8.3 Fittings for Change of Direction and Drainage Flow Patterns
Colorado Journeyworker Plumber Journeyman Plumber
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Passing the Colorado Journeyworker Plumber Exam
1.1 Exam Blueprint, Format, and the 2024 Code Changeover 1.2 Colorado Licenses, Experience Hours, and Apprentice Supervision 1.3 Permits, Inspections, Blue Tags, and Board Enforcement
2 Chapter 2: General Regulations (IPC Chapter 3)
2.1 Approved Materials, Certification, and General Installation Rules 2.2 Protection of Pipes: Contact, Notching, Shield Plates, and Freezing 2.3 Piping Support, Trenching, Bedding, and Backfill 2.4 Required Tests: Water, Air, and Backflow Assembly Testing
3 Chapter 3: Fixtures and Equipment (IPC Chapter 4)
3.1 Minimum Fixture Counts, Separate Facilities, and Toilet Room Location 3.2 Fixture Clearances, Compartments, and Setting Requirements 3.3 Water Closets, Urinals, Lavatories, Sinks, and Flush Devices 3.4 Showers, Bathtubs, Fixture Fittings, and Scald Protection
4 Chapter 4: Water Heaters (IPC Chapter 5)
4.1 Water Heater Installation, Location, Access, and Clearances 4.2 Relief Valves and Discharge Piping 4.3 Water Heater Pans, Pan Drains, and Storage Tank Requirements 4.4 Thermal Expansion Control and Hot Water Temperature Limits
5 Chapter 5: Water Supply Materials and Installation (IPC Chapter 6)
5.1 Water Service and Distribution Materials, and Sewer Separation 5.2 Joints, Connections, and Dissimilar Materials in Water Piping 5.3 Valves, Shutoffs, and Required Valve Locations
6 Chapter 6: Water Supply Sizing and Pressure (IPC Chapter 6 and Appendix E)
6.1 Pressure Limits, Pressure Reducing Valves, and Water Hammer 6.2 Water Supply Fixture Units and Estimating Demand 6.3 Sizing Water Piping with Appendix E and Table E104.1
7 Chapter 7: Cross-Connection Control and Backflow Prevention (IPC Sections 608-610, Chapter 13)
7.1 Cross-Connection Principles, Backsiphonage, and Backpressure 7.2 Air Gaps and the Backflow Preventer Family 7.3 Applying Backflow Protection to Specific Connections 7.4 Nonpotable Water Systems, Identification, and Reclaimed Water
8 Chapter 8: Sanitary Drainage Materials and Fittings (IPC Chapter 7)
8.1 Sanitary Drainage Materials and Where Each May Be Used 8.2 Drainage Joints, Transitions, and Prohibited Connections 8.3 Fittings for Change of Direction and Drainage Flow Patterns
9 Chapter 9: Sanitary Drainage Sizing (IPC Sections 704, 709-711)
9.1 Drainage Fixture Units and Load Estimation 9.2 Slope of Horizontal Drainage and Installation Rules 9.3 Sizing Building Drains, Building Sewers, and Horizontal Branches 9.4 Stacks, Branch Intervals, and Offsets in Tall Buildings
10 Chapter 10: Cleanouts, Sumps and Below-Sewer Drainage (IPC Sections 708, 712-716)
10.1 Cleanouts, Manholes, and Access Requirements 10.2 Backwater Valves and Fixtures Below the Sewer Level 10.3 Sumps, Sewage Ejectors, and Macerating Toilet Systems 10.4 Building Sewers, Private Disposal, and Special Drainage Conditions
11 Chapter 11: Vent Fundamentals and Terminals (IPC Sections 901-905, 908)
11.1 How Vents Work, Trap Seal Loss, and the One-Inch Rule 11.2 Vent Terminals, Roof Penetrations, and Sidewall Terminations 11.3 Vent Connections, Grade, and the Six-Inch Rules
12 Chapter 12: Vent Types and Sizing (IPC Sections 906-911, 917)
12.1 Individual Vents, Common Vents, and Vents for Stack Offsets 12.2 Trap-to-Vent Distance, Trap Arms, and Fixture Drains 12.3 Sizing Stack Vents, Vent Stacks, Branch Vents, and Headers 12.4 Putting a Vent System Together: A Worked Building
13 Chapter 13: Engineered and Special Venting (IPC Sections 912-916, 918-920)
13.1 Horizontal and Vertical Wet Venting 13.2 Waste Stack Vents, Circuit Vents, and Combination Waste and Vent 13.3 Island Fixture Venting and Air Admittance Valves
14 Chapter 14: Traps, Interceptors and Separators (IPC Chapter 10)
14.1 Fixture Traps, Trap Seals, and Prohibited Trap Types 14.2 Trap Seal Protection, Primers, and Barrier Devices 14.3 Grease Interceptors, Oil Separators, and Solids Interceptors
15 Chapter 15: Indirect and Special Waste (IPC Chapter 8)
15.1 Where Indirect Waste Is Required, and Air Gap Versus Air Break 15.2 Waste Receptors, Hub Drains, and Standpipes 15.3 Special Wastes, Chemical Neutralization, and Health Care Drainage
16 Chapter 16: Storm Drainage (IPC Chapter 11 and Appendix B)
16.1 Storm Drainage Scope, Disposal, and Prohibited Connections 16.2 Storm Drainage Materials, Roof Drains, and Conductors 16.3 Secondary Roof Drains, Scuppers, and Controlled Flow Systems 16.4 Rainfall Rates, Roof Area, and the Flow-Rate Conversion 16.5 Sizing Vertical Conductors, Leaders, and Storm Drains 16.6 Gutters, Subsoil Drains, Building Subdrains, and Storm Sumps
17 Chapter 17: Residential Fire Sprinklers (IRC Section P2904)
17.1 Residential Fire Sprinkler Systems (IRC Section P2904)
18 Chapter 18: Isometric Analysis and Plumbing Calculations
18.1 Reading Plumbing Isometrics and Riser Diagrams 18.2 Analyzing a DWV Isometric for Code Compliance 18.3 Offsets, Travel, and the Plumbing Math the Exam Assumes
8.3 Fittings for Change of Direction and Drainage Flow Patterns
Key Takeaways Explain This Topic AI
IPC Table 706.3 permits sanitary tees only for horizontal-to-vertical changes of direction, never vertical to horizontal or horizontal to horizontal.
IPC Table 706.3 permits long sweeps, wyes, combination wye and eighth bends, sixteenth bends, eighth bends and sixth bends in all three change-of-direction patterns.
IPC Table 706.3 footnote a restricts quarter bends and short sweeps in vertical-to-horizontal and horizontal-to-horizontal applications to 2-inch or smaller fixture drains.
IPC Table 706.3 footnote b permits short sweeps vertical to horizontal where they are 3 inches or larger.
IPC 706.4 prohibits heel-inlet quarter bends where the quarter bend serves a water closet, and prohibits a low-heel inlet as a wet-vented connection.
Last updated: September 2026
The question Table 706.3 answers
Drainage flows by gravity, and the enemy is hydraulic jump — the sudden deceleration where falling water turns horizontal. A fitting that turns flow too abruptly produces a standing wave that fills the pipe bore, collapses the air core above the flow, and pulls a vacuum on nearby trap seals.
Table 706.3 therefore governs, for each fitting, which of three patterns it may create:
Horizontal to vertical — a branch dropping into a stack. The gentlest case, because gravity is already pulling the flow the way it is going.
Vertical to horizontal — the base of a stack, or a fixture drain turning out of a wall. The most demanding case.
Horizontal to horizontal — an offset in a horizontal run.
Table 706.3 — Fittings for change in direction
- Fitting pattern Horizontal to vertical Vertical to horizontal Horizontal to horizontal
- Sixteenth bend X X X
- Eighth bend X X X
- Sixth bend X X X
- Quarter bend X X (a) X (a)
- Short sweep X X (a, b) X (a)
- Long sweep X X X
- Sanitary tee X (c) — —
- Wye X X X
- Combination wye and eighth bend X X X
Footnotes:
a. The fittings shall only be permitted for a 2-inch or smaller fixture drain .
b. Three inches or larger.
c. For a limitation on double sanitary tees, see Section 706.3 (the back-to-back water closet rule).
Colorado field note (not exam-scored): Board Rule 1.2(E)(1)(ll) deletes footnotes a and b from Table 706.3, and Rule 1.2(E)(1)(kk) adds that fixture crosses are not required to meet the exception of IPC 706.3.
Reading the table correctly
The sanitary tee is the fitting to watch. It has exactly one X, in the horizontal-to-vertical column, with a footnote. A sanitary tee laid on its back to turn a stack into a building drain is a defect, because its short-radius throat produces a violent hydraulic jump precisely where the vertical flow is fastest. A long sweep or a combination wye and eighth bend belongs at the base of a stack.
Quarter bends and short sweeps are conditional. Both are permitted horizontal to vertical without restriction. Turning vertical to horizontal or horizontal to horizontal , both are limited to a 2-inch or smaller fixture drain — and a short sweep gets an additional path through footnote b at 3 inches or larger .
Wyes and combination wye and eighth bends are unconditional , which is why they are the workhorse fittings of any well-built DWV system.
Long sweeps are unconditional too , and short sweeps are not. The difference is centerline radius: a long-sweep quarter bend has a radius roughly equal to its diameter or more, a short sweep considerably less.
The base of a stack and horizontal branches — IPC 704.3
Horizontal branches shall connect to the bases of stacks at a point located not less than 10 times the diameter of the drainage stack downstream from the stack. Horizontal branches shall connect to horizontal stack offsets at a point located not less than 10 times the diameter of the drainage stack downstream from the upper stack.
Water reaching the base of a stack has reached terminal velocity and fills a large fraction of the pipe bore for some distance downstream. A branch tied in inside that zone is subject to backflow and to severe pressure fluctuation.
Worked example
A 4-inch soil stack lands on a horizontal building drain. How far downstream may a lavatory branch connect?
10 x 4 inches = 40 inches , so not less than 40 inches (3 feet 4 inches) downstream from the base of the stack.
For a 6-inch stack, the distance becomes 10 x 6 = 60 inches (5 feet) .
Compare the parallel rule for sump discharge in IPC 712.3.5 : a pump discharge connecting into horizontal drainage piping must be made through a wye fitting into the top of the piping, located not less than 10 pipe diameters from the base of any soil stack, waste stack or fixture drain .
Heel- and side-inlet quarter bends — IPC 706.4
Arrangement Permitted?
- Heel-inlet quarter bend, general drainage Acceptable
- Heel-inlet quarter bend serving a water closet Not permitted
- Low-heel inlet as a wet-vented connection Not permitted
- Side-inlet quarter bend for drainage, wet venting and stack venting Acceptable
The distinction is where the inlet sits relative to the flow line. A low heel inlet enters near the bottom of the bend, where it can be flooded by the main flow; a side inlet enters at the springline, above the flow.
Fitting selection in practice
A three-story building's 3-inch waste stack must land on a 4-inch building drain, and a 2-inch lavatory branch must turn from horizontal in a wall to vertical, then back to horizontal beneath a slab.
Location Correct fitting Why
Base of the stack, vertical to horizontal Long sweep quarter bend or combination wye and eighth bend Unconditional in the vertical-to-horizontal column
Lavatory arm, horizontal to vertical Sanitary tee Permitted horizontal to vertical
Below slab, vertical to horizontal on a 2-inch fixture drain Quarter bend permitted under footnote a (2-inch or smaller fixture drain) 2-inch fixture drain
Horizontal offset in the 4-inch building drain Two eighth bends or a wye and eighth bend Unconditional horizontal to horizontal; quarter bends are limited to 2-inch fixture drains here
Lavatory branch tie-in to the building drain Not less than 40 inches downstream of the 4-inch stack base 704.3, 10 pipe diameters
Cleanout at the horizontal offset Required if the change of horizontal direction exceeds 45 degrees 708.1.4
Two further Chapter 3 rules apply to that offset: IPC 308.6 requires rigid bracing where horizontal drainage 4 inches and larger changes direction more than 45 degrees (except into a vertical pipe), and IPC 308.7.1 requires restraints at all direction changes for pipe larger than 4 inches.