge Protection 5.3 Overcurrent Protection Fundamentals & Standard Ratings 5.4 Feeder & Transformer Tap Rules

6 Chapter 6: Grounding and Bonding — NEC Article 250 Part I (Systems & Electrodes)

6.1 Grounding vs. Bonding: Principles, Functions & Article 250 Architecture 6.2 Grounded Conductors, Main Bonding Jumpers & System Bonding Jumpers 6.3 The Grounding Electrode System 6.4 Grounding Electrode Conductor (GEC) Sizing & Installation

7 Chapter 7: Grounding and Bonding — NEC Article 250 Part II (Equipment & Special Systems)

7.1 Equipment Grounding Conductors (EGC) Types & Identification 7.2 Sizing the Equipment Grounding Conductor 7.3 Separately Derived Systems 7.4 Grounding & Bonding at Separate Buildings or Structures

8 Chapter 8: Wiring Methods & Materials — NEC Chapter 3

8.1 General Wiring Requirements & Underground Installations 8.2 Nonmetallic and Armored Cable Assemblies 8.3 Metallic and Nonmetallic Raceways 8.4 Cable Trays, Wireways, Auxiliary Gutters & Surface Raceways

9 Chapter 9: Conductors, Ampacity & Wire Sizing — NEC Article 310

9.1 Conductor Properties, Insulation Types & NEC Table 310.16 9.2 Temperature Correction Factors 9.3 Conductor Bundling & Adjustment Factors 9.4 Comprehensive Conductor Sizing & Terminal Temperature Coordination

10 Chapter 10: Box Fill, Conduit Fill & Pull Box Calculations

10.1 Outlet and Device Box Fill Calculations — NEC 314.16(A) & (B) 10.2 Conduit Fill Calculations — Chapter 9 Tables 1, 4, 5 & Annex C 10.3 Pull and Junction Box Sizing for Conductors 4 AWG and Larger — NEC 314.28 10.4 Practical Enclosure & Raceway Sizing Exam Scenarios

11 Chapter 11: Load Calculations — Dwellings & Commercial Buildings — NEC Article 120

11.1 General Lighting, Small Appliance & Laundry Loads 11.2 Fixed Appliances, Dryers & Cooking Equipment Calculations 11.3 Standard vs. Optional Calculation Methods for Single-Family Dwellings 11.4 Commercial & Multifamily Load Calculations

12 Chapter 12: Motors, Motor Circuits & Controllers — NEC Article 430

12.1 Motor Nameplate vs. NEC Tables & Motor Full-Load Current 12.2 Sizing Motor Branch-Circuit Conductors & Overload Protection 12.3 Motor Branch-Circuit Short-Circuit & Ground-Fault Protection 12.4 Motor Feeders, Disconnecting Means & Controllers

13 Chapter 13: Transformers, Distribution & Utilization Equipment

13.1 Transformer Overcurrent Protection & Installation — NEC Article 450 13.2 Panelboards, Switchboards & Switchgear — NEC Article 408 13.3 Luminaires, Appliances & Fixed Electric Space Heating 13.4 Generators, Transfer Switches & Standby Systems

14 Chapter 14: Special Occupancies, Renewable Energy & Modern Technologies

14.1 Hazardous (Classified) Locations — NEC Articles 500-516 14.2 Health Care Facilities & Places of Assembly — NEC Articles 517 & 518 14.3 Swimming Pools, Spas, Hot Tubs & Fountains — NEC Article 680 14.4 Solar Photovoltaic (PV) Systems & Energy Storage — NEC Articles 690, 705 & 706

2.4 Voltage Drop Principles & Single/Three-Phase Formulas

Key Takeaways Explain This Topic AI

Voltage drop represents the loss of electrical potential across circuit conductors caused by natural conductor resistance and current flow (VD = I × R), resulting in reduced equipment efficiency, motor overheating, and nuisance tripping.

NEC Informational Notes 210.19(A) and 215.2(A) recommend limiting voltage drop to a maximum of 3% on branch circuits or feeders, and a maximum of 5% total combined drop from the service point to the farthest outlet.

The standard Ohm's-law-derived circular mil formulas are VD = (2 × K × I × L) / CM for single-phase two-wire circuits and VD = (1.732 × K × I × L) / CM for balanced three-phase circuits.

The resistivity constant (K) represents the resistance of one circular mil-foot of conductor at 75°C: 12.9 ohms-cmil/ft for uncoated copper and 21.2 ohms-cmil/ft for aluminum.

When ungrounded conductors are increased in size to compensate for voltage drop, NEC 250.122(B) mandates that wire-type equipment grounding conductors (EGC) must be proportionately increased in size according to their circular mil area.

Last updated: September 2026

2.4 Voltage Drop Principles & Single/Three-Phase Formulas

Quick Answer: Voltage drop ( V D V_D V D ​ ) is the reduction in electrical potential along the length of circuit wiring caused by conductor resistance: V D = I × R conductor V_D = I \times R_{\text{conductor}} V D ​ = I × R conductor ​ . National Electrical Code (NEC) Informational Notes 210.19(A) and 215.2(A) recommend limiting voltage drop to a maximum of 3 % 3\% 3% on branch circuits or feeders , and 5 % 5\% 5% total from the service entrance to the farthest outlet. For single-phase circuits, voltage drop is calculated as V D = ( 2 × K × I × L ) / CM V_D = (2 \times K \times I \times L) / \text{CM} V D ​ = ( 2 × K × I × L ) / CM , while balanced three-phase circuits use V D = ( 1.732 × K × I × L ) / CM V_D = (1.732 \times K \times I \times L) / \text{CM} V D ​ = ( 1.732 × K × I × L ) / CM . Conductor resistivity constants ( K K K ) at 75 ∘ C 75^\circ\text{C} 7 5 ∘ C are 12.9 12.9 12.9 for copper and 21.2 21.2 21.2 for aluminum . Under NEC 250.122(B), whenever phase conductors are upsized for voltage drop, the equipment grounding conductor (EGC) must be increased proportionately in circular mil area.

Electrical conductors are not perfect superconductors; they possess intrinsic electrical resistance that converts electrical energy into heat as current flows. Over short wiring runs inside a residential dwelling, this resistance is negligible. However, in sprawling commercial distribution centers, long parking lot lighting runs, agricultural irrigation pivots, and mountain facilities across Colorado where circuits extend hundreds of feet from the service panel, voltage drop becomes a dominant engineering constraint. Sizing conductors solely based on the ampacity tables in NEC 310.16 without verifying voltage drop frequently results in code inspection failures, damaged motor windings, and unreliable electronic control systems.

Physics of Voltage Drop: Ohm's Law on Conductor Runs

The resistance of any electrical conductor depends on four physical properties:

Material Resistivity ( ρ \rho ρ ): Copper conducts electricity with lower resistance than aluminum.

Length ( L L L ): Conductor resistance is directly proportional to length. Doubling the distance doubles the resistance.

Cross-Sectional Area ( A A A ): Conductor resistance is inversely proportional to cross-sectional area. Doubling the circular mil area halves the resistance.

Operating Temperature ( T T T ): Metal conductors possess a positive temperature coefficient; resistance increases as conductor temperature rises. R conductor = ρ × L A R_{\text{conductor}} = \frac{\rho \times L}{A} R conductor ​ = A ρ × L ​

Applying Ohm's law ( V = I × R V = I \times R V = I × R ), when current ( I I I ) flows through conductor resistance ( R R R ), a voltage drop ( V D V_D V D ​ ) develops across the wire. The voltage available at the utilization load ( V load V_{\text{load}} V load ​ ) is reduced: V load = V source − V D V_{\text{load}} = V_{\text{source}} - V_D V load ​ = V source ​ − V D ​

Operational Consequences of Excessive Voltage Drop

Induction Motors: Electric motors deliver mechanical shaft horsepower ( P = V × I P = V \times I P = V × I ). When terminal voltage drops, induction motors draw higher continuous current to satisfy mechanical load demands. Because internal heating follows I 2 R I^2 R I 2 R , a 10 % 10\% 10% voltage reduction increases motor winding operating temperatures by approximately 15 % 15\% 15% to 20 % 20\% 20% , rapidly breaking down winding insulation and causing premature motor burnout.

Resistive Heating Loads: Heat dissipation in electric baseboards, water heaters, and duct heaters drops according to the square of the voltage ( P = V 2 / R P = V^2 / R P = V 2 / R ). A 10 % 10\% 10% voltage drop slashes heating output by 19 % 19\% 19% ( 0.90 2 = 0.81 0.90^2 = 0.81 0.9 0 2 = 0.81 ).

Lighting Systems: Undervoltage in legacy incandescent and high-intensity discharge (HID) fixtures cuts lumen output drastically. In modern electronic LED drivers, undervoltage can cause high-frequency driver flicker, failure to strike, or internal power supply burnout.

Microprocessor & Digital Controls: Industrial programmable logic controllers (PLCs), variable frequency drives (VFDs), and sensitive computerized relays experience nuisance resets, erratic faults, and communication dropouts when line voltage sags below operating thresholds.

National Electrical Code Standards: Informational Notes vs. Mandatory Rules

One of the most heavily tested legal distinctions on the Colorado Journeyman Electrician exam is whether voltage drop is a mandatory requirement or an advisory recommendation:

The Advisory 3% and 5% Rule

NEC 210.19(A) Informational Note No. 4 (Branch Circuits): Conductors for branch circuits sized to prevent a voltage drop exceeding 3 % 3\% 3% at the farthest outlet used for power, heating, or lighting, and where the maximum total voltage drop on both feeders and branch circuits to the farthest outlet does not exceed 5 % 5\% 5% , provide reasonable efficiency of operation.

NEC 215.2(A)(1) Informational Note No. 2 (Feeders): Conductors for feeders sized to prevent a voltage drop exceeding 3 % 3\% 3% at the farthest outlet, and where the maximum total voltage drop on both feeders and branch circuits does not exceed 5 % 5\% 5% , provide reasonable efficiency of operation.

Legal Code Mandate Rule (NEC 90.5(C)): Informational Notes are explanatory and non-mandatory. Therefore, on a standard commercial branch circuit or feeder, an electrical inspector cannot fail an installation under the national model code solely for exceeding 3 % 3\% 3% voltage drop unless the local Authority Having Jurisdiction (AHJ) has enacted an explicit local ordinance amendment making it mandatory, or the approved architectural/engineering blueprints explicitly enforce voltage drop compliance.

Mandatory Voltage Drop Rules in the NEC

While general branch circuits and feeders carry advisory notes, the NEC mandates strict, enforceable voltage drop limits in specific critical articles:

NEC Article Application Mandatory Voltage Drop Limit

NEC 695.7 Fire Pump Motor Run Voltage Max 5 % 5\% 5% voltage drop at fire pump controller terminals under normal operating full-load current.

NEC 695.7 Fire Pump Motor Starting Voltage Max 15 % 15\% 15% voltage drop at controller terminals during across-the-line locked-rotor motor starting.

NEC 647.4(D) Sensitive Electronic Equipment Max 1.5 % 1.5\% 1.5% on branch circuits, and max 2.5 % 2.5\% 2.5% total combined feeder and branch circuit drop.

NEC 555.33(A) Marinas, Boat Harbors & Dock Receptacles Max 5 % 5\% 5% total voltage drop to the farthest shore-power receptacle.

Maximum Permissible Voltage Drop Table

Nominal System Voltage Maximum 3% Drop (Feeder or Branch) Maximum 5% Total System Drop Minimum Load Voltage at 5% Drop

120 V 120\text{ V} 120 V (1-Phase) 3.60 V 3.60\text{ V} 3.60 V 6.00 V 6.00\text{ V} 6.00 V 114.00 V 114.00\text{ V} 114.00 V

208 V 208\text{ V} 208 V (3-Phase / 1-Phase) 6.24 V 6.24\text{ V} 6.24 V 10.40 V 10.40\text{ V} 10.40 V 197.60 V 197.60\text{ V} 197.60 V

240 V 240\text{ V} 240 V (1-Phase) 7.20 V 7.20\text{ V} 7.20 V 12.00 V 12.00\text{ V} 12.00 V 228.00 V 228.00\text{ V} 228.00 V

277 V 277\text{ V} 277 V (1-Phase) 8.31 V 8.31\text{ V} 8.31 V 13.85 V 13.85\text{ V} 13.85 V 263.15 V 263.15\text{ V} 263.15 V

480 V 480\text{ V} 480 V (3-Phase) 14.40 V 14.40\text{ V} 14.40 V 24.00 V 24.00\text{ V} 24.00 V 456.00 V 456.00\text{ V} 456.00 V

The Circular Mil Method & Conductor Sizing Formulas

The standard method utilized on licensing examinations to calculate voltage drop and size conductors is the Circular Mil (CM) formula .

Understanding Circular Mils (CM)

A mil is an imperial unit of length equal to one-thousandth of an inch ( 1 mil = 0.001 in 1\text{ mil} = 0.001\text{ in} 1 mil = 0.001 in ). A circular mil (CM) is the cross-sectional area of a circle with a diameter of exactly 1 mil 1\text{ mil} 1 mil . Area (CM) = [ Diameter in mils ] 2 \text{Area (CM)} = [\text{Diameter in mils}]^2 Area (CM) = [ Diameter in mils ] 2

For example, a solid wire with a diameter of 0.100 inches 0.100\text{ inches} 0.100 inches ( 100 mils 100\text{ mils} 100 mils ) has a cross-sectional area of 100 2 = 10,000 circular mils 100^2 = 10{,}000\text{ circular mils} 10 0 2 = 10 , 000 circular mils . Large industrial conductors are designated directly in thousand circular mils ( kcmil or MCM ), where 1 kcmil = 1,000 CM 1\text{ kcmil} = 1{,}000\text{ CM} 1 kcmil = 1 , 000 CM ( 250 kcmil = 250,000 CM 250\text{ kcmil} = 250{,}000\text{ CM} 250 kcmil = 250 , 000 CM ).

Conductor Material Resistivity: The K Factor

The constant K K K represents the direct current resistance in ohms of a conductor wire measuring one circular mil in cross-section and one foot in length ( 1 cmil-ft 1\text{ cmil-ft} 1 cmil-ft ) operating at an elevated temperature of 75 ∘ C 75^\circ\text{C} 7 5 ∘ C :

  • Conductor Material Standard Exam K K K Value at 75 ∘ C 75^\circ\text{C} 7 5 ∘ C Simplified Value (Trade Text)
  • Uncoated Copper (Cu) 12.9 12.9 12.9 12.0 12.0 12.0
  • Aluminum (Al) / Copper-Clad Al 21.2 21.2 21.2 20.0 20.0 20.0

Exam Standard: Always use K = 12.9 K = 12.9 K = 12.9 for copper and K = 21.2 K = 21.2 K = 21.2 for aluminum on PSI Colorado Journeyman licensing calculations unless an explicit problem prompt states otherwise.

Standard Formulas: Single-Phase and Three-Phase Circuits SINGLE-PHASE (2-Wire) THREE-PHASE (Balanced)

Voltage Drop: VD = (2 × K × I × L) / CM VD = (1.732 × K × I × L) / CM

Conductor Size: CM = (2 × K × I × L) / VD CM = (1.732 × K × I × L) / VD

Where:

V D V_D V D ​ = Voltage drop in volts.

K K K = Resistivity constant ( 12.9 12.9 12.9 for copper, 21.2 21.2 21.2 for aluminum).

I I I = Load current in amperes.

L L L = One-way length of the circuit run in feet (from source to load).

CM \text{CM} CM = Conductor cross-sectional area in circular mils (from NEC Chapter 9, Table 8).

The multiplier 2 2 2 in the single-phase formula accounts for the round-trip distance of the complete circuit loop (out on the ungrounded conductor and back on the neutral/return conductor).

The multiplier 1.732 1.732 1.732 ( 3 \sqrt{3} 3 ​ ) in the three-phase formula accounts for the 120 ∘ 120^\circ 12 0 ∘ vector relationship between phase conductors in a balanced three-phase system.

NEC Chapter 9 Table 8: Conductor Properties & Resistance Values

To translate calculated circular mils into actual American Wire Gauge (AWG) or kcmil conductor sizes, refer to NEC Chapter 9, Table 8 (Conductor Properties) :

Conductor Size (AWG or kcmil) Circular Mil Area (CM) Copper Resistance ( Ω / 1,000 ft \Omega / 1{,}000\text{ ft} Ω/1 , 000 ft ) at 75 ∘ C 75^\circ\text{C} 7 5 ∘ C Aluminum Resistance ( Ω / 1,000 ft \Omega / 1{,}000\text{ ft} Ω/1 , 000 ft ) at 75 ∘ C 75^\circ\text{C} 7 5 ∘ C

  • 14 AWG 4,110 4{,}110 4 , 110 3.07 3.07 3.07 5.06 5.06 5.06
  • 12 AWG 6,530 6{,}530 6 , 530 1.93 1.93 1.93 3.18 3.18 3.18
  • 10 AWG 10,380 10{,}380 10 , 380 1.21 1.21 1.21 2.00 2.00 2.00
  • 8 AWG 16,510 16{,}510 16 , 510 0.764 0.764 0.764 1.26 1.26 1.26
  • 6 AWG 26,240 26{,}240 26 , 240 0.491 0.491 0.491 0.808 0.808 0.808
  • 4 AWG 41,740 41{,}740 41 , 740 0.308 0.308 0.308 0.508 0.508 0.508
  • 3 AWG 52,620 52{,}620 52 , 620 0.245 0.245 0.245 0.403 0.403 0.403
  • 2 AWG 66,360 66{,}360 66 , 360 0.194 0.194 0.194 0.319 0.319 0.319
  • 1 AWG 83,690 83{,}690 83 , 690 0.154 0.154 0.154 0.253 0.253 0.253
  • 1/0 AWG 105,600 105{,}600 105 , 600 0.122 0.122 0.122 0.201 0.201 0.201
  • 2/0 AWG 133,100 133{,}100 133 , 100 0.0967 0.0967 0.0967 0.159 0.159 0.159
  • 3/0 AWG 167,800 167{,}800 167 , 800 0.0766 0.0766 0.0766 0.126 0.126 0.126
  • 4/0 AWG 211,600 211{,}600 211 , 600 0.0608 0.0608 0.0608 0.100 0.100 0.100
  • 250 kcmil 250,000 250{,}000 250 , 000 0.0515 0.0515 0.0515 0.0847 0.0847 0.0847
  • 300 kcmil 300,000 300{,}000 300 , 000 0.0429 0.0429 0.0429 0.0707 0.0707 0.0707
  • 350 kcmil 350,000 350{,}000 350 , 000 0.0367 0.0367 0.0367 0.0605 0.0605 0.0605
  • 500 kcmil 500,000 500{,}000 500 , 000 0.0258 0.0258 0.0258 0.0424 0.0424 0.0424
  • Worked Step-by-Step Sizing Examples for Long Branch Runs and Feeders
  • Worked Example 1: Single-Phase Long Branch Circuit Sizing (Parking Lot Lighting)

Scenario: A 120 V 120\text{ V} 120 V , single-phase branch circuit feeds a bank of exterior parking lot LED fixtures drawing a continuous load of 16 A 16\text{ A} 16 A . The one-way distance from the panelboard to the center of the lighting load is 175 feet 175\text{ feet} 175 feet . Copper conductors will be installed. What minimum size conductor must be selected to maintain voltage drop within the NEC recommended 3 % 3\% 3% limit?

Step 1: Determine Maximum Permissible Voltage Drop ( V D V_D V D ​ ): V D -allowable = 120 V × 0.03 = 3.60 V V_{D\text{-allowable}} = 120\text{ V} \times 0.03 = 3.60\text{ V} V D -allowable ​ = 120 V × 0.03 = 3.60 V

Step 2: Apply the Single-Phase Circular Mil Formula: CM = 2 × K × I × L V D -allowable = 2 × 12.9 × 16 A × 175 ft 3.60 V \text{CM} = \frac{2 \times K \times I \times L}{V_{D\text{-allowable}}} = \frac{2 \times 12.9 \times 16\text{ A} \times 175\text{ ft}}{3.60\text{ V}} CM = V D -allowable ​ 2 × K × I × L ​ = 3.60 V 2 × 12.9 × 16 A × 175 ft ​ Numerator = 2 × 12.9 × 16 × 175 = 72,240 \text{Numerator} = 2 \times 12.9 \times 16 \times 175 = 72{,}240 Numerator = 2 × 12.9 × 16 × 175 = 72 , 240 CM = 72,240 3.60 = 20,066.67 CM \text{CM} = \frac{72{,}240}{3.60} = 20{,}066.67\text{ CM} CM = 3.60 72 , 240 ​ = 20 , 066.67 CM

Step 3: Select Conductor Size from NEC Chapter 9 Table 8:

10 AWG = 10,380 CM 10{,}380\text{ CM} 10 , 380 CM (Too small)

8 AWG = 16,510 CM 16{,}510\text{ CM} 16 , 510 CM (Too small; 16,510 < 20,067 16{,}510 < 20{,}067 16 , 510 < 20 , 067 )

6 AWG = 26,240 CM 26{,}240\text{ CM} 26 , 240 CM (Sufficient! 26,240 > 20,067 26{,}240 > 20{,}067 26 , 240 > 20 , 067 )

Conclusion: A 6 AWG copper conductor is required.

Mandatory Proportional Equipment Grounding Conductor Adjustment: NEC 250.122(B)

CRITICAL EXAM TRAP — NEC 250.122(B): Where ungrounded conductors are increased in size from the minimum size that has sufficient ampacity for the circuit (for example, upsizing from 12 AWG to 6 AWG solely for voltage drop), the wire-type equipment grounding conductor (EGC) shall be increased in size proportionately according to the circular mil area of the ungrounded conductors.

Let's apply NEC 250.122(B) to the example above:

Original required wire size for a 20 A 20\text{ A} 20 A circuit breaker per NEC 240.4(D): 12 AWG copper ( 6,530 CM 6{,}530\text{ CM} 6 , 530 CM ).

Standard minimum EGC for a 20 A 20\text{ A} 20 A circuit per NEC Table 250.122: 12 AWG copper ( 6,530 CM 6{,}530\text{ CM} 6 , 530 CM ).

Upsized ungrounded conductor: 6 AWG copper ( 26,240 CM 26{,}240\text{ CM} 26 , 240 CM ).

Proportional Multiplier: 26,240 / 6,530 = 4.018 26{,}240 / 6{,}530 = 4.018 26 , 240/6 , 530 = 4.018 .

Required EGC Size in Circular Mils: 6,530 × 4.018 = 26,240 CM 6{,}530 \times 4.018 = 26{,}240\text{ CM} 6 , 530 × 4.018 = 26 , 240 CM .

Checking Table 8: The equipment grounding conductor must also be upsized from 12 AWG to 6 AWG copper !

Worked Example 2: Three-Phase Feeder Calculation (Commercial HVAC Subpanel)

Scenario: A 480 V 480\text{ V} 480 V , balanced 3-phase, 4-wire commercial feeder supplies an 80 A 80\text{ A} 80 A HVAC subpanel located 350 feet 350\text{ feet} 350 feet away from the main service switchgear. The feeder conductors are 3 AWG copper 3\text{ AWG copper} 3 AWG copper ( 52,620 CM 52{,}620\text{ CM} 52 , 620 CM ). What is the calculated voltage drop across this feeder, what percentage drop does it represent, and does it satisfy the NEC feeder recommendation?

Step 1: Apply the Three-Phase Voltage Drop Formula: V D = 1.732 × K × I × L CM = 1.732 × 12.9 × 80 A × 350 ft 52,620 CM V_D = \frac{1.732 \times K \times I \times L}{\text{CM}} = \frac{1.732 \times 12.9 \times 80\text{ A} \times 350\text{ ft}}{52{,}620\text{ CM}} V D ​ = CM 1.732 × K × I × L ​ = 52 , 620 CM 1.732 × 12.9 × 80 A × 350 ft ​ Numerator = 1.732 × 12.9 × 80 × 350 = 625,598.4 \text{Numerator} = 1.732 \times 12.9 \times 80 \times 350 = 625{,}598.4 Numerator = 1.732 × 12.9 × 80 × 350 = 625 , 598.4 V D = 625,598.4 52,620 = 11.89 V V_D = \frac{625{,}598.4}{52{,}620} = 11.89\text{ V} V D ​ = 52 , 620 625 , 598.4 ​ = 11.89 V

Step 2: Calculate Percentage Voltage Drop: % V D = ( 11.89 V 480 V ) × 100 = 2.48 % \%\,V_D = \left( \frac{11.89\text{ V}}{480\text{ V}} \right) \times 100 = 2.48\% % V D ​ = ( 480 V 11.89 V ​ ) × 100 = 2.48%

Step 3: Evaluate Code Compliance:

Allowable 3 % 3\% 3% feeder voltage drop at 480 V 480\text{ V} 480 V is: 480 × 0.03 = 14.40 V 480 \times 0.03 = 14.40\text{ V} 480 × 0.03 = 14.40 V .

Because the actual drop of 11.89 V 11.89\text{ V} 11.89 V ( 2.48 % 2.48\% 2.48% ) is less than 14.40 V 14.40\text{ V} 14.40 V ( 3 % 3\% 3% ), the installation complies with NEC Informational Note 215.2(A)(1).

Worked Example 3: Solving for Maximum Permissible Circuit Length (L)

Frequently on the Colorado exam, questions ask for the maximum distance a circuit can be run before exceeding a specified voltage drop percentage. Rearrange the voltage drop equation to solve for length ( L L L ): L = V D × CM 2 × K × I (Single-Phase) L = \frac{V_D \times \text{CM}}{2 \times K \times I} \quad \text{(Single-Phase)} L = 2 × K × I V D ​ × CM ​ (Single-Phase) L = V D × CM 1.732 × K × I (Three-Phase) L = \frac{V_D \times \text{CM}}{1.732 \times K \times I} \quad \text{(Three-Phase)} L = 1.732 × K × I V D ​ × CM ​ (Three-Phase)

Scenario: A 240 V 240\text{ V} 240 V , single-phase residential heat pump branch circuit draws 28 A 28\text{ A} 28 A using 8 AWG copper 8\text{ AWG copper} 8 AWG copper ( 16,510 CM 16{,}510\text{ CM} 16 , 510 CM ). What is the maximum distance the circuit can run from the main service panelboard without exceeding a 3 % 3\% 3% voltage drop?

Step 1: Calculate Permissible Voltage Drop ( V D V_D V D ​ ): V D = 240 V × 0.03 = 7.20 V V_D = 240\text{ V} \times 0.03 = 7.20\text{ V} V D ​ = 240 V × 0.03 = 7.20 V

Step 2: Solve for Maximum Length ( L L L ): L = 7.20 V × 16,510 CM 2 × 12.9 × 28 A = 118,872 722.4 = 164.55 feet L = \frac{7.20\text{ V} \times 16{,}510\text{ CM}}{2 \times 12.9 \times 28\text{ A}} = \frac{118{,}872}{722.4} = 164.55\text{ feet} L = 2 × 12.9 × 28 A 7.20 V × 16 , 510 CM ​ = 722.4 118 , 872 ​ = 164.55 feet

Answer: The maximum run distance is approximately 164 feet 164\text{ feet} 164 feet .

Alternative Voltage Drop Calculation Method: Direct Resistance (NEC Chapter 9 Table 8)

Instead of the circular mil formula, electricians can use conductor resistance values directly from NEC Chapter 9, Table 8 (Column 8: Ohms per 1,000 ft 1{,}000\text{ ft} 1 , 000 ft at 75 ∘ C 75^\circ\text{C} 7 5 ∘ C ): V D = 2 × I × L × ( R Table 8 1,000 ) (Single-Phase) V_D = 2 \times I \times L \times \left( \frac{R_{\text{Table 8}}}{1{,}000} \right) \quad \text{(Single-Phase)} V D ​ = 2 × I × L × ( 1 , 000 R Table 8 ​ ​ ) (Single-Phase) V D = 1.732 × I × L × ( R Table 8 1,000 ) (Three-Phase) V_D = 1.732 \times I \times L \times \left( \frac{R_{\text{Table 8}}}{1{,}000} \right) \quad \text{(Three-Phase)} V D ​ = 1.732 × I × L × ( 1 , 000 R Table 8 ​ ​ ) (Three-Phase)

Both formulas yield virtually identical results because R Table 8 / 1,000 R_{\text{Table 8}} / 1{,}000 R Table 8 ​ /1 , 000 represents K / CM K / \text{CM} K / CM .

Colorado Journeyman Exam Traps & Calculation Pitfalls

Trap 1: Double-Counting the Distance Multiplier: The single-phase formula contains a multiplier of 2 2 2 ( 2 × K × I × L 2 \times K \times I \times L 2 × K × I × L ) specifically to account for the return conductor. In the formula, L L L is strictly the one-way distance from the panel to the load. If a problem states "the one-way distance is 200 feet," plug in L = 200 L = 200 L = 200 . Do NOT multiply the length by 2 before plugging it in, or your calculated drop will be double the actual value.

Trap 2: Forgetting the Proportional EGC Upsizing Rule (NEC 250.122(B)): Many candidates correctly calculate the upsized ungrounded conductor size (e.g., upsizing from 10 AWG to 4 AWG) but fail the follow-up question asking for the required equipment grounding conductor size. Sizing the EGC from Table 250.122 without applying the proportional circular mil increase violates NEC 250.122(B).

Trap 3: Using Aluminum K for Copper or Vice Versa: Always verify the wire metal specified in the problem statement. Using K = 12.9 K = 12.9 K = 12.9 for an aluminum conductor results in an answer that is 40 % 40\% 40% too small, leading to an undersized wire and an incorrect exam answer.

Trap 4: 3% vs. 5% Threshold Confusion: Read the question stem carefully. If it asks for the maximum drop on a "branch circuit" or "feeder," the limit is 3 % 3\% 3% . If it asks for the maximum allowable drop "from the service point to the farthest outlet" (combined system), the limit is 5 % 5\% 5% .