8.3 Metallic and Nonmetallic Raceways

Colorado Journeyman Electrician Study Guide Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Colorado Electrical Licensing Laws, DORA Rules & Exam Logistics

1.1 Colorado Electrical Board, Licensure Tiers & Application Process 1.2 Senate Bill 25-165, Apprentice Supervision & Colorado Board Rules 1.3 Permitting, Inspection Procedures, Violations & Penalties 1.4 The Colorado PSI Exam: Open-Book Format, Time Management & Code Navigation

2 Chapter 2: Electrical Theory, Mathematics & Fundamental Concepts

2.1 Ohm's Law, Joule's Law & DC Circuit Analysis 2.2 AC Fundamentals: Inductance, Capacitance & Power Factor 2.3 Three-Phase Electrical Systems: Wye & Delta Configurations 2.4 Voltage Drop Principles & Single/Three-Phase Formulas

3 Chapter 3: General Installation Requirements — NEC Articles 90 & 110

3.1 NEC Structure, Arrangement & Article 90 Fundamentals 3.2 Key Article 100 Definitions for the Exam 3.3 Equipment Examination, Listing & Termination Temperature Limits 3.4 Working Space, Dedicated Electrical Space & Guarding

4 Chapter 4: Branch Circuits & Feeders — NEC Articles 210, 215 & 225

4.1 Branch-Circuit Ratings, Conductor Sizing & Multiwire Branch Circuits 4.2 Dwelling Unit Required Outlets & Receptacle Placement 4.3 Ground-Fault Circuit-Interrupter (GFCI) Protection 4.4 Arc-Fault Circuit-Interrupter (AFCI) Protection & Feeder Rules

5 Chapter 5: Services & Overcurrent Protection — NEC Articles 230, 240 & 242

5.1 Service Conductors, Clearances & Overhead/Underground Drops 5.2 Service Disconnecting Means, Ratings & Surge Protection 5.3 Overcurrent Protection Fundamentals & Standard Ratings 5.4 Feeder & Transformer Tap Rules

6 Chapter 6: Grounding and Bonding — NEC Article 250 Part I (Systems & Electrodes)

6.1 Grounding vs. Bonding: Principles, Functions & Article 250 Architecture 6.2 Grounded Conductors, Main Bonding Jumpers & System Bonding Jumpers 6.3 The Grounding Electrode System 6.4 Grounding Electrode Conductor (GEC) Sizing & Installation

7 Chapter 7: Grounding and Bonding — NEC Article 250 Part II (Equipment & Special Systems)

7.1 Equipment Grounding Conductors (EGC) Types & Identification 7.2 Sizing the Equipment Grounding Conductor 7.3 Separately Derived Systems 7.4 Grounding & Bonding at Separate Buildings or Structures

8 Chapter 8: Wiring Methods & Materials — NEC Chapter 3

8.1 General Wiring Requirements & Underground Installations 8.2 Nonmetallic and Armored Cable Assemblies 8.3 Metallic and Nonmetallic Raceways 8.4 Cable Trays, Wireways, Auxiliary Gutters & Surface Raceways

9 Chapter 9: Conductors, Ampacity & Wire Sizing — NEC Article 310

9.1 Conductor Properties, Insulation Types & NEC Table 310.16 9.2 Temperature Correction Factors 9.3 Conductor Bundling & Adjustment Factors 9.4 Comprehensive Conductor Sizing & Terminal Temperature Coordination

10 Chapter 10: Box Fill, Conduit Fill & Pull Box Calculations

10.1 Outlet and Device Box Fill Calculations — NEC 314.16(A) & (B) 10.2 Conduit Fill Calculations — Chapter 9 Tables 1, 4, 5 & Annex C 10.3 Pull and Junction Box Sizing for Conductors 4 AWG and Larger — NEC 314.28 10.4 Practical Enclosure & Raceway Sizing Exam Scenarios

11 Chapter 11: Load Calculations — Dwellings & Commercial Buildings — NEC Article 120

11.1 General Lighting, Small Appliance & Laundry Loads 11.2 Fixed Appliances, Dryers & Cooking Equipment Calculations 11.3 Standard vs. Optional Calculation Methods for Single-Family Dwellings 11.4 Commercial & Multifamily Load Calculations

12 Chapter 12: Motors, Motor Circuits & Controllers — NEC Article 430

12.1 Motor Nameplate vs. NEC Tables & Motor Full-Load Current 12.2 Sizing Motor Branch-Circuit Conductors & Overload Protection 12.3 Motor Branch-Circuit Short-Circuit & Ground-Fault Protection 12.4 Motor Feeders, Disconnecting Means & Controllers

13 Chapter 13: Transformers, Distribution & Utilization Equipment

13.1 Transformer Overcurrent Protection & Installation — NEC Article 450 13.2 Panelboards, Switchboards & Switchgear — NEC Article 408 13.3 Luminaires, Appliances & Fixed Electric Space Heating 13.4 Generators, Transfer Switches & Standby Systems

14 Chapter 14: Special Occupancies, Renewable Energy & Modern Technologies

14.1 Hazardous (Classified) Locations — NEC Articles 500-516 14.2 Health Care Facilities & Places of Assembly — NEC Articles 517 & 518 14.3 Swimming Pools, Spas, Hot Tubs & Fountains — NEC Article 680 14.4 Solar Photovoltaic (PV) Systems & Energy Storage — NEC Articles 690, 705 & 706

8.3 Metallic and Nonmetallic Raceways

Key Takeaways Explain This Topic AI

Rigid Metal Conduit (RMC, Article 344) and Intermediate Metal Conduit (IMC, Article 342) offer the highest level of mechanical protection, are permitted in all atmospheric conditions, and allow extended support intervals up to 16 or 20 feet for straight horizontal runs with threaded couplings per Table 344.30(B)(2).

NEC 344.26, 352.26, and 358.26 mandate that the total degrees of bends between pull points (boxes, conduit bodies, or cabinets) shall not exceed 360 degrees (four 90-degree bends) to prevent insulation damage during wire pulling.

Electrical Metallic Tubing (EMT, Article 358) must be supported within 3 feet of every box or fitting and every 10 feet thereafter; set-screw fittings are restricted to dry indoor locations, while listed raintight compression fittings are required in wet and outdoor environments.

Rigid Polyvinyl Chloride Conduit (PVC, Article 352) requires Schedule 80 wherever subject to physical damage per 352.10(F), and outdoor installations must include expansion fittings calculated from Table 352.44 (0.406 inches per 100 feet per 10°F temperature change) whenever thermal movement reaches 0.25 inches.

Flexible Metal Conduit (FMC, Article 348) and Liquidtight Flexible Metal Conduit (LFMC, Article 350) require an internal or external wire-type equipment grounding conductor whenever the run exceeds 6 feet or the circuit overcurrent device exceeds 20 amperes under NEC 250.118.

Last updated: September 2026

8.3 Metallic and Nonmetallic Raceways

Exam Fast Fact: Raceway systems form the backbone of commercial, industrial, and institutional electrical construction. On the Colorado PSI Journeyman examination, candidates must know: (1) the 360-degree maximum bend rule across all conduit articles, (2) the support spacing tables for RMC (Table 344.30(B)(2)), EMT (358.30), and PVC (Table 352.30), (3) PVC thermal expansion calculations using NEC Table 352.44 , and (4) the strict 6-foot / 20-ampere equipment grounding boundary for flexible conduits (FMC and LFMC) under NEC 250.118 .

Conduit raceways provide mechanical protection, allow conductors to be pulled, upgraded, or replaced throughout a building's lifespan, and frequently serve as the equipment grounding conductor (EGC) for the enclosed circuits.

Heavy-Wall Metallic Raceways: RMC & IMC (Articles 344 & 342)

Rigid Metal Conduit (RMC) and Intermediate Metal Conduit (IMC) are threaded, heavy-wall circular raceways designed for extreme mechanical durability.

Material Differences

Rigid Metal Conduit (Article 344): Heaviest metallic wall. Manufactured from galvanized steel, stainless steel, aluminum, or red brass. Listed for all atmospheric conditions, corrosive environments, hazardous (classified) locations (Class I, Division 1), and direct burial in soil or concrete.

Intermediate Metal Conduit (Article 342): Intermediate wall thickness. Manufactured from high-strength alloy steel. Slightly lighter than RMC (roughly 30% lighter), providing similar mechanical strength and utilizing identical threaded fittings.

Threading & Field Reaming (NEC 344.28 & 342.28)

Field threads must be cut using standard pipe dies with a 3/4-inch taper per foot (NPT - National Pipe Taper). After cutting, all conduit ends must be reamed to remove sharp interior burrs that would abrade wire insulation during pulling. THE 360-DEGREE TOTAL BEND RULE

  • Pull Point A Pull Point B
  • ┌────────────┐ ┌────────────┐
  • │ Junction ├───────┐ │ Pull Box │
  • │ Box │ │ 90° Bend │ │
  • └────────────┘ ▼ └──────▲─────┘
  • │ │
  • │ 90° Bend │ 90° Bend
  • └───────────────►───────────────┐ │
  • │ │
  • ▼ │
  • └────┘
  • 90° Bend

Total Bends: 90° + 90° + 90° + 90° = 360° Maximum Permitted!

  • (Exceeding 360° requires an intermediate pull box or conduit body)
  • Maximum Bends Between Pull Points (NEC 344.26 & 342.26)

The total degrees of bends between pull points—such as junction boxes, pull boxes, cabinets, or conduit bodies (e.g., Type LB, T, or C fittings)— shall not exceed 360 degrees (the equivalent of four 90-degree bends). Every bend introduces mechanical friction during a wire pull; exceeding 360 degrees causes pulling ropes to burn through insulation or snap conductors.

Support Spacing for RMC & IMC (NEC 344.30 & Table 344.30(B)(2))

General Rule (344.30(A)): Supported within 3 feet (900 mm) of each box, cabinet, conduit body, or termination fitting, and at intervals not exceeding 10 feet (3.0 m) .

Structural Exception: Where structural framing does not permit fastening within 3 feet, the distance may be increased to 5 feet (1.5 m) .

Straight Horizontal Runs with Threaded Couplings (Table 344.30(B)(2)): For industrial and commercial straight runs utilizing threaded couplings, support intervals may be extended based on conduit trade size:

  • Conduit Trade Size (Inches) Maximum Support Distance Between Rigid Metal Conduit Supports (Table 344.30(B)(2))
  • 1/2" and 3/4" 10 feet
  • 1" 12 feet
  • 1-1/4" and 1-1/2" 14 feet
  • 2" and 2-1/2" 16 feet
  • 3" and larger 20 feet
  • Electrical Metallic Tubing: EMT (NEC Article 358)

Commonly referred to as "thinwall," Electrical Metallic Tubing (EMT) is the most widely installed raceway in commercial electrical construction due to its lightweight handling and rapid installation.

Characteristics & Prohibitions

Unthreaded Wall: EMT has a thin wall that cannot be threaded . Any attempt to cut threads into EMT violates NEC 358.28(B) .

Uses Permitted (358.10): Exposed and concealed installations in dry, damp, and wet locations (with proper fittings); embedded in concrete; installed in direct contact with earth where provided with corrosion protection.

Uses Not Permitted (358.12): Where subject to severe physical damage ; in direct burial without concrete encasement (unless specially listed); or in hazardous (classified) locations except where specifically permitted by Articles 501 through 505.

Fittings: Set-Screw vs. Compression (NEC 358.42 & 314.15)

Set-Screw Fittings: Utilize one or more clamping screws that seat against the EMT wall. Approved only for dry indoor locations . In concrete, set-screw fittings must be taped to achieve concrete-tight integrity.

Compression Fittings: Utilize a split compression ring and threaded gland nut. Standard compression fittings are concrete-tight without taping.

Raintight Compression Fittings: Outdoor and wet location installations require compression fittings equipped with internal elastomeric sealing rings/gaskets and marked "Raintight." Standard set-screw and indoor compression fittings are illegal in wet locations.

Securing and Supporting (NEC 358.30)

Fastened within 3 feet (900 mm) of every outlet box, junction box, device box, cabinet, or fitting.

Supported at intervals not exceeding 10 feet (3.0 m) .

Unbroken Length Exception: Where unbroken lengths of EMT pass through framing members, supports may be spaced up to 5 feet (1.5 m) from terminations.

Maximum bends between pull points: 360 degrees (NEC 358.26).

Rigid Polyvinyl Chloride Conduit: PVC (NEC Article 352)

Rigid PVC conduit is a nonmetallic, nonconductive, flame-retardant raceway impervious to rust, chemical attack, and soil corrosion.

Schedule 40 vs. Schedule 80 PVC

  • Technical Feature Schedule 40 PVC (NEC 352.10) Schedule 80 PVC (NEC 352.10(F))
  • Wall Thickness Standard heavy wall Extra-heavy wall (roughly 40% thicker)

Physical Damage Rating General underground and aboveground; NOT permitted where subject to physical damage MANDATORY where subject to physical damage (exterior risers, vehicular areas, loading docks)

Internal Diameter Standard internal area Smaller internal area due to thicker wall

Conduit Fill Impact Standard Chapter 9 Table 4 fill Reduced wire capacity! Must use specific Schedule 80 Table 4 values

Thermal Expansion Calculations (NEC 352.44 & Table 352.44)

PVC expands and contracts with temperature changes at roughly 5 to 6 times the rate of steel .

NEC 352.44 Rule: "Expansion fittings for PVC conduit shall be provided to compensate for thermal expansion and contraction where the length change, in accordance with Table 352.44, is expected to be 0.25 in. (6 mm) or greater in a straight run between securely mounted items."

According to NEC Table 352.44 , rigid PVC conduit expands or contracts by approximately 0.406 inches per 100 feet for every 10°F temperature change . Δ L = Length (ft) × ( Δ T ( ∘ F ) 10 ∘ F ) × ( 0.406 inches 100 ft ) \Delta L = \text{Length (ft)} \times \left(\frac{\Delta T (^{\circ}\text{F})}{10^{\circ}\text{F}}\right) \times \left(\frac{0.406\text{ inches}}{100\text{ ft}}\right) Δ L = Length (ft) × ( 1 0 ∘ F Δ T ( ∘ F ) ​ ) × ( 100 ft 0.406 inches ​ ) PVC CONDUIT THERMAL EXPANSION CALCULATION

  • Example: 120-Foot Exterior PVC Run on a Colorado Building Wall
  • Winter Low: -20°F | Summer High: 100°F | Temperature Delta: 120°F
  • Step 1: Determine Temperature Change (ΔT)
  • ΔT = 100°F - (-20°F) = 120°F
  • Step 2: Apply Table 352.44 Formula
  • ΔL = 120 ft × (120°F / 10°F) × (0.406 in. / 100 ft)

ΔL = 1.20 × 12 × 0.406 in. = 5.85 inches of thermal movement!

Conclusion: Over 5.8 inches of movement occurs! Multiple expansion

fittings must be installed to prevent conduit bowing or pulled boxes.

PVC Support Spacing (NEC Table 352.30)

Unlike steel conduit which can span 10 feet, PVC requires closer support spacing because of its flexibility:

  • Conduit Trade Size (Inches) Maximum Support Spacing for Rigid PVC (Table 352.30)
  • 1/2" through 1" 3 feet
  • 1-1/4" through 2" 5 feet
  • 2-1/2" through 3" 6 feet
  • 3-1/2" through 5" 7 feet
  • 6" 8 feet

All sizes must be supported within 3 feet of every box or termination fitting.

Flexible Metal Conduits: FMC & LFMC (Articles 348 & 350)

Flexible conduits isolate vibration from rotating machinery (motors, pumps, transformers) and provide flexible routing in tight spaces.

Types & Construction

Flexible Metal Conduit (FMC / "Greenfield" — Art. 348): Helically wound, interlocking galvanized steel or aluminum armor. Permitted only in dry locations .

Liquidtight Flexible Metal Conduit (LFMC / "Sealtite" — Art. 350): Flexible metal core with an outer sunlight-resistant, liquidtight thermoplastic jacket. Permitted in wet, outdoor, and corrosive locations.

Securing and Supporting (NEC 348.30 & 350.30)

Supported within 12 inches (300 mm) of every box, cabinet, or fitting.

Supported at intervals not exceeding 4.5 feet (1.4 m) .

The 6-Foot Luminaire/Equipment Exception: Flexible conduit runs up to 6 feet (1.8 m) from an enclosure termination are permitted without intermediate support for fixture whips to luminaires or connections to vibrating motors.

Grounding Rules: The 6-Foot / 20-Ampere Limit (NEC 250.118(5) & (6))

A heavily tested exam concept is whether FMC or LFMC can serve as the equipment grounding conductor:

NEC 250.118 Grounding Limitation: FMC and LFMC are permitted to serve as the sole equipment grounding conductor ONLY IF ALL of the following conditions are met :

The total length in any ground return path does not exceed 6 feet (1.8 m) .

The circuit conductors contained in the conduit are protected by overcurrent devices rated at 20 amperes or less .

The conduit terminates in fittings listed for grounding.

If the run exceeds 6 feet OR the circuit breaker exceeds 20 amperes , a separate wire-type equipment grounding conductor (copper or aluminum) must be installed inside or outside the conduit.

Comprehensive Conduit Selection & Support Matrix

Raceway Type Article Max Support Interval Support from Box Max Bends Permitted as Sole EGC?

RMC (Rigid Metal) Art. 344 10 ft (up to 20 ft Table 344.30(B)(2)) 3 ft (5 ft exception) 360° YES (All sizes)

IMC (Intermediate Metal) Art. 342 10 ft (up to 20 ft Table 344.30(B)(2)) 3 ft (5 ft exception) 360° YES (All sizes)

  • EMT (Thinwall) Art. 358 10 ft 3 ft (5 ft unbroken) 360° YES (All sizes)
  • PVC (Sch 40/80) Art. 352 3 ft to 8 ft (Table 352.30) 3 ft 360° NO (Wire EGC required)
  • FMC (Greenfield) Art. 348 4.5 ft (6 ft whip exception) 12 in. 360° Only if ≤ 6 ft AND ≤ 20A
  • LFMC (Liquidtight) Art. 350 4.5 ft (6 ft whip exception) 12 in. 360° Only if ≤ 6 ft AND ≤ 20A
  • Practical Jobsite Scenarios & Common Exam Traps

Jobsite Scenario Technical Reality & Code Rule Common PSI Exam Trap

Outdoor EMT Set-Screw Fittings: An installer runs EMT on the exterior wall of a car wash using zinc die-cast set-screw fittings. Violation of 358.42 & 314.15: Wet and outdoor locations mandate listed raintight compression fittings . Set-screw fittings allow water intrusion and rapid short circuits. Assuming set-screw fittings are permitted outdoors if protected by a roof overhang.

50A Rooftop AC Whip: An HVAC installer connects a 50A rooftop air handler using a 5-foot whip of LFMC without pulling a green grounding wire, relying on the metallic armor. Violation of 250.118(6): Although the whip is under 6 feet, the overcurrent device is 50A (exceeds 20A limit). A separate wire-type EGC is strictly required. Forgetting that BOTH conditions (≤ 6 feet AND ≤ 20 amperes) must be met simultaneously.

Schedule 40 PVC at Warehouse Dock: An electrician installs Schedule 40 PVC conduit exposed along a warehouse truck loading dock wall. Violation of 352.10(F): Areas subject to vehicular traffic or forklift impact are subject to physical damage. Schedule 80 PVC or RMC is mandatory. Assuming Schedule 40 PVC is permitted anywhere outdoors or in commercial facilities.

Conduit Run with Five 90° Bends: An apprentice installs a 1-inch EMT run between two junction boxes containing five 90-degree bends ( 5 × 90 ∘ = 450 ∘ 5 \times 90^{\circ} = 450^{\circ} 5 × 9 0 ∘ = 45 0 ∘ ). Violation of 358.26: The maximum total bends cannot exceed 360 degrees between pull points. An intermediate pull box or conduit body (LB) must be installed. Believing 360 degrees applies per 100 feet of pipe rather than between pull points.