3.1 Minimum Fixture Counts, Separate Facilities, and Toilet Room Location

Colorado Journeyworker Plumber Journeyman Plumber

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Passing the Colorado Journeyworker Plumber Exam

1.1 Exam Blueprint, Format, and the 2024 Code Changeover 1.2 Colorado Licenses, Experience Hours, and Apprentice Supervision 1.3 Permits, Inspections, Blue Tags, and Board Enforcement

2 Chapter 2: General Regulations (IPC Chapter 3)

2.1 Approved Materials, Certification, and General Installation Rules 2.2 Protection of Pipes: Contact, Notching, Shield Plates, and Freezing 2.3 Piping Support, Trenching, Bedding, and Backfill 2.4 Required Tests: Water, Air, and Backflow Assembly Testing

3 Chapter 3: Fixtures and Equipment (IPC Chapter 4)

3.1 Minimum Fixture Counts, Separate Facilities, and Toilet Room Location 3.2 Fixture Clearances, Compartments, and Setting Requirements 3.3 Water Closets, Urinals, Lavatories, Sinks, and Flush Devices 3.4 Showers, Bathtubs, Fixture Fittings, and Scald Protection

4 Chapter 4: Water Heaters (IPC Chapter 5)

4.1 Water Heater Installation, Location, Access, and Clearances 4.2 Relief Valves and Discharge Piping 4.3 Water Heater Pans, Pan Drains, and Storage Tank Requirements 4.4 Thermal Expansion Control and Hot Water Temperature Limits

5 Chapter 5: Water Supply Materials and Installation (IPC Chapter 6)

5.1 Water Service and Distribution Materials, and Sewer Separation 5.2 Joints, Connections, and Dissimilar Materials in Water Piping 5.3 Valves, Shutoffs, and Required Valve Locations

6 Chapter 6: Water Supply Sizing and Pressure (IPC Chapter 6 and Appendix E)

6.1 Pressure Limits, Pressure Reducing Valves, and Water Hammer 6.2 Water Supply Fixture Units and Estimating Demand 6.3 Sizing Water Piping with Appendix E and Table E104.1

7 Chapter 7: Cross-Connection Control and Backflow Prevention (IPC Sections 608-610, Chapter 13)

7.1 Cross-Connection Principles, Backsiphonage, and Backpressure 7.2 Air Gaps and the Backflow Preventer Family 7.3 Applying Backflow Protection to Specific Connections 7.4 Nonpotable Water Systems, Identification, and Reclaimed Water

8 Chapter 8: Sanitary Drainage Materials and Fittings (IPC Chapter 7)

8.1 Sanitary Drainage Materials and Where Each May Be Used 8.2 Drainage Joints, Transitions, and Prohibited Connections 8.3 Fittings for Change of Direction and Drainage Flow Patterns

9 Chapter 9: Sanitary Drainage Sizing (IPC Sections 704, 709-711)

9.1 Drainage Fixture Units and Load Estimation 9.2 Slope of Horizontal Drainage and Installation Rules 9.3 Sizing Building Drains, Building Sewers, and Horizontal Branches 9.4 Stacks, Branch Intervals, and Offsets in Tall Buildings

10 Chapter 10: Cleanouts, Sumps and Below-Sewer Drainage (IPC Sections 708, 712-716)

10.1 Cleanouts, Manholes, and Access Requirements 10.2 Backwater Valves and Fixtures Below the Sewer Level 10.3 Sumps, Sewage Ejectors, and Macerating Toilet Systems 10.4 Building Sewers, Private Disposal, and Special Drainage Conditions

11 Chapter 11: Vent Fundamentals and Terminals (IPC Sections 901-905, 908)

11.1 How Vents Work, Trap Seal Loss, and the One-Inch Rule 11.2 Vent Terminals, Roof Penetrations, and Sidewall Terminations 11.3 Vent Connections, Grade, and the Six-Inch Rules

12 Chapter 12: Vent Types and Sizing (IPC Sections 906-911, 917)

12.1 Individual Vents, Common Vents, and Vents for Stack Offsets 12.2 Trap-to-Vent Distance, Trap Arms, and Fixture Drains 12.3 Sizing Stack Vents, Vent Stacks, Branch Vents, and Headers 12.4 Putting a Vent System Together: A Worked Building

13 Chapter 13: Engineered and Special Venting (IPC Sections 912-916, 918-920)

13.1 Horizontal and Vertical Wet Venting 13.2 Waste Stack Vents, Circuit Vents, and Combination Waste and Vent 13.3 Island Fixture Venting and Air Admittance Valves

14 Chapter 14: Traps, Interceptors and Separators (IPC Chapter 10)

14.1 Fixture Traps, Trap Seals, and Prohibited Trap Types 14.2 Trap Seal Protection, Primers, and Barrier Devices 14.3 Grease Interceptors, Oil Separators, and Solids Interceptors

15 Chapter 15: Indirect and Special Waste (IPC Chapter 8)

15.1 Where Indirect Waste Is Required, and Air Gap Versus Air Break 15.2 Waste Receptors, Hub Drains, and Standpipes 15.3 Special Wastes, Chemical Neutralization, and Health Care Drainage

16 Chapter 16: Storm Drainage (IPC Chapter 11 and Appendix B)

16.1 Storm Drainage Scope, Disposal, and Prohibited Connections 16.2 Storm Drainage Materials, Roof Drains, and Conductors 16.3 Secondary Roof Drains, Scuppers, and Controlled Flow Systems 16.4 Rainfall Rates, Roof Area, and the Flow-Rate Conversion 16.5 Sizing Vertical Conductors, Leaders, and Storm Drains 16.6 Gutters, Subsoil Drains, Building Subdrains, and Storm Sumps

17 Chapter 17: Residential Fire Sprinklers (IRC Section P2904)

17.1 Residential Fire Sprinkler Systems (IRC Section P2904)

18 Chapter 18: Isometric Analysis and Plumbing Calculations

18.1 Reading Plumbing Isometrics and Riser Diagrams 18.2 Analyzing a DWV Isometric for Code Compliance 18.3 Offsets, Travel, and the Plumbing Math the Exam Assumes

3.1 Minimum Fixture Counts, Separate Facilities, and Toilet Room Location

Key Takeaways Explain This Topic AI

IPC 403.1.1 requires the total occupant load to be divided in half to determine the load of each sex, with all resulting fractional numbers rounded up to the next whole number.

IPC 403.2 exempts structures or tenant spaces with a total occupant load of 15 or fewer, mercantile occupancies with 100 or fewer, and business occupancies with 25 or fewer from the separate-facilities requirement.

IPC 403.3.3 limits the path of travel to required toilet facilities to 500 feet and one story above or below in occupancies other than malls; the limit is 300 feet in covered and open mall buildings.

IPC 424.2 allows urinals to substitute for not more than 67 percent of required water closets in assembly and educational occupancies, and 50 percent in all other occupancies.

IPC 419.1 counts every 20 inches of rim space on a group wash fixture as one lavatory for Table 403.1 purposes.

Last updated: September 2026

The eight-item content area

Fixtures and Equipment supplies 8 scored items on the Journeyworker exam. Most of them come from four places: Table 403.1 counts, the 405.3.1 clearances, the fixture-specific outlet sizes in Sections 419 through 425, and the temperature-limiting requirements of Section 412. This section covers the first of those.

How the count is calculated — IPC 403.1.1

Getting the arithmetic right matters more than memorizing the table, because the table is open in front of you on exam day.

Determine the occupant load from the International Building Code. The IPC does not set occupant load.

Divide the total occupant load in half to get the load of each sex.

Apply the ratio for each fixture type from Table 403.1 to the load of each sex.

Round every fractional result up to the next whole number.

For multiple occupancies , sum the fractional numbers for each occupancy first , then round up.

Three exceptions to the divide-in-half rule:

Approved statistical data showing a distribution other than 50/50.

Multiple-user facilities designed to serve all genders , where the count is based on 100 percent of the total occupant load , each fixture type complies with ICC A117.1, and each urinal provided is located in a stall.

Where single-user water closet and bathing rooms are provided under 403.1.2.

IPC 403.1.2 counts single-user toilet and bathing rooms — including family or assisted-use rooms — toward the total required fixtures, and requires them to be identified as available to all persons regardless of sex. IPC 403.1.3 requires lavatories to be distributed proportionately to the required water closets where two or more toilet rooms serve each sex.

Worked count: a business occupancy

An office building has an occupant load of 180 .

Load per sex: 180 / 2 = 90 each .

Water closets , business: 1 per 25 for the first 50, then 1 per 50 for the remainder.

First 50 -> 50 / 25 = 2. Remainder 40 -> 40 / 50 = 0.8. Total 2.8 -> round up to 3 per sex.

Lavatories , business: 1 per 40 for the first 80, then 1 per 80 for the remainder.

First 80 -> 80 / 40 = 2. Remainder 10 -> 10 / 80 = 0.125. Total 2.125 -> round up to 3 per sex.

Drinking fountains : 1 per 100 -> 180 / 100 = 1.8 -> 2 total.

Service sink : 1 (not required at an occupant load of 15 or fewer, per footnote e).

Result: 3 water closets and 3 lavatories per sex, 2 drinking fountains, 1 service sink.

Substituting urinals: business is not assembly or educational, so urinals may replace not more than 50 percent of the male water closets (424.2). Three male water closets means 1 may be replaced by a urinal, since 50 percent of 3 is 1.5 and you cannot exceed 50 percent.

Reading Table 403.1

The table is organized by the eight IBC occupancy groups. Ratios you should recognize on sight:

  • Occupancy Water closets (M / F) Lavatories (M / F) Drinking fountain
  • Business 1 per 25 first 50, then 1 per 50 1 per 40 first 80, then 1 per 80 1 per 100
  • Educational 1 per 50 1 per 50 1 per 100
  • Mercantile 1 per 500 1 per 750 1 per 1,000
  • Factory and industrial 1 per 100 1 per 100 1 per 400
  • Restaurants, banquet halls, food courts 1 per 75 1 per 200 1 per 500
  • Nightclubs, bars, taverns, dance halls 1 per 40 1 per 75 1 per 500
  • Theaters and performing arts 1 per 125 / 1 per 65 1 per 200 1 per 500
  • Storage (low and moderate hazard) 1 per 100 1 per 100 1 per 1,000
  • Apartment house 1 per dwelling unit 1 per dwelling unit —
  • Dormitories (not transient) 1 per 10 1 per 10 1 per 100

Footnotes worth knowing:

a. One fixture is the minimum required for the stated number of persons or any fraction of that number.

b. Employee toilet facilities must be separate from facilities for inmates or care recipients.

d. The occupant load for seasonal outdoor seating and entertainment areas counts toward the minimum.

e. Business and mercantile with an occupant load of 15 or fewer do not require a service sink.

Apartment houses additionally require 1 kitchen sink per dwelling unit and 1 automatic clothes washer connection per 20 dwelling units ; one- and two-family dwellings require 1 kitchen sink and 1 clothes washer connection per dwelling unit .

Separate facilities and the six exceptions

IPC 403.2 : where plumbing fixtures are required, separate facilities shall be provided for each sex — unless one of six exceptions applies:

Dwelling units and sleeping units.

Structures or tenant spaces with a total occupant load of 15 or fewer , employees and customers combined.

Mercantile occupancies with a maximum occupant load of 100 or fewer .

Business occupancies with a maximum occupant load of 25 or fewer .

Where single-user toilet rooms are provided under 403.1.2.

Where rooms with both water closets and lavatories are designed for both sexes with water closet privacy per 405.3.4; urinals must be visually separated or each in a stall.

The three numeric thresholds — 15 total, 100 mercantile, 25 business — are a favorite exam target because they are easy to transpose.

Where the facilities must be

Rule Requirement

403.3 Public toilet facilities required for customers, patrons and visitors; employees must have toilet facilities

403.3 Exception Not required for unattended parking garages , or for quick-transaction spaces (takeout, pickup, drop-off) with public access area 300 square feet or less

403.3.1 Access Route shall not pass through kitchens, storage rooms or closets ; access from within or from the exterior of the building; available whenever the building is occupied

  • 403.3.2 Toilet rooms shall not open directly into a room used to prepare food for service to the public
  • 403.3.3 Other than malls: not more than one story above or below, path of travel not exceeding 500 feet

403.3.4 Covered and open malls: one story , 300 feet , measured from the main entrance of the store or tenant space

403.3.5 Pay facilities must be in excess of the required minimum; required facilities are free of charge

403.3.6 A multiple-occupant toilet room's egress door shall not be lockable from the inside (family/assisted-use rooms excepted)

403.5 Drinking fountains need not be in each tenant space if public fountains are within 500 feet (300 in a mall) and one story

403.6 Service sinks need not be in each mall tenant space if within 300 feet and one story, on an accessible route

IPC 403.4 requires signs designating the sex, readily visible near the entrance, with accessible-facility signs per IBC Section 1111, and 403.4.1 requires directional signage readable from the main entrance of the building or tenant space.

Accessible fixtures

IPC 404.1 sends the question of where accessible facilities are required to Chapter 11 of the International Building Code , and 404.2 sends how they are installed to ICC A117.1 . The IPC itself does not contain accessible stall dimensions. Note that IPC 405.3.1 contains a single accessibility-flavored exception of its own: an accessible children's water closet may be set as close as 12 inches from its center to the required partition or wall on one side.

Group wash fixtures and urinal substitution

IPC 419.1 : for determining the number of lavatories required by Table 403.1, every 20 inches of rim space on a group wash fixture counts as one lavatory . A 100-inch circular wash fountain therefore counts as five lavatories.

IPC 424.2 : urinals may substitute for not more than 67 percent of required water closets in assembly and educational occupancies, and not more than 50 percent in all other occupancies.

Colorado field note (not exam-scored): Board Rule 1.2(E)(1)(r) adds a sentence to 403.1 requiring the lavatory-to-water-closet-or-urinal ratios in Table 403.1 to be maintained in all restrooms , and Rule 1.2(E)(1)(s) requires new or remodeled state, county, city and municipal buildings (excluding K-12 schools) to provide an ADA-compliant single-user or multi-user non-gendered restroom under C.R.S. 9-5.7-103. Rule 1.2(E)(1)(t) excludes classroom toilet rooms and their lavatories from the Table 403.1 count.

Loading diagram... Minimum fixture count calculation sequence