16.4 Rainfall Rates, Roof Area, and the Flow-Rate Conversion

Colorado Journeyworker Plumber Journeyman Plumber

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Passing the Colorado Journeyworker Plumber Exam

1.1 Exam Blueprint, Format, and the 2024 Code Changeover 1.2 Colorado Licenses, Experience Hours, and Apprentice Supervision 1.3 Permits, Inspections, Blue Tags, and Board Enforcement

2 Chapter 2: General Regulations (IPC Chapter 3)

2.1 Approved Materials, Certification, and General Installation Rules 2.2 Protection of Pipes: Contact, Notching, Shield Plates, and Freezing 2.3 Piping Support, Trenching, Bedding, and Backfill 2.4 Required Tests: Water, Air, and Backflow Assembly Testing

3 Chapter 3: Fixtures and Equipment (IPC Chapter 4)

3.1 Minimum Fixture Counts, Separate Facilities, and Toilet Room Location 3.2 Fixture Clearances, Compartments, and Setting Requirements 3.3 Water Closets, Urinals, Lavatories, Sinks, and Flush Devices 3.4 Showers, Bathtubs, Fixture Fittings, and Scald Protection

4 Chapter 4: Water Heaters (IPC Chapter 5)

4.1 Water Heater Installation, Location, Access, and Clearances 4.2 Relief Valves and Discharge Piping 4.3 Water Heater Pans, Pan Drains, and Storage Tank Requirements 4.4 Thermal Expansion Control and Hot Water Temperature Limits

5 Chapter 5: Water Supply Materials and Installation (IPC Chapter 6)

5.1 Water Service and Distribution Materials, and Sewer Separation 5.2 Joints, Connections, and Dissimilar Materials in Water Piping 5.3 Valves, Shutoffs, and Required Valve Locations

6 Chapter 6: Water Supply Sizing and Pressure (IPC Chapter 6 and Appendix E)

6.1 Pressure Limits, Pressure Reducing Valves, and Water Hammer 6.2 Water Supply Fixture Units and Estimating Demand 6.3 Sizing Water Piping with Appendix E and Table E104.1

7 Chapter 7: Cross-Connection Control and Backflow Prevention (IPC Sections 608-610, Chapter 13)

7.1 Cross-Connection Principles, Backsiphonage, and Backpressure 7.2 Air Gaps and the Backflow Preventer Family 7.3 Applying Backflow Protection to Specific Connections 7.4 Nonpotable Water Systems, Identification, and Reclaimed Water

8 Chapter 8: Sanitary Drainage Materials and Fittings (IPC Chapter 7)

8.1 Sanitary Drainage Materials and Where Each May Be Used 8.2 Drainage Joints, Transitions, and Prohibited Connections 8.3 Fittings for Change of Direction and Drainage Flow Patterns

9 Chapter 9: Sanitary Drainage Sizing (IPC Sections 704, 709-711)

9.1 Drainage Fixture Units and Load Estimation 9.2 Slope of Horizontal Drainage and Installation Rules 9.3 Sizing Building Drains, Building Sewers, and Horizontal Branches 9.4 Stacks, Branch Intervals, and Offsets in Tall Buildings

10 Chapter 10: Cleanouts, Sumps and Below-Sewer Drainage (IPC Sections 708, 712-716)

10.1 Cleanouts, Manholes, and Access Requirements 10.2 Backwater Valves and Fixtures Below the Sewer Level 10.3 Sumps, Sewage Ejectors, and Macerating Toilet Systems 10.4 Building Sewers, Private Disposal, and Special Drainage Conditions

11 Chapter 11: Vent Fundamentals and Terminals (IPC Sections 901-905, 908)

11.1 How Vents Work, Trap Seal Loss, and the One-Inch Rule 11.2 Vent Terminals, Roof Penetrations, and Sidewall Terminations 11.3 Vent Connections, Grade, and the Six-Inch Rules

12 Chapter 12: Vent Types and Sizing (IPC Sections 906-911, 917)

12.1 Individual Vents, Common Vents, and Vents for Stack Offsets 12.2 Trap-to-Vent Distance, Trap Arms, and Fixture Drains 12.3 Sizing Stack Vents, Vent Stacks, Branch Vents, and Headers 12.4 Putting a Vent System Together: A Worked Building

13 Chapter 13: Engineered and Special Venting (IPC Sections 912-916, 918-920)

13.1 Horizontal and Vertical Wet Venting 13.2 Waste Stack Vents, Circuit Vents, and Combination Waste and Vent 13.3 Island Fixture Venting and Air Admittance Valves

14 Chapter 14: Traps, Interceptors and Separators (IPC Chapter 10)

14.1 Fixture Traps, Trap Seals, and Prohibited Trap Types 14.2 Trap Seal Protection, Primers, and Barrier Devices 14.3 Grease Interceptors, Oil Separators, and Solids Interceptors

15 Chapter 15: Indirect and Special Waste (IPC Chapter 8)

15.1 Where Indirect Waste Is Required, and Air Gap Versus Air Break 15.2 Waste Receptors, Hub Drains, and Standpipes 15.3 Special Wastes, Chemical Neutralization, and Health Care Drainage

16 Chapter 16: Storm Drainage (IPC Chapter 11 and Appendix B)

16.1 Storm Drainage Scope, Disposal, and Prohibited Connections 16.2 Storm Drainage Materials, Roof Drains, and Conductors 16.3 Secondary Roof Drains, Scuppers, and Controlled Flow Systems 16.4 Rainfall Rates, Roof Area, and the Flow-Rate Conversion 16.5 Sizing Vertical Conductors, Leaders, and Storm Drains 16.6 Gutters, Subsoil Drains, Building Subdrains, and Storm Sumps

17 Chapter 17: Residential Fire Sprinklers (IRC Section P2904)

17.1 Residential Fire Sprinkler Systems (IRC Section P2904)

18 Chapter 18: Isometric Analysis and Plumbing Calculations

18.1 Reading Plumbing Isometrics and Riser Diagrams 18.2 Analyzing a DWV Isometric for Code Compliance 18.3 Offsets, Travel, and the Plumbing Math the Exam Assumes

16.4 Rainfall Rates, Roof Area, and the Flow-Rate Conversion

Key Takeaways Explain This Topic AI

IPC 1106.1 sizes vertical conductors, leaders, building storm drains, storm sewers and horizontal branches on the 100-year hourly rainfall rate from Figures 1106.1(1) through 1106.1(5) or approved local weather data.

IPC 1106.2.1 converts rainfall rate on a roof surface to a gallon per minute flow rate using Equation 11-1, where R is rainfall intensity in inches per hour and A is roof area in square feet.

IPC 1106.4 requires one-half of the area of any vertical wall that diverts rainwater to the roof to be added to the projected roof area for sizing conductors, leaders and horizontal storm piping.

IPC Appendix B Table B101 lists Colorado 100-year 1-hour rainfall rates of 2.4 inches per hour for Denver, 2.5 for Pueblo, 1.8 for Durango, 1.7 for Grand Junction, 1.5 for Craig and 3.0 for Lamar.

Appendix B is informative and not part of the code; its rates are derived from Figures 1106.1(1) through 1106.1(5).

Last updated: September 2026

The design storm

IPC 1106.1 :

The size of the vertical conductors and leaders, building storm drains, building storm sewers and any horizontal branches of such drains or sewers shall be based on the 100-year hourly rainfall rate indicated in Figures 1106.1(1) through 1106.1(5) or on other rainfall rates determined from approved local weather data .

Five figures cover the Western, Central and Eastern United States, Alaska and Hawaii. The rate is expressed in inches per hour for a 1-hour storm with a 100-year return period .

Appendix B tabulates the same data for major cities. Note its status: "This appendix is informative and is not part of the code," and its rates are derived from Figures 1106.1(1) through 1106.1(5) . Colorado adopts Appendix B by reference in Board Rule 1.2(A)(1), which is useful in the field; on the exam, the figures are the primary source and the appendix is a convenient lookup.

Colorado rates from Table B101

  • City Rate (in/hr)
  • Lamar 3.0
  • Pueblo 2.5
  • Denver 2.4
  • Durango 1.8
  • Grand Junction 1.7
  • Craig 1.5

Two things to notice. First, the range across a single state is twice over — a design that works in Grand Junction is badly undersized in Lamar. Second, Colorado's rates are modest by national standards: Miami is 4.7, New Orleans 4.8, Hilo 6.2.

Equation 11-1 — converting rainfall to flow

IPC 1106.2.1 Rainfall rate conversion method : the rainfall rate falling on a roof surface shall be converted to a gallon per minute flow rate in accordance with Equation 11-1 , where:

  • R = rainfall intensity in inches per hour
  • A = roof area in square feet
  • The conversion constant follows directly from unit arithmetic: 1 inch of rain over 1 square foot
  • = 1/12 cubic foot
  • = 0.0833 cubic feet
  • x 7.48 gallons per cubic foot
  • = 0.623 gallons per hour
  • / 60 minutes
  • = 0.0104 gallons per minute

So: Q (gpm) = 0.0104 x A (square feet) x R (inches per hour)

Carry 0.0104 and you can compute any storm flow without a table.

Worked conversions

  • Location Rate R Roof area A Q = 0.0104 x A x R
  • Denver 2.4 5,000 sq ft 124.8 gpm
  • Denver 2.4 20,000 sq ft 499.2 gpm
  • Pueblo 2.5 5,000 sq ft 130.0 gpm
  • Grand Junction 1.7 5,000 sq ft 88.4 gpm
  • Lamar 3.0 5,000 sq ft 156.0 gpm

Same roof, four Colorado cities, and the required flow varies by 76 percent .

Vertical walls — IPC 1106.4

In sizing roof drains and storm drainage piping, one-half of the area of any vertical wall that diverts rainwater to the roof shall be added to the projected roof area for inclusion in calculating the required size of vertical conductors, leaders and horizontal storm drainage piping.

Why one-half? Rain falls at an angle in wind. A vertical wall rising above a roof intercepts wind-driven rain and sheds it onto the roof below, but only from one side and only part of the time. The code's empirical allowance is 50 percent of the wall's area .

Worked vertical wall adjustment

A 60 ft x 40 ft lower roof ( 2,400 square feet ) abuts a taller building whose wall rises 25 feet above the lower roof along the full 60-foot length.

Wall area = 60 x 25 = 1,500 square feet .

Add one-half: 1,500 / 2 = 750 square feet .

Adjusted design area = 2,400 + 750 = 3,150 square feet.

In Denver: Q = 0.0104 x 3,150 x 2.4 = 78.6 gpm .

Ignoring the wall would have given 0.0104 x 2,400 x 2.4 = 59.9 gpm — a 31 percent undersizing error.

Where two walls divert onto the same roof, add one-half of each .

Checking against the roof drain

IPC 1106.2 :

Vertical and horizontal storm drain piping shall be sized based on the flow rate through the roof drain . The flow rate, as calculated in accordance with Section 1106.2.1, shall be checked against the roof drain manufacturer's published flow rate for the specific roof drain model and size to verify that the selected roof drain will handle the anticipated flow. The flow rate in storm drain piping shall not exceed that specified in Table 1106.2 .

Three checks, in order:

Compute the flow from rainfall and area (Equation 11-1).

Verify the roof drain can pass that flow at the anticipated ponding head (manufacturer's published rate, 1105.2).

Verify the piping can pass it within the Table 1106.2 limits.

Distributing flow among multiple drains

A roof with several drains divides the total flow among them, but not necessarily equally . Each drain serves the roof area that actually slopes to it. The practical method:

Determine the drainage area tributary to each drain from the roof slopes and crickets.

Add one-half of any diverting vertical wall area that sheds into that tributary area (1106.4).

Compute Q for each drain with Equation 11-1.

Size each conductor from Table 1106.2 (vertical column) for its own Q.

Size the horizontal collector for the accumulated Q at each point, at its installed slope.

Worked distribution

A 12,000 square foot Denver roof has four drains, with tributary areas of 4,000, 3,500, 2,500 and 2,000 square feet.

  • Drain Area Q = 0.0104 x A x 2.4
  • 1 4,000 99.8 gpm
  • 2 3,500 87.4 gpm
  • 3 2,500 62.4 gpm
  • 4 2,000 49.9 gpm
  • Total 12,000 299.5 gpm

Each vertical conductor is sized for its own flow; the horizontal main accumulates to 299.5 gpm at the building storm drain.

What Appendix B is and is not

Question Answer

Is Appendix B part of the code? No — it is informative, and it is adopted only where a jurisdiction adopts the appendix. Colorado does adopt Appendix B

  • Where do its numbers come from? Figures 1106.1(1) through 1106.1(5)
  • What if my city is not listed? Use the figures , or approved local weather data (1106.1)
  • What storm does it describe? 1-hour duration, 100-year return period
  • What units? Inches per hour

Loading diagram... Converting rainfall and roof area to design flow