16.6 Gutters, Subsoil Drains, Building Subdrains, and Storm Sumps

Colorado Journeyworker Plumber Journeyman Plumber

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Passing the Colorado Journeyworker Plumber Exam

1.1 Exam Blueprint, Format, and the 2024 Code Changeover 1.2 Colorado Licenses, Experience Hours, and Apprentice Supervision 1.3 Permits, Inspections, Blue Tags, and Board Enforcement

2 Chapter 2: General Regulations (IPC Chapter 3)

2.1 Approved Materials, Certification, and General Installation Rules 2.2 Protection of Pipes: Contact, Notching, Shield Plates, and Freezing 2.3 Piping Support, Trenching, Bedding, and Backfill 2.4 Required Tests: Water, Air, and Backflow Assembly Testing

3 Chapter 3: Fixtures and Equipment (IPC Chapter 4)

3.1 Minimum Fixture Counts, Separate Facilities, and Toilet Room Location 3.2 Fixture Clearances, Compartments, and Setting Requirements 3.3 Water Closets, Urinals, Lavatories, Sinks, and Flush Devices 3.4 Showers, Bathtubs, Fixture Fittings, and Scald Protection

4 Chapter 4: Water Heaters (IPC Chapter 5)

4.1 Water Heater Installation, Location, Access, and Clearances 4.2 Relief Valves and Discharge Piping 4.3 Water Heater Pans, Pan Drains, and Storage Tank Requirements 4.4 Thermal Expansion Control and Hot Water Temperature Limits

5 Chapter 5: Water Supply Materials and Installation (IPC Chapter 6)

5.1 Water Service and Distribution Materials, and Sewer Separation 5.2 Joints, Connections, and Dissimilar Materials in Water Piping 5.3 Valves, Shutoffs, and Required Valve Locations

6 Chapter 6: Water Supply Sizing and Pressure (IPC Chapter 6 and Appendix E)

6.1 Pressure Limits, Pressure Reducing Valves, and Water Hammer 6.2 Water Supply Fixture Units and Estimating Demand 6.3 Sizing Water Piping with Appendix E and Table E104.1

7 Chapter 7: Cross-Connection Control and Backflow Prevention (IPC Sections 608-610, Chapter 13)

7.1 Cross-Connection Principles, Backsiphonage, and Backpressure 7.2 Air Gaps and the Backflow Preventer Family 7.3 Applying Backflow Protection to Specific Connections 7.4 Nonpotable Water Systems, Identification, and Reclaimed Water

8 Chapter 8: Sanitary Drainage Materials and Fittings (IPC Chapter 7)

8.1 Sanitary Drainage Materials and Where Each May Be Used 8.2 Drainage Joints, Transitions, and Prohibited Connections 8.3 Fittings for Change of Direction and Drainage Flow Patterns

9 Chapter 9: Sanitary Drainage Sizing (IPC Sections 704, 709-711)

9.1 Drainage Fixture Units and Load Estimation 9.2 Slope of Horizontal Drainage and Installation Rules 9.3 Sizing Building Drains, Building Sewers, and Horizontal Branches 9.4 Stacks, Branch Intervals, and Offsets in Tall Buildings

10 Chapter 10: Cleanouts, Sumps and Below-Sewer Drainage (IPC Sections 708, 712-716)

10.1 Cleanouts, Manholes, and Access Requirements 10.2 Backwater Valves and Fixtures Below the Sewer Level 10.3 Sumps, Sewage Ejectors, and Macerating Toilet Systems 10.4 Building Sewers, Private Disposal, and Special Drainage Conditions

11 Chapter 11: Vent Fundamentals and Terminals (IPC Sections 901-905, 908)

11.1 How Vents Work, Trap Seal Loss, and the One-Inch Rule 11.2 Vent Terminals, Roof Penetrations, and Sidewall Terminations 11.3 Vent Connections, Grade, and the Six-Inch Rules

12 Chapter 12: Vent Types and Sizing (IPC Sections 906-911, 917)

12.1 Individual Vents, Common Vents, and Vents for Stack Offsets 12.2 Trap-to-Vent Distance, Trap Arms, and Fixture Drains 12.3 Sizing Stack Vents, Vent Stacks, Branch Vents, and Headers 12.4 Putting a Vent System Together: A Worked Building

13 Chapter 13: Engineered and Special Venting (IPC Sections 912-916, 918-920)

13.1 Horizontal and Vertical Wet Venting 13.2 Waste Stack Vents, Circuit Vents, and Combination Waste and Vent 13.3 Island Fixture Venting and Air Admittance Valves

14 Chapter 14: Traps, Interceptors and Separators (IPC Chapter 10)

14.1 Fixture Traps, Trap Seals, and Prohibited Trap Types 14.2 Trap Seal Protection, Primers, and Barrier Devices 14.3 Grease Interceptors, Oil Separators, and Solids Interceptors

15 Chapter 15: Indirect and Special Waste (IPC Chapter 8)

15.1 Where Indirect Waste Is Required, and Air Gap Versus Air Break 15.2 Waste Receptors, Hub Drains, and Standpipes 15.3 Special Wastes, Chemical Neutralization, and Health Care Drainage

16 Chapter 16: Storm Drainage (IPC Chapter 11 and Appendix B)

16.1 Storm Drainage Scope, Disposal, and Prohibited Connections 16.2 Storm Drainage Materials, Roof Drains, and Conductors 16.3 Secondary Roof Drains, Scuppers, and Controlled Flow Systems 16.4 Rainfall Rates, Roof Area, and the Flow-Rate Conversion 16.5 Sizing Vertical Conductors, Leaders, and Storm Drains 16.6 Gutters, Subsoil Drains, Building Subdrains, and Storm Sumps

17 Chapter 17: Residential Fire Sprinklers (IRC Section P2904)

17.1 Residential Fire Sprinkler Systems (IRC Section P2904)

18 Chapter 18: Isometric Analysis and Plumbing Calculations

18.1 Reading Plumbing Isometrics and Riser Diagrams 18.2 Analyzing a DWV Isometric for Code Compliance 18.3 Offsets, Travel, and the Plumbing Math the Exam Assumes

16.6 Gutters, Subsoil Drains, Building Subdrains, and Storm Sumps

Key Takeaways Explain This Topic AI

IPC Table 1106.6 sizes horizontal gutters by dimensions and slope, rating a 6-inch semicircular gutter at 110 gpm at 1/8 inch per foot and 157 gpm at 1/4 inch per foot.

IPC 1111.1 requires subsoil drains to be not less than 4 inches in diameter, protected by an accessibly located backwater valve where subject to backwater.

IPC 1111.1 states the subsoil sump shall not be required to have either a gastight cover or a vent, unlike a sanitary sump.

IPC 1113.1.2 requires a storm sump pit not less than 18 inches in diameter and not less than 24 inches in depth, with access and a removable cover.

IPC 1113.1.4 requires storm sump discharge piping to include a gate valve and a full flow check valve, with an exception permitting only a check valve in one- and two-family dwellings.

Last updated: September 2026

Gutters — IPC 1106.6 and Table 1106.6

Horizontal gutters shall be sized based on the flow rate from the roof surface. The flow rate in horizontal gutters shall not exceed that specified in Table 1106.6.

Table 1106.6 is organized by gutter dimensions — width by depth for rectangular shapes, single dimensions being diameters of a semicircle — and by slope .

  • Gutter dimensions (in) Slope (in/ft) Capacity (gpm)
  • 1-1/2 x 2-1/2 1/4 26
  • 1-1/2 x 2-1/2 1/2 40
  • 4 (semicircular) 1/8 39
  • 2-1/4 x 3 1/4 55
  • 2-1/4 x 3 1/2 87
  • 5 (semicircular) 1/8 74
  • 4 x 2-1/2 1/4 106
  • 3 x 3-1/2 1/2 156
  • 6 (semicircular) 1/8 110
  • 3 x 5 1/4 157
  • 3 x 5 1/2 225
  • 8 (semicircular) 1/16 172
  • 8 (semicircular) 1/8 247
  • 4-1/2 x 6 1/4 348
  • 4-1/2 x 6 1/2 494
  • 10 (semicircular) 1/16 331
  • 10 (semicircular) 1/8 472
  • 5 x 8 1/4 651
  • 4 x 10-1/2 1/2 1,055

Footnote a: dimensions are width by depth for rectangular shapes; single dimensions are diameters of a semicircle.

Two useful readings:

Slope buys a great deal of gutter capacity. A 1-1/2 x 2-1/2 gutter carries 26 gpm at 1/4 inch per foot and 40 gpm at 1/2 — a 54 percent gain.

A "6-inch gutter" in the trade is a 6-inch semicircular gutter at 110 gpm at 1/8 inch per foot. That is the everyday residential size.

Worked gutter sizing

A 1,200 square foot roof section in Durango (R = 1.8) drains to one gutter run.

Q = 0.0104 x 1,200 x 1.8 = 22.5 gpm .

Table 1106.6: a 4-inch semicircular gutter at 1/8 inch per foot carries 39 gpm . Sufficient.

The leader from that gutter: Table 1106.3, 2-inch round = 30 gpm . Sufficient at 22.5 gpm.

Move it to Lamar (R = 3.0): Q = 0.0104 x 1,200 x 3.0 = 37.4 gpm . The 4-inch gutter at 39 gpm still works, barely; the 2-inch leader at 30 gpm does not — go to 2-1/2 inch (54 gpm) .

Subsoil drains — IPC 1111

Subsoil drains shall be open-jointed, horizontally split or perforated pipe conforming to one of the standards listed in Table 1102.5 . Such drains shall be not less than 4 inches in diameter . Where the building is subject to backwater, the subsoil drain shall be protected by an accessibly located backwater valve . Subsoil drains shall discharge to a trapped area drain, sump, dry well or approved location above ground . The subsoil sump shall not be required to have either a gastight cover or a vent. The sump and pumping system shall comply with Section 1113.1.

Five requirements worth separating:

Open-jointed, horizontally split or perforated — the pipe must admit ground water.

Not less than 4 inches in diameter.

Backwater valve , accessibly located, where subject to backwater.

Discharge to a trapped area drain, sump, dry well or approved above-ground location .

The subsoil sump needs neither a gastight cover nor a vent — a direct contrast with the sanitary sump of IPC 712.3.2, which requires both.

That contrast is a favorite exam item. A subsoil sump handles ground water , not sewage; there is no gas to contain.

1101.8 Exception : the storm cleanout requirement does not apply to a subsurface drainage system .

Building subdrains — IPC 1112

Building subdrains located below the public sewer level shall discharge into a sump or receiving tank , the contents of which shall be automatically lifted and discharged into the drainage system as required for building sumps. The sump and pumping equipment shall comply with Section 1113.1 .

Compare IPC 712.1 , the sanitary equivalent, which adds the restriction that in other than existing structures, the sump shall not receive drainage from any piping within the building capable of being discharged by gravity to the building sewer. The storm section does not repeat that sentence, but the same engineering logic applies: do not pump what gravity can carry.

Storm sumps and pumping systems — IPC 1113

1113.1 : the sump pump, pit and discharge piping shall conform to Sections 1113.1.1 through 1113.1.4.

  • Section Requirement
  • 1113.1.1 Pump capacity and head Of a capacity and head appropriate to anticipated use requirements

1113.1.2 Sump pit Not less than 18 inches in diameter and not less than 24 inches in depth , unless otherwise approved. Provided with access , located so all drainage flows into the pit by gravity . Constructed of tile, steel, plastic, cast iron, concrete or other approved material, with a removable cover adequate to support anticipated loads . The pit floor shall be solid and provide permanent support for the pump

1113.1.3 Electrical Electrical service outlets, where required, meet NFPA 70

1113.1.4 Piping Discharge piping meets 1102.2, 1102.3 or 1102.4 and shall include a gate valve and a full flow check valve . Pipe and fittings the same size as, or larger than, the pump discharge tapping . Exception: in one- and two-family dwellings, only a check valve shall be required , located on the discharge piping from the pump or ejector

Sanitary sump versus storm sump

  • Feature Sanitary (712.3.2, 712.2) Storm (1113.1.2, 1113.1.4)
  • Pit diameter 18 inches minimum 18 inches minimum
  • Pit depth 24 inches minimum 24 inches minimum

Cover Gastight, removable , not more than 2 inches below grade or floor level Removable , adequate to support loads; not required to be gastight for subsoil sumps (1111.1)

Vent Required , per Chapter 9 Not required for a subsoil sump (1111.1)

Valves Check valve then a full open valve on the discharge side, with access Gate valve and a full flow check valve ; one- and two-family dwellings need only a check valve

Solids handling 2-inch spherical solids for water closet discharge; 1/2 inch otherwise Not specified — clear water

Capacity table Table 712.4.2 Not tabulated; "appropriate to anticipated use"

The pit dimensions are the same. Everything about gas containment and solids differs, because one carries sewage and the other carries rain and ground water.

Combined sanitary and storm public sewer — IPC 1109

Where the public sewer is a combined system for both sanitary and storm water, the storm sewer shall be connected independently to the public sewer.

The storm and sanitary systems remain separate inside and up to the public sewer, joining only at the public main. This mirrors IPC 703.6 on the sanitary side.

And recall 1103.1 : a storm system connected to a combined sewer must be trapped , either per conductor branch or with a single main trap just before the connection, with a cleanout on the building side of the trap (1103.4).

A residential storm package

A house in Grand Junction (R = 1.7) with a 1,800 square foot roof, gutters on two sides, and a perimeter foundation drain.

  • Item Result Basis
  • Flow per gutter run (900 sq ft each) 0.0104 x 900 x 1.7 = 15.9 gpm Equation 11-1
  • Gutter 4-inch semicircular at 1/8 in/ft = 39 gpm Table 1106.6
  • Leader 2-inch round = 30 gpm Table 1106.3

Discharge Permitted onto flat areas such as streets or lawns where approved, flowing away from the building 1101.2

  • Foundation drain Not less than 4 inches , perforated or open-jointed , Table 1102.5 material 1102.5, 1111.1
  • Foundation drain discharge Trapped area drain, sump, dry well or approved above-ground location 1111.1
  • Subsoil sump 18 inches diameter, 24 inches deep, no gastight cover, no vent 1111.1, 1113.1.2
  • Sump discharge valves Only a check valve required in a one- or two-family dwelling 1113.1.4 Exception
  • Backwater protection Accessibly located backwater valve if subject to backwater 1111.1

Loading diagram... Site storm drainage components