3.3 Water Closets, Urinals, Lavatories, Sinks, and Flush Devices

Colorado Journeyworker Plumber Journeyman Plumber

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Passing the Colorado Journeyworker Plumber Exam

1.1 Exam Blueprint, Format, and the 2024 Code Changeover 1.2 Colorado Licenses, Experience Hours, and Apprentice Supervision 1.3 Permits, Inspections, Blue Tags, and Board Enforcement

2 Chapter 2: General Regulations (IPC Chapter 3)

2.1 Approved Materials, Certification, and General Installation Rules 2.2 Protection of Pipes: Contact, Notching, Shield Plates, and Freezing 2.3 Piping Support, Trenching, Bedding, and Backfill 2.4 Required Tests: Water, Air, and Backflow Assembly Testing

3 Chapter 3: Fixtures and Equipment (IPC Chapter 4)

3.1 Minimum Fixture Counts, Separate Facilities, and Toilet Room Location 3.2 Fixture Clearances, Compartments, and Setting Requirements 3.3 Water Closets, Urinals, Lavatories, Sinks, and Flush Devices 3.4 Showers, Bathtubs, Fixture Fittings, and Scald Protection

4 Chapter 4: Water Heaters (IPC Chapter 5)

4.1 Water Heater Installation, Location, Access, and Clearances 4.2 Relief Valves and Discharge Piping 4.3 Water Heater Pans, Pan Drains, and Storage Tank Requirements 4.4 Thermal Expansion Control and Hot Water Temperature Limits

5 Chapter 5: Water Supply Materials and Installation (IPC Chapter 6)

5.1 Water Service and Distribution Materials, and Sewer Separation 5.2 Joints, Connections, and Dissimilar Materials in Water Piping 5.3 Valves, Shutoffs, and Required Valve Locations

6 Chapter 6: Water Supply Sizing and Pressure (IPC Chapter 6 and Appendix E)

6.1 Pressure Limits, Pressure Reducing Valves, and Water Hammer 6.2 Water Supply Fixture Units and Estimating Demand 6.3 Sizing Water Piping with Appendix E and Table E104.1

7 Chapter 7: Cross-Connection Control and Backflow Prevention (IPC Sections 608-610, Chapter 13)

7.1 Cross-Connection Principles, Backsiphonage, and Backpressure 7.2 Air Gaps and the Backflow Preventer Family 7.3 Applying Backflow Protection to Specific Connections 7.4 Nonpotable Water Systems, Identification, and Reclaimed Water

8 Chapter 8: Sanitary Drainage Materials and Fittings (IPC Chapter 7)

8.1 Sanitary Drainage Materials and Where Each May Be Used 8.2 Drainage Joints, Transitions, and Prohibited Connections 8.3 Fittings for Change of Direction and Drainage Flow Patterns

9 Chapter 9: Sanitary Drainage Sizing (IPC Sections 704, 709-711)

9.1 Drainage Fixture Units and Load Estimation 9.2 Slope of Horizontal Drainage and Installation Rules 9.3 Sizing Building Drains, Building Sewers, and Horizontal Branches 9.4 Stacks, Branch Intervals, and Offsets in Tall Buildings

10 Chapter 10: Cleanouts, Sumps and Below-Sewer Drainage (IPC Sections 708, 712-716)

10.1 Cleanouts, Manholes, and Access Requirements 10.2 Backwater Valves and Fixtures Below the Sewer Level 10.3 Sumps, Sewage Ejectors, and Macerating Toilet Systems 10.4 Building Sewers, Private Disposal, and Special Drainage Conditions

11 Chapter 11: Vent Fundamentals and Terminals (IPC Sections 901-905, 908)

11.1 How Vents Work, Trap Seal Loss, and the One-Inch Rule 11.2 Vent Terminals, Roof Penetrations, and Sidewall Terminations 11.3 Vent Connections, Grade, and the Six-Inch Rules

12 Chapter 12: Vent Types and Sizing (IPC Sections 906-911, 917)

12.1 Individual Vents, Common Vents, and Vents for Stack Offsets 12.2 Trap-to-Vent Distance, Trap Arms, and Fixture Drains 12.3 Sizing Stack Vents, Vent Stacks, Branch Vents, and Headers 12.4 Putting a Vent System Together: A Worked Building

13 Chapter 13: Engineered and Special Venting (IPC Sections 912-916, 918-920)

13.1 Horizontal and Vertical Wet Venting 13.2 Waste Stack Vents, Circuit Vents, and Combination Waste and Vent 13.3 Island Fixture Venting and Air Admittance Valves

14 Chapter 14: Traps, Interceptors and Separators (IPC Chapter 10)

14.1 Fixture Traps, Trap Seals, and Prohibited Trap Types 14.2 Trap Seal Protection, Primers, and Barrier Devices 14.3 Grease Interceptors, Oil Separators, and Solids Interceptors

15 Chapter 15: Indirect and Special Waste (IPC Chapter 8)

15.1 Where Indirect Waste Is Required, and Air Gap Versus Air Break 15.2 Waste Receptors, Hub Drains, and Standpipes 15.3 Special Wastes, Chemical Neutralization, and Health Care Drainage

16 Chapter 16: Storm Drainage (IPC Chapter 11 and Appendix B)

16.1 Storm Drainage Scope, Disposal, and Prohibited Connections 16.2 Storm Drainage Materials, Roof Drains, and Conductors 16.3 Secondary Roof Drains, Scuppers, and Controlled Flow Systems 16.4 Rainfall Rates, Roof Area, and the Flow-Rate Conversion 16.5 Sizing Vertical Conductors, Leaders, and Storm Drains 16.6 Gutters, Subsoil Drains, Building Subdrains, and Storm Sumps

17 Chapter 17: Residential Fire Sprinklers (IRC Section P2904)

17.1 Residential Fire Sprinkler Systems (IRC Section P2904)

18 Chapter 18: Isometric Analysis and Plumbing Calculations

18.1 Reading Plumbing Isometrics and Riser Diagrams 18.2 Analyzing a DWV Isometric for Code Compliance 18.3 Offsets, Travel, and the Plumbing Math the Exam Assumes

3.3 Water Closets, Urinals, Lavatories, Sinks, and Flush Devices

Key Takeaways Explain This Topic AI

IPC Table 604.4 limits water closets to 1.6 gallons per flushing cycle and urinals to 1.0 gallon per flushing cycle.

IPC 425.2 and 425.3 require elongated bowls and hinged open-front seats for water closets in public or employee toilet facilities.

IPC 419.3 requires lavatory waste outlets not less than 1-1/4 inches in diameter, and IPC 422.2 requires sink waste outlets not less than 1-1/2 inches.

IPC 413.3 requires floor drains to have a drain outlet not less than 2 inches in diameter, increasing to 3 inches in public laundries and central washing facilities (413.4).

IPC 425.4 accepts a 4-inch by 3-inch closet bend, and requires a 4-inch by 3-inch flange to receive the fixture horn where a 3-inch bend is used.

Last updated: September 2026

Flow rates and flush volumes — IPC Table 604.4

Section 401.3 sends every fixture and fitting to Table 604.4 for maximum water use. These seven rows are worth memorizing outright:

  • Fixture or fitting Maximum flow rate or quantity
  • Water closet 1.6 gallons per flushing cycle
  • Urinal 1.0 gallon per flushing cycle
  • Shower head 2.5 gpm at 80 psi
  • Lavatory, private 2.2 gpm at 60 psi
  • Lavatory, public (metering) 0.25 gallon per metering cycle
  • Lavatory, public (other than metering) 0.5 gpm at 60 psi
  • Sink faucet 2.2 gpm at 60 psi

Two footnotes: a hand-held shower spray is a shower head (so it carries the 2.5 gpm limit), and consumption tolerances come from the referenced standards.

The pressure reference changes with the fixture — 80 psi for shower heads, 60 psi for lavatory and sink faucets. That difference shows up in exam distractors.

Water closets — Section 425

Rule Requirement

425.1 Conform to Table 604.4 consumption and to ASME A112.19.2/CSA B45.1, ASME A112.19.3/CSA B45.4 or CSA B45.5/IAPMO Z124

  • 425.1.3 Dual-flush devices comply with ASME A112.19.14
  • 425.2 Bowls for public or employee toilet facilities shall be of the elongated type

425.3 Seats of smooth, nonabsorbent material; public or employee seats shall be hinged open-front ; integral seats of the same material as the fixture

425.4 A 4-inch by 3-inch closet bend is acceptable; where a 3-inch bend is used, install a 4-inch by 3-inch flange to receive the fixture horn

IPC 401.2 prohibits water closets having a concealed trap seal , an unventilated space , or walls not thoroughly washed at each discharge , and prohibits any water closet that permits siphonage of the bowl contents back into the tank . Trough urinals are prohibited outright.

Remember the companion drainage rule from IPC 704.2: a 4-inch by 3-inch closet flange, a closet bend with a 4-inch inlet and 3-inch outlet (4-inch leg upright and below), and an offset closet flange are not considered reductions in size in the direction of flow.

Flushing devices — Section 415

415.1 Every water closet, urinal, and similar fixture must be provided with a flushing device, and 415.1.1 requires a separate flushing device for each fixture .

415.2 Flushometer valves and tanks conform to ASSE 1037/ASME A112.1037/CSA B125.37.

415.3.1 Fill valves conform to ASSE 1002/ASME A112.1002/CSA B125.12 or CSA B125.3, with the fill valve backflow preventer located not less than 1 inch above the full opening of the overflow pipe .

415.3.2 Overflows in flush tanks shall discharge to the water closet or urinal connected to the tank, and shall be sized to prevent flooding the tank at the maximum rate at which the tank is supplied with water under the manufacturer's design conditions. The overflow pipe opening shall be located above the flood level rim of the water closet or urinal, or above a secondary overflow in the tank.

415.3.4 Access is required to flush tank interiors.

Urinals — Section 424

Beyond the 1.0-gallon limit and the 67/50 percent substitution rule from 424.2, urinals are governed by 405.3.5 partitions (30 inches apart, 12 inches up from the floor, 60 inches high, 18 inches out or 6 inches past the lip) and by the 15-inch centerline and 21-inch front clearances of 405.3.1. Table 709.1 gives a nonwater-supplied urinal a drainage fixture unit value of 1/2 , against 2 dfu for a urinal of 1 gallon per flush or less and 4 dfu for any other urinal.

Lavatories — Section 419

Rule Requirement

419.1 Conform to ASME A112.19.1/CSA B45.2, A112.19.2, A112.19.3 or CSA B45.5/IAPMO Z124; 20 inches of group wash rim space = one lavatory

419.3 Waste outlet not less than 1-1/4 inches , with a strainer, pop-up stopper, crossbar or other device restricting the clear opening

419.4 Movable lavatory systems comply with ASME A112.19.12

419.5 Tempered water must be delivered from lavatories and group wash fixtures in public toilet facilities provided for customers, patrons and visitors, through an ASSE 1070/ASME A112.1070/CSA B125.70 limiting device

"Tempered water" is defined in the code as water ranging in temperature from 85 degrees F to 110 degrees F .

Sinks, dishwashers and food waste disposers

IPC 422.2 : sink waste outlets not less than 1-1/2 inches , with a strainer or crossbar restricting the clear opening.

IPC 416.2 : domestic food waste disposers shall be connected to a drain not less than 1-1/2 inches in diameter.

IPC 416.3 : commercial food waste disposers shall be connected to a drain not less than 1-1/2 inches in diameter, and shall be connected and trapped separately from any other fixtures or sink compartments .

IPC 416.4 : food waste disposers shall be provided with a supply of cold water , protected against backflow by an air gap or backflow preventer in accordance with Section 608.

IPC 409.4 : a residential dishwasher waste connection shall connect directly to a wye branch fitting on the tailpiece of the kitchen sink , directly to the dishwasher connection of a food waste disposer , or through an air break to a standpipe . The waste line shall rise and be securely fastened to the underside of the sink rim or countertop .

IPC 409.2 : dishwashing machines require backflow protection per Section 608.

Bathtubs, bidets and specialty fixtures

IPC 407.2 : bathtub waste outlets not less than 1-1/2 inches ; overflows conform to the same standards.

IPC 408.3 : bidet water temperature is limited to not greater than 110 degrees F by a water-temperature-limiting device conforming to ASSE 1070.

IPC 423.1 : baptisteries, ornamental and lily pools, aquariums, fountain basins and swimming pools with water supplies must be protected against backflow per Section 608 .

IPC 423.3 : pedicure chairs with an integral foot bathtub, and footbaths, are limited to not greater than 120 degrees F .

IPC 412.10 : head shampoo sink faucets are limited to not more than 120 degrees F and must have integral check valves preventing crossover between hot and cold.

Drinking fountains — Section 410

410.3.1 : where drinking fountains are provided on an exterior site, a floor, or within a secured area, not fewer than two must be provided — one for people who use a wheelchair and one for standing persons . A single fountain with two separate spouts meeting both may substitute.

410.3.2 : where more than the minimum is provided, 50 percent must serve wheelchair users and 50 percent standing persons.

410.4 : where a restaurant provides drinking water in a container free of charge , drinking fountains are not required there. In other occupancies where three or more fountains are required, water dispensers may substitute for not more than 50 percent .

410.5 : drinking fountains, water coolers and water dispensers shall not be installed in public restrooms .

Colorado field note (not exam-scored): Board Rule 1.2(E)(1)(u) broadens 410.4 to cover restaurants and A-2 occupancies , and Rule 1.2(E)(1)(nn) adds section 802.1.8 expressly allowing a domestic dishwasher to connect to a separately trapped standpipe with an air break or air gap.

Floor and trench drains — Section 413

  • Rule Requirement
  • 413.1 Floor drains conform to ASME A112.3.1, ASME A112.6.3 or CSA B79; trench drains to ASME A112.6.3

413.2 Removable strainers ; constructed so the drain can be cleaned; access to the drain inlet and ready access to floor drains (refrigerated display case drains need access only)

413.3 Drain outlet not less than 2 inches in diameter

413.4 Public coin-operated laundries and multiple-family central washing facilities: floor drains located to drain the entire floor area, outlet not less than 3 inches

Pair 413.3 with the rodentproofing rule in IPC 304.2 — strainer plate openings not greater than 1/2 inch in least dimension — and with the trap-seal protection requirements of Chapter 14 of this guide.

Loading diagram... Minimum fixture waste outlet sizes