8.2 Drainage Joints, Transitions, and Prohibited Connections
Colorado Journeyworker Plumber Journeyman Plumber
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Passing the Colorado Journeyworker Plumber Exam
1.1 Exam Blueprint, Format, and the 2024 Code Changeover 1.2 Colorado Licenses, Experience Hours, and Apprentice Supervision 1.3 Permits, Inspections, Blue Tags, and Board Enforcement
2 Chapter 2: General Regulations (IPC Chapter 3)
2.1 Approved Materials, Certification, and General Installation Rules 2.2 Protection of Pipes: Contact, Notching, Shield Plates, and Freezing 2.3 Piping Support, Trenching, Bedding, and Backfill 2.4 Required Tests: Water, Air, and Backflow Assembly Testing
3 Chapter 3: Fixtures and Equipment (IPC Chapter 4)
3.1 Minimum Fixture Counts, Separate Facilities, and Toilet Room Location 3.2 Fixture Clearances, Compartments, and Setting Requirements 3.3 Water Closets, Urinals, Lavatories, Sinks, and Flush Devices 3.4 Showers, Bathtubs, Fixture Fittings, and Scald Protection
4 Chapter 4: Water Heaters (IPC Chapter 5)
4.1 Water Heater Installation, Location, Access, and Clearances 4.2 Relief Valves and Discharge Piping 4.3 Water Heater Pans, Pan Drains, and Storage Tank Requirements 4.4 Thermal Expansion Control and Hot Water Temperature Limits
5 Chapter 5: Water Supply Materials and Installation (IPC Chapter 6)
5.1 Water Service and Distribution Materials, and Sewer Separation 5.2 Joints, Connections, and Dissimilar Materials in Water Piping 5.3 Valves, Shutoffs, and Required Valve Locations
6 Chapter 6: Water Supply Sizing and Pressure (IPC Chapter 6 and Appendix E)
6.1 Pressure Limits, Pressure Reducing Valves, and Water Hammer 6.2 Water Supply Fixture Units and Estimating Demand 6.3 Sizing Water Piping with Appendix E and Table E104.1
7 Chapter 7: Cross-Connection Control and Backflow Prevention (IPC Sections 608-610, Chapter 13)
7.1 Cross-Connection Principles, Backsiphonage, and Backpressure 7.2 Air Gaps and the Backflow Preventer Family 7.3 Applying Backflow Protection to Specific Connections 7.4 Nonpotable Water Systems, Identification, and Reclaimed Water
8 Chapter 8: Sanitary Drainage Materials and Fittings (IPC Chapter 7)
8.1 Sanitary Drainage Materials and Where Each May Be Used 8.2 Drainage Joints, Transitions, and Prohibited Connections 8.3 Fittings for Change of Direction and Drainage Flow Patterns
9 Chapter 9: Sanitary Drainage Sizing (IPC Sections 704, 709-711)
9.1 Drainage Fixture Units and Load Estimation 9.2 Slope of Horizontal Drainage and Installation Rules 9.3 Sizing Building Drains, Building Sewers, and Horizontal Branches 9.4 Stacks, Branch Intervals, and Offsets in Tall Buildings
10 Chapter 10: Cleanouts, Sumps and Below-Sewer Drainage (IPC Sections 708, 712-716)
10.1 Cleanouts, Manholes, and Access Requirements 10.2 Backwater Valves and Fixtures Below the Sewer Level 10.3 Sumps, Sewage Ejectors, and Macerating Toilet Systems 10.4 Building Sewers, Private Disposal, and Special Drainage Conditions
11 Chapter 11: Vent Fundamentals and Terminals (IPC Sections 901-905, 908)
11.1 How Vents Work, Trap Seal Loss, and the One-Inch Rule 11.2 Vent Terminals, Roof Penetrations, and Sidewall Terminations 11.3 Vent Connections, Grade, and the Six-Inch Rules
12 Chapter 12: Vent Types and Sizing (IPC Sections 906-911, 917)
12.1 Individual Vents, Common Vents, and Vents for Stack Offsets 12.2 Trap-to-Vent Distance, Trap Arms, and Fixture Drains 12.3 Sizing Stack Vents, Vent Stacks, Branch Vents, and Headers 12.4 Putting a Vent System Together: A Worked Building
13 Chapter 13: Engineered and Special Venting (IPC Sections 912-916, 918-920)
13.1 Horizontal and Vertical Wet Venting 13.2 Waste Stack Vents, Circuit Vents, and Combination Waste and Vent 13.3 Island Fixture Venting and Air Admittance Valves
14 Chapter 14: Traps, Interceptors and Separators (IPC Chapter 10)
14.1 Fixture Traps, Trap Seals, and Prohibited Trap Types 14.2 Trap Seal Protection, Primers, and Barrier Devices 14.3 Grease Interceptors, Oil Separators, and Solids Interceptors
15 Chapter 15: Indirect and Special Waste (IPC Chapter 8)
15.1 Where Indirect Waste Is Required, and Air Gap Versus Air Break 15.2 Waste Receptors, Hub Drains, and Standpipes 15.3 Special Wastes, Chemical Neutralization, and Health Care Drainage
16 Chapter 16: Storm Drainage (IPC Chapter 11 and Appendix B)
16.1 Storm Drainage Scope, Disposal, and Prohibited Connections 16.2 Storm Drainage Materials, Roof Drains, and Conductors 16.3 Secondary Roof Drains, Scuppers, and Controlled Flow Systems 16.4 Rainfall Rates, Roof Area, and the Flow-Rate Conversion 16.5 Sizing Vertical Conductors, Leaders, and Storm Drains 16.6 Gutters, Subsoil Drains, Building Subdrains, and Storm Sumps
17 Chapter 17: Residential Fire Sprinklers (IRC Section P2904)
17.1 Residential Fire Sprinkler Systems (IRC Section P2904)
18 Chapter 18: Isometric Analysis and Plumbing Calculations
18.1 Reading Plumbing Isometrics and Riser Diagrams 18.2 Analyzing a DWV Isometric for Code Compliance 18.3 Offsets, Travel, and the Plumbing Math the Exam Assumes
8.2 Drainage Joints, Transitions, and Prohibited Connections
Key Takeaways Explain This Topic AI
IPC 707.1 prohibits cement or concrete joints, mastic or hot-pour bituminous joints, unapproved fittings, joints between different diameter pipes made with elastomeric rolling O-rings, solvent-cement joints between different types of plastic pipe, and saddle-type fittings.
IPC 705.16.1 requires copper pipe or tubing to cast-iron hub pipe to be joined by a brass ferrule or compression joint.
IPC 705.16.2 requires a brass converter fitting or dielectric fitting between copper or copper-alloy pipe and galvanized steel pipe.
IPC 705.17 permits drainage slip joints only on the trap inlet, trap outlet and within the trap seal.
IPC 705.10.2 requires PVC solvent-cement joints to be made with primer conforming to ASTM F656 and cement conforming to ASTM D2564.
Last updated: September 2026
Prohibited joints and connections — IPC 707.1
Six items. Learn them as a list, because exam questions ask which one is not permitted.
Cement or concrete joints.
Mastic or hot-pour bituminous joints.
Joints made with fittings not approved for the specific installation.
Joints between different diameter pipes made with elastomeric rolling O-rings.
Solvent-cement joints between different types of plastic pipe , except as provided in Section 705.16.4.
Saddle-type fittings.
Compare the water-supply list in IPC 605.9 , which shares items 1, 2, 3, 5 and 6 but does not include the elastomeric rolling O-ring item. Item 4 exists because a rolling O-ring depends on precise annular geometry; between different diameters it cannot seal reliably.
Saddle fittings appear on both lists. Cutting a hole in an existing main and strapping on a saddle is prohibited on the supply side and the drainage side alike.
Joining methods by drainage material
- Material Section Permitted joints
- ABS 705.2 Mechanical, solvent cementing (ASTM D2235), threaded, push-fit
Cast iron 705.3 Caulked (lead and oakum), compression gasket (ASTM C564), mechanical joint coupling (shielded, CISPI 310 or ASTM C1277/C1540)
- Concrete 705.4 Per ASTM C443 gaskets
- Copper pipe 705.5 Brazed, mechanical, solder , threaded, welded
- Copper tubing 705.6 Brazed, mechanical, solder
- Borosilicate glass 705.7 Caulked, per manufacturer
- Steel 705.8 Threaded (ASME B1.20.1), mechanical
Lead 705.9 Burned (lead-to-lead, fused) or wiped (minimum 0.75 inch exposed solder, 0.375 inch thickness at the thickest point)
- PVC 705.10 Mechanical, solvent cementing (primer ASTM F656, cement ASTM D2564), threaded, push-fit
- Vitrified clay 705.11 Compression, per ASTM C425
- PE 705.12 Heat fusion , mechanical
- Polyolefin 705.13 Heat fusion , mechanical and compression sleeve
- PVDF 705.14 Heat fusion , mechanical and compression sleeve
- Polypropylene 705.15 Per the referenced standards
- Stainless steel drainage 705.20 Per ASME A112.3.1
Colorado field note (not exam-scored): Board Rule 1.2(E)(1)(jj) deletes the exception in IPC 705.10.2 — the exception that otherwise permits a one-step cement without primer on certain PVC joints. In Colorado, primer is required on those solvent-cement joints.
Joints between different materials — IPC 705.16
Transitions are where DWV systems leak and where inspectors look first.
- Transition Required method Section
- Copper pipe or tubing to cast-iron hub pipe Brass ferrule or compression joint 705.16.1
Copper or copper-alloy pipe or tubing to galvanized steel pipe Brass converter fitting or dielectric fitting ; the copper end soldered or brazed into the fitting 705.16.2
- Cast-iron pipe to galvanized steel pipe Caulked or threaded adapter fitting 705.16.3
- Plastic pipe or tubing to other piping material Approved adapter fitting 705.16.4
- Lead pipe to other piping material Wiped joint to a caulking ferrule, soldering nipple or bushing 705.16.5
- Borosilicate glass to other materials Approved adapter fitting 705.16.6
- Stainless steel drainage systems to other materials Approved adapter fitting 705.16.7
Two supporting tables set dimensions for the transition hardware:
Table 705.18 Caulking ferrules : a 2-inch ferrule has an inside diameter of 2-1/4 inches , a length of 4-1/2 inches and a minimum weight of 1 pound ; a 4-inch ferrule is 4-1/4 inches inside diameter, 4-1/2 inches long, and weighs at least 2 pounds 8 ounces.
Table 705.19 Soldering bushings : of copper or copper alloy ; a 2-inch bushing weighs at least 14 ounces , a 3-inch bushing 2 pounds , and a 4-inch bushing 3 pounds 8 ounces .
Drainage slip joints — IPC 705.17
Slip joints shall be made with an approved elastomeric gasket and shall only be installed on the trap inlet, trap outlet and within the trap seal .
Identical in substance to the fixture-side rule of IPC 405.9 , which adds that a concealed slip joint requires an access panel or utility space not less than 12 inches in its smallest dimension . A tubular slip-joint connection buried in a finished wall or ceiling violates both sections.
Fittings and changes of direction — IPC 706
IPC 706.1 : connections and changes in direction shall be made with approved drainage fittings ; connections between drainage piping and fixtures conform to Section 405.
IPC 706.2 Obstructions : fittings shall not have ledges, shoulders or reductions capable of retarding or obstructing flow . Threaded drainage pipe fittings shall be of the recessed drainage type — the reason you cannot use a standard black-iron threaded tee on a drainage line. The section does not apply to tubular waste fittings conveying vertical flow upstream of the trap seal liquid level .
IPC 706.4 Heel- or side-inlet quarter bends :
Heel-inlet quarter bends are acceptable except where the quarter bend serves a water closet .
A low-heel inlet shall not be used as a wet-vented connection .
Side-inlet quarter bends are acceptable for drainage, wet venting and stack venting arrangements.
Reduction in size, and the water closet exceptions
IPC 704.2 : the size of drainage piping shall not be reduced in the direction of flow. Three arrangements are expressly not considered reductions:
A 4-inch by 3-inch water closet flange .
A water closet bend fitting with a 4-inch inlet and a 3-inch outlet , provided the 4-inch leg of the fitting is upright and below — though not necessarily directly connected to — the water closet flange.
An offset closet flange .
Pair this with IPC 425.4 , which accepts a 4-inch by 3-inch closet bend and requires a 4-by-3 flange to receive the fixture horn where a 3-inch bend is used, and with IPC 1101.5 , which applies the same no-reduction rule to storm drainage.
Prohibited fitting patterns
IPC 706.3 carries one limitation stated in the body text rather than in a table:
Double sanitary tee patterns shall not receive the discharge of back-to-back water closets and fixtures or appliances with pumping action discharge .
Exception: back-to-back water closet connections to double sanitary tees are permitted where the horizontal developed length between the outlet of the water closet and the connection to the double sanitary tee pattern is 18 inches or greater .
The 18-inch exception exists because the developed length lets the discharge lose enough velocity that one closet's flush cannot blow across the fitting and siphon the opposing closet's trap.
A transition audit on a remodel
An older house has a 2-inch galvanized steel lavatory waste tied into a 3-inch cast-iron stack. The remodel adds a 2-inch PVC branch.
- Connection Correct method Section
- Existing galvanized to cast-iron hub Caulked or threaded adapter fitting 705.16.3
New PVC to cast iron Approved adapter fitting — in practice a shielded mechanical coupling to ASTM C1277 or C1540 705.16.4, 705.3.3
New PVC to the existing galvanized stub Approved adapter fitting ; if copper were involved instead, a brass converter or dielectric fitting would be required 705.16.4, 705.16.2
- Tapping the existing 3-inch stack with a saddle Prohibited 707.1 item 6
- Threaded black-iron tee reused on the galvanized branch Prohibited unless recessed drainage pattern 706.2