Study guide
5.4 Feeder & Transformer Tap Rules
Colorado Journeyman Electrician Study Guide Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Colorado Electrical Licensing Laws, DORA Rules & Exam Logistics
1.1 Colorado Electrical Board, Licensure Tiers & Application Process 1.2 Senate Bill 25-165, Apprentice Supervision & Colorado Board Rules 1.3 Permitting, Inspection Procedures, Violations & Penalties 1.4 The Colorado PSI Exam: Open-Book Format, Time Management & Code Navigation
2 Chapter 2: Electrical Theory, Mathematics & Fundamental Concepts
2.1 Ohm's Law, Joule's Law & DC Circuit Analysis 2.2 AC Fundamentals: Inductance, Capacitance & Power Factor 2.3 Three-Phase Electrical Systems: Wye & Delta Configurations 2.4 Voltage Drop Principles & Single/Three-Phase Formulas
3 Chapter 3: General Installation Requirements — NEC Articles 90 & 110
3.1 NEC Structure, Arrangement & Article 90 Fundamentals 3.2 Key Article 100 Definitions for the Exam 3.3 Equipment Examination, Listing & Termination Temperature Limits 3.4 Working Space, Dedicated Electrical Space & Guarding
4 Chapter 4: Branch Circuits & Feeders — NEC Articles 210, 215 & 225
4.1 Branch-Circuit Ratings, Conductor Sizing & Multiwire Branch Circuits 4.2 Dwelling Unit Required Outlets & Receptacle Placement 4.3 Ground-Fault Circuit-Interrupter (GFCI) Protection 4.4 Arc-Fault Circuit-Interrupter (AFCI) Protection & Feeder Rules
5 Chapter 5: Services & Overcurrent Protection — NEC Articles 230, 240 & 242
5.1 Service Conductors, Clearances & Overhead/Underground Drops 5.2 Service Disconnecting Means, Ratings & Surge Protection 5.3 Overcurrent Protection Fundamentals & Standard Ratings 5.4 Feeder & Transformer Tap Rules
6 Chapter 6: Grounding and Bonding — NEC Article 250 Part I (Systems & Electrodes)
6.1 Grounding vs. Bonding: Principles, Functions & Article 250 Architecture 6.2 Grounded Conductors, Main Bonding Jumpers & System Bonding Jumpers 6.3 The Grounding Electrode System 6.4 Grounding Electrode Conductor (GEC) Sizing & Installation
7 Chapter 7: Grounding and Bonding — NEC Article 250 Part II (Equipment & Special Systems)
7.1 Equipment Grounding Conductors (EGC) Types & Identification 7.2 Sizing the Equipment Grounding Conductor 7.3 Separately Derived Systems 7.4 Grounding & Bonding at Separate Buildings or Structures
8 Chapter 8: Wiring Methods & Materials — NEC Chapter 3
8.1 General Wiring Requirements & Underground Installations 8.2 Nonmetallic and Armored Cable Assemblies 8.3 Metallic and Nonmetallic Raceways 8.4 Cable Trays, Wireways, Auxiliary Gutters & Surface Raceways
9 Chapter 9: Conductors, Ampacity & Wire Sizing — NEC Article 310
9.1 Conductor Properties, Insulation Types & NEC Table 310.16 9.2 Temperature Correction Factors 9.3 Conductor Bundling & Adjustment Factors 9.4 Comprehensive Conductor Sizing & Terminal Temperature Coordination
10 Chapter 10: Box Fill, Conduit Fill & Pull Box Calculations
10.1 Outlet and Device Box Fill Calculations — NEC 314.16(A) & (B) 10.2 Conduit Fill Calculations — Chapter 9 Tables 1, 4, 5 & Annex C 10.3 Pull and Junction Box Sizing for Conductors 4 AWG and Larger — NEC 314.28 10.4 Practical Enclosure & Raceway Sizing Exam Scenarios
11 Chapter 11: Load Calculations — Dwellings & Commercial Buildings — NEC Article 120
11.1 General Lighting, Small Appliance & Laundry Loads 11.2 Fixed Appliances, Dryers & Cooking Equipment Calculations 11.3 Standard vs. Optional Calculation Methods for Single-Family Dwellings 11.4 Commercial & Multifamily Load Calculations
12 Chapter 12: Motors, Motor Circuits & Controllers — NEC Article 430
12.1 Motor Nameplate vs. NEC Tables & Motor Full-Load Current 12.2 Sizing Motor Branch-Circuit Conductors & Overload Protection 12.3 Motor Branch-Circuit Short-Circuit & Ground-Fault Protection 12.4 Motor Feeders, Disconnecting Means & Controllers
13 Chapter 13: Transformers, Distribution & Utilization Equipment
13.1 Transformer Overcurrent Protection & Installation — NEC Article 450 13.2 Panelboards, Switchboards & Switchgear — NEC Article 408 13.3 Luminaires, Appliances & Fixed Electric Space Heating 13.4 Generators, Transfer Switches & Standby Systems
14 Chapter 14: Special Occupancies, Renewable Energy & Modern Technologies
14.1 Hazardous (Classified) Locations — NEC Articles 500-516 14.2 Health Care Facilities & Places of Assembly — NEC Articles 517 & 518 14.3 Swimming Pools, Spas, Hot Tubs & Fountains — NEC Article 680 14.4 Solar Photovoltaic (PV) Systems & Energy Storage — NEC Articles 690, 705 & 706
5.4 Feeder & Transformer Tap Rules
Key Takeaways Explain This Topic AI
Under NEC 240.21, overcurrent protection is required at the point where a conductor receives its supply, except where specific feeder tap rules (240.21(B)) or transformer secondary tap rules (240.21(C)) permit smaller conductors without overcurrent protection at the tap point.
The 10-foot feeder tap rule (NEC 240.21(B)(1)) allows tap conductors up to 10 feet long provided their ampacity meets the calculated load and the rating of the device supplied, they do not extend beyond the equipment, and they are enclosed in an approved raceway.
The 25-foot feeder tap rule (NEC 240.21(B)(2)) allows tap conductors up to 25 feet long provided their ampacity is at least one-third (1/3) of the rating of the overcurrent device protecting the feeder, they terminate in a single OCPD, and they are protected from physical damage.
Under NEC 240.4(F), transformer secondary conductors are generally not protected by primary overcurrent devices; therefore, secondary conductors must comply with the transformer secondary tap rules of NEC 240.21(C), such as the 10-foot secondary tap rule (240.21(C)(2)).
Outside feeder taps of unlimited length (NEC 240.21(B)(5)) are permitted where conductors remain outdoors, are protected from physical damage, terminate in a single OCPD, and have an accessible disconnecting means.
Last updated: September 2026
5.4 Feeder & Transformer Tap Rules
Exam Fast Fact: When performing tap calculations on the exam, remember the two cornerstone ratios: the 10-foot feeder tap has no minimum 1/3 or 1/10 ampacity ratio when contained inside an enclosure/panelboard (it only needs to handle the calculated load and the rating of the device supplied), but must be at least 1/10 of the feeder OCPD if it leaves the enclosure. The 25-foot feeder tap strictly requires conductor ampacity to be at least one-third (1/3) of the feeder overcurrent device rating and must terminate in a single OCPD.
In standard electrical circuit design, every wire must be protected at the exact point where it receives its supply. If a 400A feeder supplies a distribution gutter, connecting a 10 AWG or 1 AWG conductor directly to that 400A busbar would create a catastrophic hazard: a short circuit or sustained overload on that smaller conductor would incinerate the wire long before the 400A upstream breaker tripped. However, installing a large, separate disconnect at every single junction point is physically and economically impractical. NEC 240.21 provides specific, rigorously engineered exceptions known as the Tap Rules .
The Supply Point Mandate & Definition of a Tap — NEC 240.21
NEC 240.21 states the general rule: Overcurrent protection shall be provided in each ungrounded circuit conductor at the point where the conductor receives its supply.
What is a Tap Conductor?
Article 240 defines a Tap Conductor as a conductor, other than a service conductor, that has overcurrent protection ahead of its point of supply that exceeds the value permitted for that conductor in NEC 240.4.
The Ironclad Anti-Tap Rule: You Cannot "Tap a Tap"
One of the most critical structural rules in electrical design is that a tap conductor cannot be tapped again . Every tap must originate from a full-sized conductor protected at its rated ampacity. Tapping a tap conductor results in cumulative impedance that prevents upstream overcurrent devices from clearing faults, and is an immediate Code violation under NEC 240.21. COMPLIANT FEEDER TAP CONFIGURATION:
- [400A Feeder Overcurrent Device]
- │
- ▼ (Full 400A Rated Feeder Conductors)
- ══════════════════════════════════════════════════════ (Distribution Gutter / Bus)
- │ │
- ▼ (10-ft Tap ≤ 10') ▼ (25-ft Tap ≤ 25')
- [Enclosed in Raceway] [Min. 1/3 Ampacity (≥ 133.3A)]
- │ │
- ▼ ▼
- [Terminates in Panelboard Main] [Terminates in Single Breaker ≤ Wire Ampacity]
- The 10-Foot Feeder Tap Rule — NEC 240.21(B)(1)
Conductors are permitted to be tapped to a feeder without overcurrent protection at the point of supply, provided the tap length does not exceed 10 feet (3.0 m) and satisfies all of the following conditions:
Ampacity Floor: The ampacity of the tap conductors must not be less than:
The calculated load on the circuits supplied by the tap conductors, AND
The rating of the device supplied by the tap conductors, or the rating of the overcurrent protective device at the termination of the tap conductors.
Physical Boundary: The tap conductors must not extend beyond the switchboard, switchgear, panelboard, disconnecting means, or control devices that they supply.
Physical Protection: The tap conductors must be enclosed in an approved raceway (such as EMT, RMC, or IMC) extending from the point of tap to the equipment enclosure, or installed within an enclosed switchboard, switchgear, or panelboard.
Field Installation 1/10th Rule: For field installations where the tap conductors leave the enclosure or vault in which the tap is made, the rating of the overcurrent device protecting the feeder must not exceed 10 times the tap conductor's ampacity (i.e., tap conductor ampacity ≥ 1 / 10 \ge 1/10 ≥ 1/10 of feeder OCPD).
Worked Example: Sizing a 10-Foot Tap
Problem: An electrical contractor taps a 400A commercial feeder in an auxiliary wireway to supply a 100A main breaker lighting panelboard located 6 feet away in EMT raceway. The calculated load is 78 amperes. What is the minimum conductor size required for this tap?
Analysis:
Check 1: Length is 6 feet ≤ 10 \le 10 ≤ 10 feet.
Check 2: Tap conductor ampacity must be at least the calculated load (78A) and at least the rating of the device supplied (100A main breaker).
Check 3: The wireway tap leaves the enclosure, so the 1/10th rule applies: 400 A ÷ 10 = 40 A 400\text{ A} \div 10 = 40\text{ A} 400 A ÷ 10 = 40 A .
Evaluation: The 100A main breaker rating is the highest threshold ( 100 A > 78 A > 40 A 100\text{ A} > 78\text{ A} > 40\text{ A} 100 A > 78 A > 40 A ).
Conductor Selection: From Table 310.16 (75°C column), a 3 AWG copper conductor is rated 100 amperes (or 1 AWG aluminum rated 100A). The tap conductors must have an ampacity of at least 100A.
The 25-Foot Feeder Tap Rule — NEC 240.21(B)(2)
Where the distance between the feeder tap and the terminating overcurrent device is between 10 feet and 25 feet (7.5 m) , the requirements become significantly more restrictive. To prevent severe overcurrent damage across extended wire runs, the Code enforces the famous One-Third (1/3) Ampacity Rule :
Length Limit: Conductor length must not exceed 25 feet (7.5 m) .
The 1/3 Ampacity Mandate: The ampacity of the tap conductors must be not less than one-third (1/3) of the rating of the overcurrent protective device protecting the feeder conductors: Tap Conductor Ampacity ≥ Feeder OCPD Rating 3 \text{Tap Conductor Ampacity} \ge \frac{\text{Feeder OCPD Rating}}{3} Tap Conductor Ampacity ≥ 3 Feeder OCPD Rating
Single OCPD Termination: The tap conductors must terminate in a single circuit breaker or single set of fuses that limits the load to the allowable ampacity of the tap conductors.
Physical Protection: The tap conductors must be protected from physical damage by being enclosed in an approved raceway or by other approved means.
Worked Example: Sizing a 25-Foot Tap
Problem: An electrician needs to run a 22-foot feeder tap from an 800-ampere feeder in a manufacturing plant to supply an enclosed circuit breaker. What is the minimum allowable conductor size and what is the maximum rating of the terminating circuit breaker?
Step 1: Calculate Minimum Tap Ampacity: Minimum Ampacity = 800 A 3 = 266.67 Amperes \text{Minimum Ampacity} = \frac{800\text{ A}}{3} = 266.67\text{ Amperes} Minimum Ampacity = 3 800 A = 266.67 Amperes
Step 2: Select Conductor from Table 310.16 (75°C Column):
- 250 kcmil copper is rated 255A. (255A < 266.67A — INSUFFICIENT! )
- 300 kcmil copper is rated 285A. (285A ≥ \ge ≥ 266.67A — COMPLIANT! )
Step 3: Select Terminating Overcurrent Device:
Condition 2 of 240.21(B)(2) states that the tap conductors must terminate in a single OCPD that limits the load to the ampacity of the tap conductors .
The tap conductor ampacity is 285A. Standard breaker sizes in 240.6(A) are 250A and 300A.
Can the electrician install a 300A breaker? NO! Under 240.21, you cannot use the next-size-up rule (240.4(B)) to protect tap conductors at their termination! The terminating OCPD cannot exceed the conductor ampacity.
Therefore, the maximum breaker rating for 300 kcmil (285A) is 250 amperes . If a 300A breaker is required for the load, the tap conductor must be upsized to 350 kcmil copper (rated 310A)!
Outside Feeder Taps of Unlimited Length — NEC 240.21(B)(5)
Where feeder taps are installed completely outside of a building, the risk of structural building fire caused by conductor overheating is substantially reduced. NEC 240.21(B)(5) allows outside taps of unlimited length , provided:
The tap conductors are protected from physical damage in an approved raceway, cable tray, or underground duct bank.
The tap conductors terminate at a single circuit breaker or single set of fuses that limits the load to the allowable ampacity of the conductors.
The overcurrent device is an integral part of a disconnecting means or immediately adjacent thereto.
The disconnecting means is installed outside the building or inside nearest the point of entrance of the conductors.
Tap Rule Type Maximum Length Minimum Conductor Ampacity Required Termination Raceway Enclosure Required?
10-Foot Feeder Tap 10 ft (3.0 m) ≥ \ge ≥ calculated load and ≥ \ge ≥ device rating; ≥ 1 / 10 \ge 1/10 ≥ 1/10 feeder OCPD if leaving enclosure Device supplied or OCPD Yes (approved raceway or enclosure)
25-Foot Feeder Tap 25 ft (7.5 m) ≥ \ge ≥ 1/3 of feeder OCPD rating Single circuit breaker or set of fuses Yes (protected from physical damage)
Outside Feeder Tap Unlimited Sized to supply calculated load Single circuit breaker or set of fuses Yes (outside / protected from damage)
Transformer Secondary Tap Rules — NEC 240.21(C) & 240.4(F)
A common misconception among apprentice electricians is assuming that a circuit breaker on the primary side of a transformer protects the secondary conductors. Under NEC 240.4(F), transformer secondary conductors are generally NOT considered protected by the primary overcurrent device .
Why Primary Breakers Do Not Protect Secondary Wires
In a standard 3-phase Delta-Wye transformer (e.g., 480V Delta primary to 208Y/120V Wye secondary):
A single-phase line-to-neutral fault on the secondary side draws current through only two conductors of the primary delta winding.
Due to the square root of 3 ( 3 \sqrt{3} 3 ) vector relationship and transformation ratios, the primary current does not rise proportionately to the secondary fault current.
A severe 150% or 200% continuous overload on a secondary neutral or phase wire may register as a normal operating load on the primary breaker, allowing secondary conductors to overheat and ignite insulation without tripping the primary device. THE DELTA-WYE SECONDARY PROTECTION DILEMMA (NEC 240.4(F)):
- 480V Primary (Delta) 208Y/120V Secondary (Wye)
- ┌─────────┐ ┌─────────┐
- │ ┌─────┐ │ │ A ├─── Secondary Phase A
- Phase ├─┤ W1 ├─┤ ├─▲───────┤
- │ └─────┘ │ Magnetic Flux │ │ W1 ├─── Secondary Phase B
- Phase ├─┤ W2 ├─┼────────────────────►│ ├─▲─────┤
- │ └─────┘ │ │ │ │ W2 ├─── Secondary Phase C
- Phase ├─┤ W3 ├─┤ │ │ │ ├───┤
- │ └─────┘ │ └─┼─┼─┼───┘
- └─────────┘ │ │ │
- Primary Breaker CANNOT detect └─┴─┴─────── NEUTRAL (Ground Fault / Unbalance)
phase-to-neutral secondary overloads!
The 10-Foot Transformer Secondary Rule — NEC 240.21(C)(2)
Secondary conductors from a transformer are permitted to be installed without secondary overcurrent protection at the transformer terminals if the length does not exceed 10 feet (3.0 m) and:
Conductor ampacity is not less than the calculated load supplied.
Conductor ampacity is not less than the rating of the device supplied or the terminating overcurrent device.
For field installations, the secondary conductor ampacity is not less than the primary-to-secondary voltage ratio formula: Secondary Ampacity ≥ Primary OCPD Rating × ( V primary V secondary ) 10 \text{Secondary Ampacity} \ge \frac{\text{Primary OCPD Rating} \times \left(\frac{V_{\text{primary}}}{V_{\text{secondary}}}\right)}{10} Secondary Ampacity ≥ 10 Primary OCPD Rating × ( V secondary V primary )
Conductors are enclosed in an approved raceway.
Worked Calculation: Sizing Secondary Conductors for a 45 kVA Transformer
Transformer Specifications: 45 kVA, 3-phase, 480V Delta primary to 208Y/120V Wye secondary. The secondary feeds a panelboard located 7 feet away.
Step 1: Calculate Secondary Full-Load Amperes (FLA): I secondary = 45,000 VA 208 V × 1.732 = 45,000 360.26 = 124.9 Amperes I_{\text{secondary}} = \frac{45{,}000\text{ VA}}{208\text{ V} \times 1.732} = \frac{45{,}000}{360.26} = 124.9\text{ Amperes} I secondary = 208 V × 1.732 45 , 000 VA = 360.26 45 , 000 = 124.9 Amperes
Step 2: Apply Continuous Sizing (125%): 124.9 A × 1.25 = 156.1 Amperes 124.9\text{ A} \times 1.25 = 156.1\text{ Amperes} 124.9 A × 1.25 = 156.1 Amperes
Step 3: Select Conductor from Table 310.16 (75°C Column):
2/0 AWG THHN copper is rated 175 amperes at 75°C ( 175 A ≥ 156.1 A 175\text{ A} \ge 156.1\text{ A} 175 A ≥ 156.1 A ).
Step 4: Select Terminating Main Breaker:
The panelboard main circuit breaker must not exceed the conductor ampacity: install a 175A main circuit breaker (or a 150A breaker if load permits).
Practical Jobsite Scenarios & Colorado Exam Traps
Jobsite Scenario Code Determination & Rule Common Exam Trap
Tapping a Tap in a Gutter: An electrician taps a 400A feeder with 1/0 AWG wire (150A) for 8 feet into a wireway, then taps that 1/0 AWG wire with 10 AWG wire to feed a small timeclock. Strict Violation: NEC 240.21 strictly prohibits tapping a tap conductor. The 10 AWG wire must be tapped directly from a protected feeder or have its own overcurrent protection. Assuming that as long as all conductors are under 10 feet, sub-tapping is permissible.
The 25-Foot Next-Size-Up Trap: An electrician runs a 24-foot tap from a 600A feeder using 3/0 AWG copper (rated 200A at 75°C, satisfying the 1/3 rule: 600 ÷ 3 = 200 A 600 \div 3 = 200\text{ A} 600 ÷ 3 = 200 A ). He terminates the tap in a 225A main breaker. Code Violation: Under NEC 240.21(B)(2), tap conductors must terminate in a single OCPD rated not greater than the tap conductor ampacity . Rounding up to 225A is prohibited. Incorrectly applying the 240.4(B) next-size-up rule to tap conductor terminations.
The Unprotected Secondary: A contractor runs 18 feet of secondary wire from a 480V-208Y/120V transformer directly to a main-lug-only (MLO) panelboard, claiming the primary breaker protects it. Code Violation: Under NEC 240.4(F) and 240.21(C), primary breakers cannot protect Delta-Wye secondaries. Secondary conductors must terminate in a main breaker or fuse set. Believing primary transformer fuses protect 3-phase 4-wire secondary panelboards.