7.4 Nonpotable Water Systems, Identification, and Reclaimed Water

Colorado Journeyworker Plumber Journeyman Plumber

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Passing the Colorado Journeyworker Plumber Exam

1.1 Exam Blueprint, Format, and the 2024 Code Changeover 1.2 Colorado Licenses, Experience Hours, and Apprentice Supervision 1.3 Permits, Inspections, Blue Tags, and Board Enforcement

2 Chapter 2: General Regulations (IPC Chapter 3)

2.1 Approved Materials, Certification, and General Installation Rules 2.2 Protection of Pipes: Contact, Notching, Shield Plates, and Freezing 2.3 Piping Support, Trenching, Bedding, and Backfill 2.4 Required Tests: Water, Air, and Backflow Assembly Testing

3 Chapter 3: Fixtures and Equipment (IPC Chapter 4)

3.1 Minimum Fixture Counts, Separate Facilities, and Toilet Room Location 3.2 Fixture Clearances, Compartments, and Setting Requirements 3.3 Water Closets, Urinals, Lavatories, Sinks, and Flush Devices 3.4 Showers, Bathtubs, Fixture Fittings, and Scald Protection

4 Chapter 4: Water Heaters (IPC Chapter 5)

4.1 Water Heater Installation, Location, Access, and Clearances 4.2 Relief Valves and Discharge Piping 4.3 Water Heater Pans, Pan Drains, and Storage Tank Requirements 4.4 Thermal Expansion Control and Hot Water Temperature Limits

5 Chapter 5: Water Supply Materials and Installation (IPC Chapter 6)

5.1 Water Service and Distribution Materials, and Sewer Separation 5.2 Joints, Connections, and Dissimilar Materials in Water Piping 5.3 Valves, Shutoffs, and Required Valve Locations

6 Chapter 6: Water Supply Sizing and Pressure (IPC Chapter 6 and Appendix E)

6.1 Pressure Limits, Pressure Reducing Valves, and Water Hammer 6.2 Water Supply Fixture Units and Estimating Demand 6.3 Sizing Water Piping with Appendix E and Table E104.1

7 Chapter 7: Cross-Connection Control and Backflow Prevention (IPC Sections 608-610, Chapter 13)

7.1 Cross-Connection Principles, Backsiphonage, and Backpressure 7.2 Air Gaps and the Backflow Preventer Family 7.3 Applying Backflow Protection to Specific Connections 7.4 Nonpotable Water Systems, Identification, and Reclaimed Water

8 Chapter 8: Sanitary Drainage Materials and Fittings (IPC Chapter 7)

8.1 Sanitary Drainage Materials and Where Each May Be Used 8.2 Drainage Joints, Transitions, and Prohibited Connections 8.3 Fittings for Change of Direction and Drainage Flow Patterns

9 Chapter 9: Sanitary Drainage Sizing (IPC Sections 704, 709-711)

9.1 Drainage Fixture Units and Load Estimation 9.2 Slope of Horizontal Drainage and Installation Rules 9.3 Sizing Building Drains, Building Sewers, and Horizontal Branches 9.4 Stacks, Branch Intervals, and Offsets in Tall Buildings

10 Chapter 10: Cleanouts, Sumps and Below-Sewer Drainage (IPC Sections 708, 712-716)

10.1 Cleanouts, Manholes, and Access Requirements 10.2 Backwater Valves and Fixtures Below the Sewer Level 10.3 Sumps, Sewage Ejectors, and Macerating Toilet Systems 10.4 Building Sewers, Private Disposal, and Special Drainage Conditions

11 Chapter 11: Vent Fundamentals and Terminals (IPC Sections 901-905, 908)

11.1 How Vents Work, Trap Seal Loss, and the One-Inch Rule 11.2 Vent Terminals, Roof Penetrations, and Sidewall Terminations 11.3 Vent Connections, Grade, and the Six-Inch Rules

12 Chapter 12: Vent Types and Sizing (IPC Sections 906-911, 917)

12.1 Individual Vents, Common Vents, and Vents for Stack Offsets 12.2 Trap-to-Vent Distance, Trap Arms, and Fixture Drains 12.3 Sizing Stack Vents, Vent Stacks, Branch Vents, and Headers 12.4 Putting a Vent System Together: A Worked Building

13 Chapter 13: Engineered and Special Venting (IPC Sections 912-916, 918-920)

13.1 Horizontal and Vertical Wet Venting 13.2 Waste Stack Vents, Circuit Vents, and Combination Waste and Vent 13.3 Island Fixture Venting and Air Admittance Valves

14 Chapter 14: Traps, Interceptors and Separators (IPC Chapter 10)

14.1 Fixture Traps, Trap Seals, and Prohibited Trap Types 14.2 Trap Seal Protection, Primers, and Barrier Devices 14.3 Grease Interceptors, Oil Separators, and Solids Interceptors

15 Chapter 15: Indirect and Special Waste (IPC Chapter 8)

15.1 Where Indirect Waste Is Required, and Air Gap Versus Air Break 15.2 Waste Receptors, Hub Drains, and Standpipes 15.3 Special Wastes, Chemical Neutralization, and Health Care Drainage

16 Chapter 16: Storm Drainage (IPC Chapter 11 and Appendix B)

16.1 Storm Drainage Scope, Disposal, and Prohibited Connections 16.2 Storm Drainage Materials, Roof Drains, and Conductors 16.3 Secondary Roof Drains, Scuppers, and Controlled Flow Systems 16.4 Rainfall Rates, Roof Area, and the Flow-Rate Conversion 16.5 Sizing Vertical Conductors, Leaders, and Storm Drains 16.6 Gutters, Subsoil Drains, Building Subdrains, and Storm Sumps

17 Chapter 17: Residential Fire Sprinklers (IRC Section P2904)

17.1 Residential Fire Sprinkler Systems (IRC Section P2904)

18 Chapter 18: Isometric Analysis and Plumbing Calculations

18.1 Reading Plumbing Isometrics and Riser Diagrams 18.2 Analyzing a DWV Isometric for Code Compliance 18.3 Offsets, Travel, and the Plumbing Math the Exam Assumes

7.4 Nonpotable Water Systems, Identification, and Reclaimed Water

Key Takeaways Explain This Topic AI

IPC 608.9.2 requires nonpotable distribution piping to be purple and embossed, stamped or marked CAUTION: NONPOTABLE WATER - DO NOT DRINK, or installed with purple identification tape or wrap.

IPC 608.9.2 requires pipe identification to be repeated at intervals not exceeding 25 feet and at each point where the piping passes through a wall, floor or roof.

IPC 608.9.1 requires nonpotable outlet signage with letters not less than 0.5 inch in height, in contrasting colors, plus the Figure 608.9.1 do-not-drink pictograph.

IPC 1301.2.2 requires nonpotable water used for water closet and urinal flushing to be filtered by a 100-micron or finer filter.

IPC 608.10 permits water used for cooling equipment or other processes to be reused for flushing water closets and urinals or for irrigation, provided it is not sprayed onto areas open to public use.

Last updated: September 2026

Why identification is a safety system

Every other rule in Chapter 7 of this guide prevents nonpotable water from entering the potable system. Identification prevents the opposite failure: a future plumber, maintenance technician or homeowner mistaking a nonpotable line for a potable one and tapping it. Buildings outlive the people who built them, so the marking has to survive.

Signage at outlets — IPC 608.9.1

Nonpotable water outlets, such as hose connections, open-ended pipes and faucets , shall be identified with signage that reads: "Nonpotable water is utilized for [application name]. CAUTION: NONPOTABLE WATER - DO NOT DRINK."

Requirements for the sign:

Words legibly and indelibly printed on a tag or sign of corrosion-resistant waterproof material , or indelibly printed on the fixture.

Letters not less than 0.5 inch in height .

Colors in contrast to the background .

In addition to the wording, the pictograph in Figure 608.9.1 ("do not drink") must appear.

Pipe labeling and marking — IPC 608.9.2

  • Requirement Rule
  • Color Nonpotable distribution piping shall be purple

Marking Embossed, integrally stamped or marked "CAUTION: NONPOTABLE WATER - DO NOT DRINK", or installed with purple identification tape or wrap

  • Content Identification includes the contents of the piping system and an arrow indicating direction of flow
  • Hazard Hazardous piping systems shall also contain information addressing the nature of the hazard

Interval Repeated at intervals not exceeding 25 feet and at each point where the piping passes through a wall, floor or roof

Visibility Lettering readily observable within the room or space where the piping is located

608.9.2.1 Color : the identification color must be discernible and consistent throughout the building , and purple identifies reclaimed, rain and graywater distribution systems.

608.9.2.2 Lettering size scales with pipe diameter, per Table 608.9.2.2:

  • Pipe diameter Background color field length Letter size
  • 3/4 to 1-1/4 inch 8 inches 0.5 inch
  • 1-1/2 to 2 inch 8 inches 0.75 inch
  • 2-1/2 to 6 inch 12 inches 1.25 inch
  • 8 to 10 inch 24 inches 2.5 inch
  • Over 10 inch 32 inches 3.5 inch
  • Nonpotable water systems — IPC Chapter 13

Chapter 13 covers nonpotable water systems generally: graywater, rainwater, reclaimed water and on-site treated nonpotable water. Colorado adopts IPC Chapters 2 through 13, so Chapter 13 is part of the Colorado Plumbing Code.

Core rules:

1301.2.2 Filtration : nonpotable water used for water closet and urinal flushing applications shall be filtered by a 100-micron or finer filter .

1301.3 Identification : nonpotable distribution piping is identified per 608.9.2.

1301.4 Materials : nonpotable piping conforms to the material tables for the application.

Storage tanks must be covered, labeled, and protected from contamination , with overflows and drains that cannot cross-connect.

Makeup water to a nonpotable storage tank from the potable system must be protected by an air gap — never a mechanical device on an open tank.

IPC 608.12 Potable water tanks requires potable tanks to be enclosed and covered; 608.4 requires overflow, relief valve and waste discharge pipes from pumps, filters, softeners and tanks handling potable water to terminate through an air gap .

Definitions that matter

Graywater (IPC 202): waste discharged from lavatories, bathtubs, showers, clothes washers and laundry trays. It excludes water closet, urinal, kitchen sink, dishwasher and utility sink waste.

Reclaimed water : nonpotable water that has been derived from the treatment of wastewater by a facility or system duly authorized by the authority having jurisdiction.

Blackwater : waste containing bodily or other biological wastes, as from water closets, urinals, kitchen sinks, dishwashers and utility sinks.

Colorado field note (not exam-scored): Colorado rewrites both definitions. Board Rule 1.2(E)(1)(f) defines graywater as wastewater collected from bathroom and laundry room sinks, bathtubs, showers and laundry machines for beneficial use, excluding toilets, urinals, kitchen sinks, dishwashers and non-laundry utility sinks. Rule 1.2(E)(1)(g) defines reclaimed water as domestic wastewater that has received secondary treatment by a domestic wastewater treatment works plus additional treatment sufficient to meet the standards for approved uses.

Colorado also modifies the filtration exception (Rule 1.2(E)(1)(yy)): reclaimed water sources are not required to meet the 100-micron filtration requirement, and graywater treatment systems installed per Section 1302.6.1 do not need additional filtration. Rule 1.2(E)(1)(aaa) adds a required sign on the door of any room containing graywater treatment works : "CAUTION GRAYWATER TREATMENT WORKS, DO NOT DRINK, DO NOT CONNECT TO THE POTABLE DRINKING WATER SYSTEM. NOTICE: CONTACT BUILDING MANAGEMENT BEFORE PERFORMING ANY WORK ON THIS WATER SYSTEM."

Reuse rules — IPC 608.10 and 608.11

608.10 Reutilization prohibited : water used for cooling equipment or other processes shall not be returned to the potable water system . Such water may be reused for:

  • flushing water closets and urinals , or
  • irrigation ,

provided that it is not sprayed onto areas open to public use — the spray restriction exists because aerosolized nonpotable water is an inhalation route.

608.11 Reuse of piping : piping that has conveyed nonpotable water or other contaminating substances shall not be reused for potable water service or distribution. Reusing an old irrigation main as a domestic water line is prohibited no matter how thoroughly it is flushed.

Putting the chapter together: an inspection walkthrough

A commercial building uses reclaimed water for water closet and urinal flushing and for site irrigation.

  • Item to verify Requirement
  • Distribution piping color Purple (608.9.2, 608.9.2.1)
  • Pipe marking text "CAUTION: NONPOTABLE WATER - DO NOT DRINK", with contents and flow arrow
  • Marking interval Every 25 feet maximum and at every wall, floor and roof penetration
  • Letter size on a 4-inch line 1.25 inch , on a 12-inch background field (Table 608.9.2.2)
  • Outlet signage 0.5-inch letters minimum, contrasting colors, plus the do-not-drink pictograph
  • Flushing water filtration 100-micron or finer filter (1301.2.2)
  • Potable makeup to the reclaimed storage tank Air gap
  • Irrigation spray Not sprayed onto areas open to public use (608.10)
  • Backflow protection at the irrigation connection AVB, PVB or RPZ; RPZ if chemicals are injected (608.17.5)
  • Annual duties Inspect all assemblies and air gaps ; test assemblies (312.10.1, 312.10.2)

Loading diagram... Nonpotable water identification requirements