3.4 Showers, Bathtubs, Fixture Fittings, and Scald Protection
Colorado Journeyworker Plumber Journeyman Plumber
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Passing the Colorado Journeyworker Plumber Exam
1.1 Exam Blueprint, Format, and the 2024 Code Changeover 1.2 Colorado Licenses, Experience Hours, and Apprentice Supervision 1.3 Permits, Inspections, Blue Tags, and Board Enforcement
2 Chapter 2: General Regulations (IPC Chapter 3)
2.1 Approved Materials, Certification, and General Installation Rules 2.2 Protection of Pipes: Contact, Notching, Shield Plates, and Freezing 2.3 Piping Support, Trenching, Bedding, and Backfill 2.4 Required Tests: Water, Air, and Backflow Assembly Testing
3 Chapter 3: Fixtures and Equipment (IPC Chapter 4)
3.1 Minimum Fixture Counts, Separate Facilities, and Toilet Room Location 3.2 Fixture Clearances, Compartments, and Setting Requirements 3.3 Water Closets, Urinals, Lavatories, Sinks, and Flush Devices 3.4 Showers, Bathtubs, Fixture Fittings, and Scald Protection
4 Chapter 4: Water Heaters (IPC Chapter 5)
4.1 Water Heater Installation, Location, Access, and Clearances 4.2 Relief Valves and Discharge Piping 4.3 Water Heater Pans, Pan Drains, and Storage Tank Requirements 4.4 Thermal Expansion Control and Hot Water Temperature Limits
5 Chapter 5: Water Supply Materials and Installation (IPC Chapter 6)
5.1 Water Service and Distribution Materials, and Sewer Separation 5.2 Joints, Connections, and Dissimilar Materials in Water Piping 5.3 Valves, Shutoffs, and Required Valve Locations
6 Chapter 6: Water Supply Sizing and Pressure (IPC Chapter 6 and Appendix E)
6.1 Pressure Limits, Pressure Reducing Valves, and Water Hammer 6.2 Water Supply Fixture Units and Estimating Demand 6.3 Sizing Water Piping with Appendix E and Table E104.1
7 Chapter 7: Cross-Connection Control and Backflow Prevention (IPC Sections 608-610, Chapter 13)
7.1 Cross-Connection Principles, Backsiphonage, and Backpressure 7.2 Air Gaps and the Backflow Preventer Family 7.3 Applying Backflow Protection to Specific Connections 7.4 Nonpotable Water Systems, Identification, and Reclaimed Water
8 Chapter 8: Sanitary Drainage Materials and Fittings (IPC Chapter 7)
8.1 Sanitary Drainage Materials and Where Each May Be Used 8.2 Drainage Joints, Transitions, and Prohibited Connections 8.3 Fittings for Change of Direction and Drainage Flow Patterns
9 Chapter 9: Sanitary Drainage Sizing (IPC Sections 704, 709-711)
9.1 Drainage Fixture Units and Load Estimation 9.2 Slope of Horizontal Drainage and Installation Rules 9.3 Sizing Building Drains, Building Sewers, and Horizontal Branches 9.4 Stacks, Branch Intervals, and Offsets in Tall Buildings
10 Chapter 10: Cleanouts, Sumps and Below-Sewer Drainage (IPC Sections 708, 712-716)
10.1 Cleanouts, Manholes, and Access Requirements 10.2 Backwater Valves and Fixtures Below the Sewer Level 10.3 Sumps, Sewage Ejectors, and Macerating Toilet Systems 10.4 Building Sewers, Private Disposal, and Special Drainage Conditions
11 Chapter 11: Vent Fundamentals and Terminals (IPC Sections 901-905, 908)
11.1 How Vents Work, Trap Seal Loss, and the One-Inch Rule 11.2 Vent Terminals, Roof Penetrations, and Sidewall Terminations 11.3 Vent Connections, Grade, and the Six-Inch Rules
12 Chapter 12: Vent Types and Sizing (IPC Sections 906-911, 917)
12.1 Individual Vents, Common Vents, and Vents for Stack Offsets 12.2 Trap-to-Vent Distance, Trap Arms, and Fixture Drains 12.3 Sizing Stack Vents, Vent Stacks, Branch Vents, and Headers 12.4 Putting a Vent System Together: A Worked Building
13 Chapter 13: Engineered and Special Venting (IPC Sections 912-916, 918-920)
13.1 Horizontal and Vertical Wet Venting 13.2 Waste Stack Vents, Circuit Vents, and Combination Waste and Vent 13.3 Island Fixture Venting and Air Admittance Valves
14 Chapter 14: Traps, Interceptors and Separators (IPC Chapter 10)
14.1 Fixture Traps, Trap Seals, and Prohibited Trap Types 14.2 Trap Seal Protection, Primers, and Barrier Devices 14.3 Grease Interceptors, Oil Separators, and Solids Interceptors
15 Chapter 15: Indirect and Special Waste (IPC Chapter 8)
15.1 Where Indirect Waste Is Required, and Air Gap Versus Air Break 15.2 Waste Receptors, Hub Drains, and Standpipes 15.3 Special Wastes, Chemical Neutralization, and Health Care Drainage
16 Chapter 16: Storm Drainage (IPC Chapter 11 and Appendix B)
16.1 Storm Drainage Scope, Disposal, and Prohibited Connections 16.2 Storm Drainage Materials, Roof Drains, and Conductors 16.3 Secondary Roof Drains, Scuppers, and Controlled Flow Systems 16.4 Rainfall Rates, Roof Area, and the Flow-Rate Conversion 16.5 Sizing Vertical Conductors, Leaders, and Storm Drains 16.6 Gutters, Subsoil Drains, Building Subdrains, and Storm Sumps
17 Chapter 17: Residential Fire Sprinklers (IRC Section P2904)
17.1 Residential Fire Sprinkler Systems (IRC Section P2904)
18 Chapter 18: Isometric Analysis and Plumbing Calculations
18.1 Reading Plumbing Isometrics and Riser Diagrams 18.2 Analyzing a DWV Isometric for Code Compliance 18.3 Offsets, Travel, and the Plumbing Math the Exam Assumes
3.4 Showers, Bathtubs, Fixture Fittings, and Scald Protection
Key Takeaways Explain This Topic AI
IPC 421.4 requires shower compartments of not less than 900 square inches of interior cross-sectional area and not less than 30 inches in least dimension, with a 25-inch/1,300-square-inch alternative.
IPC 421.4.2 requires a shower compartment access and egress opening with a clear unobstructed finished width of not less than 22 inches.
IPC 412.3 requires individual shower and tub-shower valves to be balanced-pressure, thermostatic or combination valves limited to a maximum setting of 120 degrees F.
IPC 421.5.2 requires shower liners to turn up not less than 2 inches above the finished threshold, be pitched 1/4 inch per foot, and never be nailed or perforated less than 1 inch above the threshold.
IPC 421.4.1 requires shower and tub wall materials to extend not less than 6 feet above the room floor and not less than 70 inches above the tub or shower drain.
Last updated: September 2026
Shower compartment geometry
IPC 421.4 sets two dimensions that must both be satisfied:
Not less than 900 square inches of interior cross-sectional area, and
not less than 30 inches in least dimension , measured from the finished interior dimension of the compartment, exclusive of fixture valves, shower heads, soap dishes and safety grab bars or rails.
The measurement is taken at a height equal to the top of the threshold, at a point tangent to its centerline , and must be continued to a height of not less than 70 inches above the shower drain outlet . In other words, a compartment that pinches in above the threshold does not comply just because it measures 30 inches at the curb.
Exception: a compartment with not less than 25 inches in minimum dimension is permitted provided it has not less than 1,300 square inches of cross-sectional area.
A 30 x 30 inch compartment yields exactly 900 square inches and complies. A 25 x 52 inch compartment yields 1,300 square inches and complies under the exception. A 28 x 34 inch compartment (952 square inches) fails — it beats the area minimum but falls below the 30-inch least dimension and does not reach 1,300 square inches.
IPC 421.4.2 Access: the shower compartment access and egress opening must have a clear and unobstructed finished width of not less than 22 inches . Compartments required to be accessible comply with IPC 404.1 and ICC A117.1 instead.
Wall and floor construction
IPC 421.4.1 requires bathtub floors, shower floors, wall areas above built-in tubs that have shower heads, and shower compartment walls to be of smooth, corrosion-resistant, nonabsorbent waterproof materials . Wall materials must extend:
not less than 6 feet above the room floor level , and
not less than 70 inches above the drain of the tub or shower.
Those walls must form a watertight joint with each other and with the tub or shower floor.
IPC 421.5 requires floor surfaces of impervious, noncorrosive, nonabsorbent and waterproof materials, and 421.5.1 requires floors or receptors to be laid on and supported by a smooth and structurally sound base .
Shower liners — IPC 421.5.2
Except where a prefabricated receptor is used, shower floors must be lined and made watertight . The installation rules are specific and heavily tested:
Liners turn up on all sides not less than 2 inches above the finished threshold level .
Liners are recessed and fastened to an approved backing so as not to occupy the space required for wall covering.
Liners shall not be nailed or perforated at any point less than 1 inch above the finished threshold .
Liners are pitched 1/4 unit vertical in 12 units horizontal (2-percent slope) , sloped toward the fixture drain, and securely fastened to the waste outlet at the seepage entrance making a watertight joint.
The completed liner is tested per IPC 312.9 — potable water at least 2 inches deep at the threshold, 15 minutes, no leakage.
Approved liner materials and their thresholds:
- Material Requirement
- Plasticized PVC sheet ASTM D4551, solvent welded per manufacturer
- Chlorinated polyethylene (CPE) sheet ASTM D4068
Sheet lead not less than 4 pounds per square foot , coated with asphalt paint, insulated by 15-pound asphalt felt, joined by burning
Sheet copper ASTM B152, not less than 12 ounces per square foot , insulated by 15-pound asphalt felt, joined by brazing or soldering
- Sheet-applied bonded membrane ANSI A118.10 (need not be recessed)
- Liquid trowel-applied bonded material ANSI A118.10
Two exceptions to the lining requirement: floor surfaces under shower heads provided for rinsing laid directly on the ground , and sheet-applied load-bearing bonded waterproof membranes, which need not be recessed.
Colorado field note: Board Rule 1.2(E)(1)(p) deletes IPC 312.9 shower liner test from the Colorado Plumbing Code, and Rule 1.2(D)(7) declares shower wall composition (421.4.1) and shower floors (421.5) to be informational only in Colorado, not subject to licensing, permitting or inspection, because they are typically not installed by plumbers. The model-code requirements still control on the exam.
Shower waste outlets and risers
IPC 421.3 : shower waste outlets are not less than 1-1/2 inches in diameter. Other than in bathtubs, they must have removable strainers not less than 3 inches in diameter with strainer openings not less than 1/4 inch in least dimension . Where each shower space does not have its own waste outlet, the outlet must be located and the floor pitched so waste from one shower does not flow across the area serving another. Outlets are fastened to the waste pipe in an approved manner.
IPC 421.2 : water supply risers from the shower valve to the shower head outlet, whether exposed or concealed , must be attached to the structure using support devices designed for the specific piping material or fittings anchored with screws. This is why a PEX shower riser must land in a drop-ear elbow screwed to blocking, not float free in the wall.
Scald protection — the 120-degree family of rules
This cluster is the single richest source of Fixtures and Equipment exam items. Learn which device belongs to which fixture.
Fixture Section Required device Limit
Individual shower / tub-shower valve 412.3 Balanced-pressure, thermostatic or combination valve to ASSE 1016/ASME A112.1016/CSA B125.16 or ASME A112.18.1 max setting 120 F
Multiple (gang) showers, single tempered supply 412.4 Automatic temperature control mixing valve to ASSE 1069 or CSA B125.3 , or individual point-of-use valves max setting 120 F , access required to the ASSE 1069 valve
Bathtub / whirlpool valve (not a combo tub/shower) 412.5 Water-temperature-limiting device to ASSE 1070 , or a water heater to ASSE 1082 or 1084 max setting 120 F
- Individual fixture fitting 412.7 Temperature-actuated flow-reduction device to ASSE 1062 120 F
- Public hand-washing lavatory 419.5 ASSE 1070 limiting device tempered (85-110 F)
- Bidet 408.3 ASSE 1070 limiting device 110 F
- Footbath / pedicure bath 423.3 ASSE 1070 device or ASSE 1082 water heater 120 F
Head shampoo sink faucet 412.10 ASSE 1070 device, ASSE 1082 heater, or ASSE 1062 device; integral check valves 120 F
Tankless water heater outlet 501.6 — 140 F for domestic use
Two rules that generate distractors:
412.3 : the valve must be installed at the point of use , must be rated for the flow rate of the installed shower head , and the maximum setting is field adjusted per the manufacturer's instructions . In-line thermostatic valves shall not be used to satisfy this section.
412.7 : an ASSE 1062 flow-reduction device shall not be used alone as a substitute for the shower valve required by 412.3 or the tub valve required by 412.5.
Fixture fittings generally
412.1 : faucets and fixture fittings conform to ASME A112.18.1/CSA B125.1 ; fittings supplying drinking water for human ingestion conform to NSF 61, Section 9 ; flexible water connectors exposed to continuous pressure comply with IPC 605.6.
412.1.1 : faucets and supply fittings must meet the 604.4 consumption limits.
412.1.2 : waste fittings conform to ASME A112.18.2/CSA B125.2, ASTM F409, or a standard listed in Tables 702.1 and 702.4.
412.2 : hand-held showers must provide backflow protection per ASME A112.18.1 or a device complying with ASME A112.18.3.
412.6 : faucets and fittings with hose-connected outlets conform to ASME A112.18.3 or ASME A112.18.1.
412.8 : deck-mounted bath/shower transfer valves with an integral atmospheric vacuum breaker conform to ASME A112.18.1.
Colorado field note (not exam-scored): Colorado adds 421.7, requiring shower heads to be on the sidewall of the compartment or arranged so the head does not discharge directly at the entrance and the bather can adjust the valve before stepping into the spray (roll-in accessible showers excepted); and 421.8, permitting a shower or tub/shower control valve only where the spout or head discharges into an approved tub or shower compartment , excepting emergency showers.