9.3 Sizing Building Drains, Building Sewers, and Horizontal Branches
Colorado Journeyworker Plumber Journeyman Plumber
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Passing the Colorado Journeyworker Plumber Exam
1.1 Exam Blueprint, Format, and the 2024 Code Changeover 1.2 Colorado Licenses, Experience Hours, and Apprentice Supervision 1.3 Permits, Inspections, Blue Tags, and Board Enforcement
2 Chapter 2: General Regulations (IPC Chapter 3)
2.1 Approved Materials, Certification, and General Installation Rules 2.2 Protection of Pipes: Contact, Notching, Shield Plates, and Freezing 2.3 Piping Support, Trenching, Bedding, and Backfill 2.4 Required Tests: Water, Air, and Backflow Assembly Testing
3 Chapter 3: Fixtures and Equipment (IPC Chapter 4)
3.1 Minimum Fixture Counts, Separate Facilities, and Toilet Room Location 3.2 Fixture Clearances, Compartments, and Setting Requirements 3.3 Water Closets, Urinals, Lavatories, Sinks, and Flush Devices 3.4 Showers, Bathtubs, Fixture Fittings, and Scald Protection
4 Chapter 4: Water Heaters (IPC Chapter 5)
4.1 Water Heater Installation, Location, Access, and Clearances 4.2 Relief Valves and Discharge Piping 4.3 Water Heater Pans, Pan Drains, and Storage Tank Requirements 4.4 Thermal Expansion Control and Hot Water Temperature Limits
5 Chapter 5: Water Supply Materials and Installation (IPC Chapter 6)
5.1 Water Service and Distribution Materials, and Sewer Separation 5.2 Joints, Connections, and Dissimilar Materials in Water Piping 5.3 Valves, Shutoffs, and Required Valve Locations
6 Chapter 6: Water Supply Sizing and Pressure (IPC Chapter 6 and Appendix E)
6.1 Pressure Limits, Pressure Reducing Valves, and Water Hammer 6.2 Water Supply Fixture Units and Estimating Demand 6.3 Sizing Water Piping with Appendix E and Table E104.1
7 Chapter 7: Cross-Connection Control and Backflow Prevention (IPC Sections 608-610, Chapter 13)
7.1 Cross-Connection Principles, Backsiphonage, and Backpressure 7.2 Air Gaps and the Backflow Preventer Family 7.3 Applying Backflow Protection to Specific Connections 7.4 Nonpotable Water Systems, Identification, and Reclaimed Water
8 Chapter 8: Sanitary Drainage Materials and Fittings (IPC Chapter 7)
8.1 Sanitary Drainage Materials and Where Each May Be Used 8.2 Drainage Joints, Transitions, and Prohibited Connections 8.3 Fittings for Change of Direction and Drainage Flow Patterns
9 Chapter 9: Sanitary Drainage Sizing (IPC Sections 704, 709-711)
9.1 Drainage Fixture Units and Load Estimation 9.2 Slope of Horizontal Drainage and Installation Rules 9.3 Sizing Building Drains, Building Sewers, and Horizontal Branches 9.4 Stacks, Branch Intervals, and Offsets in Tall Buildings
10 Chapter 10: Cleanouts, Sumps and Below-Sewer Drainage (IPC Sections 708, 712-716)
10.1 Cleanouts, Manholes, and Access Requirements 10.2 Backwater Valves and Fixtures Below the Sewer Level 10.3 Sumps, Sewage Ejectors, and Macerating Toilet Systems 10.4 Building Sewers, Private Disposal, and Special Drainage Conditions
11 Chapter 11: Vent Fundamentals and Terminals (IPC Sections 901-905, 908)
11.1 How Vents Work, Trap Seal Loss, and the One-Inch Rule 11.2 Vent Terminals, Roof Penetrations, and Sidewall Terminations 11.3 Vent Connections, Grade, and the Six-Inch Rules
12 Chapter 12: Vent Types and Sizing (IPC Sections 906-911, 917)
12.1 Individual Vents, Common Vents, and Vents for Stack Offsets 12.2 Trap-to-Vent Distance, Trap Arms, and Fixture Drains 12.3 Sizing Stack Vents, Vent Stacks, Branch Vents, and Headers 12.4 Putting a Vent System Together: A Worked Building
13 Chapter 13: Engineered and Special Venting (IPC Sections 912-916, 918-920)
13.1 Horizontal and Vertical Wet Venting 13.2 Waste Stack Vents, Circuit Vents, and Combination Waste and Vent 13.3 Island Fixture Venting and Air Admittance Valves
14 Chapter 14: Traps, Interceptors and Separators (IPC Chapter 10)
14.1 Fixture Traps, Trap Seals, and Prohibited Trap Types 14.2 Trap Seal Protection, Primers, and Barrier Devices 14.3 Grease Interceptors, Oil Separators, and Solids Interceptors
15 Chapter 15: Indirect and Special Waste (IPC Chapter 8)
15.1 Where Indirect Waste Is Required, and Air Gap Versus Air Break 15.2 Waste Receptors, Hub Drains, and Standpipes 15.3 Special Wastes, Chemical Neutralization, and Health Care Drainage
16 Chapter 16: Storm Drainage (IPC Chapter 11 and Appendix B)
16.1 Storm Drainage Scope, Disposal, and Prohibited Connections 16.2 Storm Drainage Materials, Roof Drains, and Conductors 16.3 Secondary Roof Drains, Scuppers, and Controlled Flow Systems 16.4 Rainfall Rates, Roof Area, and the Flow-Rate Conversion 16.5 Sizing Vertical Conductors, Leaders, and Storm Drains 16.6 Gutters, Subsoil Drains, Building Subdrains, and Storm Sumps
17 Chapter 17: Residential Fire Sprinklers (IRC Section P2904)
17.1 Residential Fire Sprinkler Systems (IRC Section P2904)
18 Chapter 18: Isometric Analysis and Plumbing Calculations
18.1 Reading Plumbing Isometrics and Riser Diagrams 18.2 Analyzing a DWV Isometric for Code Compliance 18.3 Offsets, Travel, and the Plumbing Math the Exam Assumes
9.3 Sizing Building Drains, Building Sewers, and Horizontal Branches
Key Takeaways Explain This Topic AI
IPC Table 710.1(1) sizes building sewers, building drains and branches of the building drain; Table 710.1(2) sizes horizontal fixture branches and vertical stacks.
IPC Table 710.1(1) footnote a requires the minimum size of any building drain serving a water closet to be 3 inches.
IPC Table 710.1(1) allows a 4-inch building drain 180 dfu at 1/8 inch per foot, 216 dfu at 1/4 inch per foot and 250 dfu at 1/2 inch per foot.
IPC Table 710.1(1) allows a 3-inch building drain 36 dfu at 1/8 inch per foot and 42 dfu at 1/4 inch per foot.
IPC Table 710.1(2) limits a 3-inch horizontal fixture branch to 20 dfu and a 4-inch horizontal branch to 160 dfu.
Last updated: September 2026
Two tables, two jobs
This is where candidates lose points. IPC 710.1 assigns each table a specific class of pipe:
Use this table For this pipe
Table 710.1(1) Building Drains and Sewers Building sewer , building drain , and horizontal branches of the building drain
Table 710.1(2) Horizontal Fixture Branches and Stacks Horizontal fixture branches and vertical soil or waste stacks
The phrase " branch of the building drain " means a horizontal branch that connects to the building drain itself — below the lowest floor, typically under the slab. A " horizontal fixture branch " is a horizontal drain above that, receiving fixtures and carrying them to a stack.
Table 710.1(1) is organized by slope because the pipe runs horizontally its entire length. Table 710.1(2) has no slope column for stacks because a stack is vertical.
Table 710.1(1) — building drains and sewers
Maximum dfu connected to any portion of the building drain or building sewer, including branches of the building drain:
- Pipe size 1/16 in/ft 1/8 in/ft 1/4 in/ft 1/2 in/ft
- 1-1/4 — — 1 1
- 1-1/2 — — 3 3
- 2 — — 21 26
- 2-1/2 — — 24 31
- 3 — 36 42 50
- 4 — 180 216 250
- 5 — 390 480 575
- 6 — 700 840 1,000
- 8 1,400 1,600 1,920 2,300
- 10 2,500 2,900 3,500 4,200
- 12 3,900 4,600 5,600 6,700
- 15 7,000 8,300 10,000 12,000
Footnote a: the minimum size of any building drain serving a water closet shall be 3 inches. That floor overrides the dfu math. A single private water closet is 3 dfu, which a 2-inch line would carry numerically — but a water closet needs 3 inches.
Notice the enormous jump from 3 inches to 4 inches: 42 dfu to 216 dfu at 1/4 inch per foot , more than a fivefold increase for a one-size step. Flow capacity in a partially full gravity pipe scales roughly with diameter to the 8/3 power, which is why the 3-to-4 step is so dramatic and why dropping a 4-inch drain to 3 inches to clear an obstruction is almost never workable.
Notice also the blank cells. The 1/16 inch per foot column is empty below 8 inches because Table 704.1 does not allow that slope on smaller pipe.
Table 710.1(2) — horizontal fixture branches and stacks
Pipe size Horizontal branch total Stack: discharge into one branch interval Stack of 3 branch intervals or less Stack greater than 3 branch intervals
- 1-1/2 3 2 4 8
- 2 6 6 10 24
- 2-1/2 12 9 20 42
- 3 20 20 48 72
- 4 160 90 240 500
- 5 360 200 540 1,100
- 6 620 350 960 1,900
- 8 1,400 600 2,200 3,600
- 10 2,500 1,000 3,800 5,600
- 12 3,900 1,500 6,000 8,400
Footnote a: the table does not include branches of the building drain — refer to Table 710.1(1).
Compare a 3-inch pipe across the two tables: 20 dfu as a horizontal fixture branch, but 36 to 50 dfu as a building drain depending on slope. The horizontal branch value is lower because a branch discharges into a stack, where surging matters, while a building drain runs to open sewer.
Worked sizing: a 24-unit apartment building
Each of 24 units has one bathroom group (1.6 gpf water closet), one kitchen sink and one residential clothes washer. There is also a common laundry with two commercial clothes washers and one service sink, and three floor drains in the mechanical room.
Step 1 — total dfu:
- Fixture dfu each Count Subtotal
- Bathroom group, 1.6 gpf 5 24 120
- Kitchen sink, domestic 2 24 48
- Clothes washer, residential 2 24 48
- Clothes washer, commercial 3 2 6
- Service sink 2 1 2
- Floor drain 2 3 6
- Total 230 dfu
Step 2 — building drain. Enter Table 710.1(1) at 230 dfu:
At 1/8 inch per foot : 4-inch carries 180 (too small); 5-inch carries 390 — sufficient.
At 1/4 inch per foot : 4-inch carries 216 — still too small; 5-inch carries 480 — sufficient.
At 1/2 inch per foot : 4-inch carries 250 — sufficient, if that slope is achievable.
So a 5-inch building drain at 1/8 or 1/4 inch per foot , or a 4-inch drain at 1/2 inch per foot if the site has the fall. In practice the 5-inch at 1/4 inch per foot is the ordinary answer; 1/2 inch per foot over a long run demands a great deal of depth.
Step 3 — check the water closet floor. Footnote a requires at least 3 inches for any building drain serving a water closet. Satisfied.
Step 4 — the stack. If the building has three stacks each serving 8 units, each stack carries roughly (8 x 5) + (8 x 2) + (8 x 2) = 72 dfu and spans four stories, which is more than three branch intervals. From Table 710.1(2), "stack greater than 3 branch intervals": a 3-inch stack carries 72 dfu — exactly at the limit — and a 4-inch stack carries 500 . Because there is no margin at 3 inches and every added fixture would bust it, 4 inches is the sound choice.
Step 5 — horizontal branches. A branch serving two bathroom groups plus two kitchen sinks is (2 x 5) + (2 x 2) = 14 dfu . Table 710.1(2) horizontal branch column: 2-1/2 inch carries 12 (too small), 3-inch carries 20 — a 3-inch branch works, and it also satisfies the requirement that a branch serving a water closet be at least 3 inches.
Offsets
IPC 710.1.1 Horizontal stack offsets : sized as required for building drains per Table 710.1(1), except as required by 711.3.
IPC 710.1.2 Vertical stack offsets : sized as required for straight stacks per Table 710.1(2), except where required to be sized as a building drain per 711.1.1.
The logic is physical: a horizontal offset behaves like a building drain — flow decelerates and runs partially full along a slope. A vertical offset is still a stack.
Section 711 adds special rules for buildings of five stories or more , covered in the next section of this guide.