8.2 Nonmetallic and Armored Cable Assemblies

Colorado Journeyman Electrician Study Guide Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Colorado Electrical Licensing Laws, DORA Rules & Exam Logistics

1.1 Colorado Electrical Board, Licensure Tiers & Application Process 1.2 Senate Bill 25-165, Apprentice Supervision & Colorado Board Rules 1.3 Permitting, Inspection Procedures, Violations & Penalties 1.4 The Colorado PSI Exam: Open-Book Format, Time Management & Code Navigation

2 Chapter 2: Electrical Theory, Mathematics & Fundamental Concepts

2.1 Ohm's Law, Joule's Law & DC Circuit Analysis 2.2 AC Fundamentals: Inductance, Capacitance & Power Factor 2.3 Three-Phase Electrical Systems: Wye & Delta Configurations 2.4 Voltage Drop Principles & Single/Three-Phase Formulas

3 Chapter 3: General Installation Requirements — NEC Articles 90 & 110

3.1 NEC Structure, Arrangement & Article 90 Fundamentals 3.2 Key Article 100 Definitions for the Exam 3.3 Equipment Examination, Listing & Termination Temperature Limits 3.4 Working Space, Dedicated Electrical Space & Guarding

4 Chapter 4: Branch Circuits & Feeders — NEC Articles 210, 215 & 225

4.1 Branch-Circuit Ratings, Conductor Sizing & Multiwire Branch Circuits 4.2 Dwelling Unit Required Outlets & Receptacle Placement 4.3 Ground-Fault Circuit-Interrupter (GFCI) Protection 4.4 Arc-Fault Circuit-Interrupter (AFCI) Protection & Feeder Rules

5 Chapter 5: Services & Overcurrent Protection — NEC Articles 230, 240 & 242

5.1 Service Conductors, Clearances & Overhead/Underground Drops 5.2 Service Disconnecting Means, Ratings & Surge Protection 5.3 Overcurrent Protection Fundamentals & Standard Ratings 5.4 Feeder & Transformer Tap Rules

6 Chapter 6: Grounding and Bonding — NEC Article 250 Part I (Systems & Electrodes)

6.1 Grounding vs. Bonding: Principles, Functions & Article 250 Architecture 6.2 Grounded Conductors, Main Bonding Jumpers & System Bonding Jumpers 6.3 The Grounding Electrode System 6.4 Grounding Electrode Conductor (GEC) Sizing & Installation

7 Chapter 7: Grounding and Bonding — NEC Article 250 Part II (Equipment & Special Systems)

7.1 Equipment Grounding Conductors (EGC) Types & Identification 7.2 Sizing the Equipment Grounding Conductor 7.3 Separately Derived Systems 7.4 Grounding & Bonding at Separate Buildings or Structures

8 Chapter 8: Wiring Methods & Materials — NEC Chapter 3

8.1 General Wiring Requirements & Underground Installations 8.2 Nonmetallic and Armored Cable Assemblies 8.3 Metallic and Nonmetallic Raceways 8.4 Cable Trays, Wireways, Auxiliary Gutters & Surface Raceways

9 Chapter 9: Conductors, Ampacity & Wire Sizing — NEC Article 310

9.1 Conductor Properties, Insulation Types & NEC Table 310.16 9.2 Temperature Correction Factors 9.3 Conductor Bundling & Adjustment Factors 9.4 Comprehensive Conductor Sizing & Terminal Temperature Coordination

10 Chapter 10: Box Fill, Conduit Fill & Pull Box Calculations

10.1 Outlet and Device Box Fill Calculations — NEC 314.16(A) & (B) 10.2 Conduit Fill Calculations — Chapter 9 Tables 1, 4, 5 & Annex C 10.3 Pull and Junction Box Sizing for Conductors 4 AWG and Larger — NEC 314.28 10.4 Practical Enclosure & Raceway Sizing Exam Scenarios

11 Chapter 11: Load Calculations — Dwellings & Commercial Buildings — NEC Article 120

11.1 General Lighting, Small Appliance & Laundry Loads 11.2 Fixed Appliances, Dryers & Cooking Equipment Calculations 11.3 Standard vs. Optional Calculation Methods for Single-Family Dwellings 11.4 Commercial & Multifamily Load Calculations

12 Chapter 12: Motors, Motor Circuits & Controllers — NEC Article 430

12.1 Motor Nameplate vs. NEC Tables & Motor Full-Load Current 12.2 Sizing Motor Branch-Circuit Conductors & Overload Protection 12.3 Motor Branch-Circuit Short-Circuit & Ground-Fault Protection 12.4 Motor Feeders, Disconnecting Means & Controllers

13 Chapter 13: Transformers, Distribution & Utilization Equipment

13.1 Transformer Overcurrent Protection & Installation — NEC Article 450 13.2 Panelboards, Switchboards & Switchgear — NEC Article 408 13.3 Luminaires, Appliances & Fixed Electric Space Heating 13.4 Generators, Transfer Switches & Standby Systems

14 Chapter 14: Special Occupancies, Renewable Energy & Modern Technologies

14.1 Hazardous (Classified) Locations — NEC Articles 500-516 14.2 Health Care Facilities & Places of Assembly — NEC Articles 517 & 518 14.3 Swimming Pools, Spas, Hot Tubs & Fountains — NEC Article 680 14.4 Solar Photovoltaic (PV) Systems & Energy Storage — NEC Articles 690, 705 & 706

8.2 Nonmetallic and Armored Cable Assemblies

Key Takeaways Explain This Topic AI

Type NM cable (Romex, Article 334) is permitted in one- and two-family dwellings, multifamily dwellings, and other structures of Types III, IV, and V construction, but is strictly prohibited in commercial suspended ceilings, damp or wet locations, and places of assembly seating 100 or more persons.

Under NEC 334.80, Type NM cable conductors have 90°C insulation (NM-B), but the final allowable ampacity is strictly capped at the 60°C column of Table 310.16; the 90°C rating may only be utilized as the baseline for ambient temperature and bundling derating calculations.

Type MC cable (Metal-Clad, Article 330) must be supported within 12 inches of every box, cabinet, or fitting and at intervals not exceeding 6 feet; standard interlocking MC armor does not serve as an equipment grounding conductor and requires an internal insulated copper EGC.

Type AC cable (Armored Cable / BX, Article 320) utilizes the combination of its interlocking armor and an internal bare aluminum bonding strip as an approved equipment grounding path, and NEC 320.40 mandates listed insulating anti-short bushings ('red devils') at all terminations.

Type SE (Service-Entrance) cable used for interior branch circuits and feeders must comply with the installation and 60°C ampacity rules of Type NM cable when installed in thermal insulation per NEC 338.10(B)(4), whereas Type USE is prohibited inside buildings beyond the terminal point.

Last updated: September 2026

8.2 Nonmetallic and Armored Cable Assemblies

Exam Fast Fact: Questions on cable assemblies are heavily represented on the Colorado Journeyman exam. The three most critical testing points are: (1) the 60°C ampacity limitation for Type NM cable under NEC 334.80 (even though NM-B has 90°C rated conductors), (2) the prohibition of Type NM cable in dropped ceilings of commercial buildings under NEC 334.12(A)(2) , and (3) distinguishing the equipment grounding mechanism of Type MC cable (insulated EGC required) versus Type AC cable (armor plus internal aluminum bonding strip).

Pre-fabricated factory cable assemblies provide rapid, cost-effective wiring solutions across residential, commercial, and industrial facilities. However, the National Electrical Code imposes strict boundaries on where each cable assembly may be deployed based on building construction types, environmental conditions, and mechanical protection requirements.

Nonmetallic-Sheathed Cable: Types NM, NMC, & NMS (NEC Article 334)

Commonly known by the trade name "Romex," nonmetallic-sheathed cable is the predominant wiring method in modern residential construction.

Cable Classifications

Type NM: Flame-retardant and moisture-resistant nonmetallic outer jacket. Permitted only in dry locations .

Type NMC: Flame-retardant, moisture-resistant, fungus-resistant, and corrosion-resistant jacket. Permitted in dry, moist, or damp locations (not wet locations).

Type NMS: Contains factory-assembled signaling, data, or control conductors along with power conductors under a nonmetallic jacket for home automation and energy management systems.

Uses Permitted (NEC 334.10)

Type NM, NMC, and NMS cables are permitted to be used in the following structures:

One- and Two-Family Dwellings and their attached or detached garages and accessory storage buildings.

Multifamily Dwellings permitted to be of Types III, IV, and V construction (wood frame, brick, or masonry construction).

Other Structures permitted to be of Types III, IV, and V construction, except where explicitly prohibited by other code sections.

Cables may be installed exposed or concealed in dry locations, and fished in existing wall cavities. NM CABLE COMMERCIAL CEILING PROHIBITION

  • RESIDENTIAL (Dwelling Units) COMMERCIAL (Offices, Retail, Clinics)
  • ┌──────────────────────────────┐ ┌──────────────────────────────────────┐
  • │ Drop / Suspended Ceiling │ │ Drop / Suspended Ceiling │
  • │ │ │ │
  • │ NM-B Cable Permitted │ │ NM CABLE STRICTLY PROHIBITED! │
  • │ (Above ceiling grid) │ │ (NEC 334.12(A)(2)) │
  • │ │ │ │
  • │ │ │ Must use MC Cable, EMT, or Conduit │
  • └──────────────────────────────┘ └──────────────────────────────────────┘
  • Uses Not Permitted (NEC 334.12) — High-Yield Exam Rules

Type NM cable shall not be used :

Commercial Dropped Ceilings (334.12(A)(2)): Exposed or concealed within or above suspended or dropped ceiling assemblies in commercial and industrial occupancies (other than one- and two-family and multifamily dwellings).

Damp or Wet Locations: Embedded in poured concrete, cinder block in contact with earth, or outdoor conduits.

Commercial Garages & Theaters: In commercial service garages with hazardous atmospheres, motion picture studios, or places of assembly seating 100 or more people (NEC Article 518).

As Service-Entrance Cable: Prohibited from serving as service-entrance conductors.

Ampacity & The 60°C Rule (NEC 334.80)

Modern Type NM cable manufactured since 1984 is labeled NM-B , indicating its internal conductors have 90°C insulation (such as THHN). However, NEC 334.80 establishes an absolute rule for final circuit sizing:

NEC 334.80 Mandate: "The allowable ampacity of Types NM, NMC, and NMS cable shall not exceed that of a 60°C (140°F) rated conductor."

Conductor Gauge (AWG) Table 310.16 (60°C Rating) — Final Ampacity Table 310.16 (90°C Rating) — Derating Baseline Maximum Overcurrent Protection (NEC 240.4(D))

  • 14 AWG Copper 15 Amperes 25 Amperes 15 Amperes
  • 12 AWG Copper 20 Amperes 30 Amperes 20 Amperes
  • 10 AWG Copper 30 Amperes 40 Amperes 30 Amperes
  • 8 AWG Copper 40 Amperes 55 Amperes 40 Amperes
  • 6 AWG Copper 55 Amperes 75 Amperes 60 Amperes (Next Size Up)

The Bundling Derating Rule: Where more than two NM cables containing two or more current-carrying conductors are passed through wood framing holes that are fire- or draft-stopped using thermal insulation, caulk, or sealing foam, the ampacity of each conductor must be derated using the adjustment factors in NEC Table 310.15(C)(1) . Crucially, the derating percentage is calculated from the 90°C column , but the final derated ampacity cannot exceed the 60°C limit .

Securing and Supporting (NEC 334.30)

Distance to Box: Must be secured within 12 inches of every outlet box, junction box, cabinet, or termination fitting.

Nonmetallic Boxes Without Clamps (Single-Gang): Where installed into a single-gang plastic box without internal cable clamps, the cable must be secured within 8 inches of the box.

Interval Along Run: Must be supported and secured at intervals not exceeding 4.5 feet (1.4 m) .

Bored Holes: Cable run horizontally through bored holes in wood or metal studs is considered supported, provided the 4.5-foot spacing is maintained.

Unfinished Basements (NEC 334.15(C)): Cables smaller than two 6 AWG or three 8 AWG conductors must be run through bored holes in joists or on running boards; cables 6 AWG or 8 AWG may be secured directly to the underside of joists.

Metal-Clad Cable: Type MC (NEC Article 330)

Type MC cable is a factory assembly of one or more insulated circuit conductors enclosed in an armor of interlocking metal tape or a smooth or corrugated metallic sheath. CABLE ASSEMBLY COMPARISON

  • Type MC Cable (Article 330) Type AC Cable (Article 320)
  • ┌───────────────────────────────┐ ┌───────────────────────────────┐
  • │ ▒▒▒▒▒ Interlocking Armor │ │ ▒▒▒▒▒ Interlocking Steel Armor│
  • │ (●) Phase Conductors │ │ (●) Phase Conductors │
  • │ (○) Neutral Conductor │ │ (○) Neutral Conductor │
  • │ (⊘) Dedicated Green Copper EGC│ │ ════ Bare Aluminum Bonding │
  • │ │ │ Strip (Must be folded) │
  • │ Armor ALONE is NOT an EGC! │ │ Armor + Bonding Strip = EGC! │
  • │ (Unless listed MC-AP) │ │ Red Devil Bushing MANDATORY │
  • └───────────────────────────────┘ └───────────────────────────────┘
  • Armor Types and Construction

Interlocking Metal Tape Armor: Spiral-wound galvanized steel or aluminum tape.

Smooth or Corrugated Tube Armor: Continuously welded impervious metal tube, offering gas- and vapor-tight seals for industrial and hazardous applications.

Equipment Grounding in Type MC Cable (NEC 330.108)

A critical distinction on the Journeyman exam is the grounding path:

Standard Interlocking MC Cable: The interlocking metal armor does not qualify as an equipment grounding conductor (EGC) by itself. A separate, insulated green copper equipment grounding conductor must be included within the cable assembly.

MC-AP (All-Purpose / Smart Ground): Listed MC cables incorporating an aluminum armor with a full-length uninsulated aluminum bonding wire in continuous intimate contact with the armor. This specific listed assembly is recognized as an EGC without an additional insulated copper wire.

Uses Permitted (NEC 330.10)

Type MC cable is one of the most versatile wiring methods recognized by the NEC:

  • Branch circuits, feeders, and services in commercial, industrial, and residential occupancies
  • Exposed or concealed work
  • Cable trays and environmental air spaces / plenums (where listed for plenum use)
  • Wet locations only where the metallic sheath is impervious to moisture or covered by a listed PVC outer jacket
  • Securing and Supporting (NEC 330.30)

Supported and secured within 12 inches of every box, cabinet, or termination fitting.

Supported at intervals not exceeding 6 feet along the run.

Drop to Luminaires (Exception 2 to 330.30(D)): An unsupported drop of up to 6 feet is permitted from an accessible ceiling junction box to a luminaire or equipment.

Armored Cable: Type AC (NEC Article 320)

Type AC cable, historically known as "BX," is a fabricated assembly of insulated conductors enclosed in a flexible metallic enclosure.

Construction and Grounding Continuity (NEC 320.108)

Type AC cable features an interlocking flexible steel or aluminum tape armor containing an internal bare aluminum bonding strip (typically 16 AWG or 14 AWG) running longitudinally throughout the entire length of the cable.

The Grounding Mechanism: The thin aluminum bonding strip acts in parallel with the flexible metal outer armor to reduce high-frequency AC impedance. The armor and bonding strip together form an approved equipment grounding conductor.

Installation Detail: The aluminum bonding strip is never terminated to a green grounding screw inside the box. At terminations, the strip is bent back sharply over the outer armor before the cable is inserted into the connector, ensuring firm mechanical and electrical contact against the connector body.

Anti-Short Bushings (NEC 320.40)

NEC 320.40 Absolute Mandate: "At all points where the armor of AC cable terminates, a listed fitting shall be provided with an approved insulating anti-short bushing (or equivalent) placed between the conductors and the armor."

Electricians refer to these bright red fiber or plastic inserts as "red devils." The bushing prevents the sharp jagged edges of cut steel armor from slicing through conductor insulation under vibration or thermal cycling. Connectors for Type AC cable feature an inspection slot through which the inspector can visually verify the presence of the red anti-short bushing.

Securing and Supporting (NEC 320.30)

Secured within 12 inches of every box, cabinet, or fitting.

Supported at intervals not exceeding 4.5 feet along the run.

Service-Entrance Cable: Types SE & USE (NEC Article 338)

Service-entrance cable is a factory assembly of one or more conductors with a protective outer covering primarily designed for bringing electrical utility power into a premises.

Type SE vs. Type USE

Cable Classification Description & Environmental Rating Interior Building Use Permitted? Grounding Conductor Configuration

Type SE (Service Entrance) Above-ground cable; moisture-resistant, flame-retardant outer jacket. Style U (flat, concentric neutral) or Style R (round, insulated neutral). YES. Permitted for interior feeders and branch circuits (e.g., ranges, dryers). Concentric bare neutral or insulated neutral with separate bare EGC.

Type USE (Underground Service Entrance) Direct-burial underground cable; moisture-resistant, NOT flame-retardant . STRICTLY PROHIBITED. Cannot enter building structure beyond the service disconnect terminal. Moisture-resistant insulation, bare or covered neutral.

Interior Feeders & The 60°C Rule (NEC 338.10(B)(4))

When Type SE cable is used for interior branch circuits or feeders (such as supplying an electric clothes dryer, kitchen range, or residential subpanel):

It must be installed in compliance with Part II of Article 334 (NM Cable Rules) .

Where installed in thermal insulation, its allowable ampacity shall not exceed the 60°C column of Table 310.16.

Comprehensive Comparison Matrix: NM vs. MC vs. AC vs. SE

Technical Parameter Type NM (Romex) — Art. 334 Type MC (Metal-Clad) — Art. 330 Type AC (BX) — Art. 320 Type SE — Art. 338

Conductor Temp Rating 90°C (NM-B) 90°C 90°C 75°C or 90°C

Final Ampacity Column Strictly 60°C 75°C or 90°C per terminal 75°C or 90°C per terminal 60°C in thermal insulation

  • Support from Box 12 inches (8" plastic box) 12 inches 12 inches 12 inches
  • Support Along Run 4.5 feet 6.0 feet 4.5 feet 4.5 feet

Armor Serves as EGC? No armor (Bare wire EGC) NO (Insulated EGC required) YES (Armor + Bonding strip) Bare wire or neutral

  • Anti-Short Bushing? Not applicable Recommended / per listing MANDATORY (320.40) Not applicable
  • Commercial Dropped Ceilings PROHIBITED (334.12) PERMITTED PERMITTED PROHIBITED
  • Practical Jobsite Scenarios & Common Exam Traps

Jobsite Scenario Technical Reality & Code Rule Common PSI Exam Trap

Office Tenant Finish Ceiling: An electrical contractor runs 12/2 NM-B cable above an acoustic ceiling tile grid in a commercial dental office to feed LED flat panels. Immediate Violation of 334.12(A)(2): NM cable cannot be installed in commercial dropped ceilings. The contractor must replace with Type MC cable or EMT raceway. Believing NM cable is permitted in commercial dropped ceilings if supported every 4.5 feet.

10 AWG NM-B Water Heater: An electrician installs 10/2 NM-B for a 30A residential electric water heater. A continuous load requires 125%: 24 A × 1.25 = 30 A 24\text{A} \times 1.25 = 30\text{A} 24 A × 1.25 = 30 A . 10 AWG NM-B 60°C rating is 30A. Code Compliant: 10 AWG at 60°C is rated 30A. However, if the water heater drew 25A continuous ( 25 × 1.25 = 31.25 A 25 \times 1.25 = 31.25\text{A} 25 × 1.25 = 31.25 A ), 10 NM-B would violate the 60°C limit. Attempting to use the 90°C rating (40A) of 10 AWG NM-B for the continuous load sizing.

Terminating AC Cable: An apprentice trims the aluminum bonding strip flush with the armor of Type AC cable and throws away the red anti-short bushing before inserting the connector. Severe Violation of 320.40 & 320.108: Red anti-short bushing is mandatory. The bonding strip must be folded back over the armor to ensure grounding continuity. Believing the aluminum bonding strip must be terminated under a grounding screw like an EGC.

Type USE Run to Main Panel: An electrician pulls Type USE cable directly from an underground utility transformer through a basement wall to an indoor main panel. Violation of 338.12(B): Type USE cable is not flame-retardant and cannot be run inside a structure. It must terminate at an exterior meter or disconnect. Assuming Type USE cable is permitted inside buildings because it is rated for service entrance.