4.3 Water Heater Pans, Pan Drains, and Storage Tank Requirements
Colorado Journeyworker Plumber Journeyman Plumber
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Passing the Colorado Journeyworker Plumber Exam
1.1 Exam Blueprint, Format, and the 2024 Code Changeover 1.2 Colorado Licenses, Experience Hours, and Apprentice Supervision 1.3 Permits, Inspections, Blue Tags, and Board Enforcement
2 Chapter 2: General Regulations (IPC Chapter 3)
2.1 Approved Materials, Certification, and General Installation Rules 2.2 Protection of Pipes: Contact, Notching, Shield Plates, and Freezing 2.3 Piping Support, Trenching, Bedding, and Backfill 2.4 Required Tests: Water, Air, and Backflow Assembly Testing
3 Chapter 3: Fixtures and Equipment (IPC Chapter 4)
3.1 Minimum Fixture Counts, Separate Facilities, and Toilet Room Location 3.2 Fixture Clearances, Compartments, and Setting Requirements 3.3 Water Closets, Urinals, Lavatories, Sinks, and Flush Devices 3.4 Showers, Bathtubs, Fixture Fittings, and Scald Protection
4 Chapter 4: Water Heaters (IPC Chapter 5)
4.1 Water Heater Installation, Location, Access, and Clearances 4.2 Relief Valves and Discharge Piping 4.3 Water Heater Pans, Pan Drains, and Storage Tank Requirements 4.4 Thermal Expansion Control and Hot Water Temperature Limits
5 Chapter 5: Water Supply Materials and Installation (IPC Chapter 6)
5.1 Water Service and Distribution Materials, and Sewer Separation 5.2 Joints, Connections, and Dissimilar Materials in Water Piping 5.3 Valves, Shutoffs, and Required Valve Locations
6 Chapter 6: Water Supply Sizing and Pressure (IPC Chapter 6 and Appendix E)
6.1 Pressure Limits, Pressure Reducing Valves, and Water Hammer 6.2 Water Supply Fixture Units and Estimating Demand 6.3 Sizing Water Piping with Appendix E and Table E104.1
7 Chapter 7: Cross-Connection Control and Backflow Prevention (IPC Sections 608-610, Chapter 13)
7.1 Cross-Connection Principles, Backsiphonage, and Backpressure 7.2 Air Gaps and the Backflow Preventer Family 7.3 Applying Backflow Protection to Specific Connections 7.4 Nonpotable Water Systems, Identification, and Reclaimed Water
8 Chapter 8: Sanitary Drainage Materials and Fittings (IPC Chapter 7)
8.1 Sanitary Drainage Materials and Where Each May Be Used 8.2 Drainage Joints, Transitions, and Prohibited Connections 8.3 Fittings for Change of Direction and Drainage Flow Patterns
9 Chapter 9: Sanitary Drainage Sizing (IPC Sections 704, 709-711)
9.1 Drainage Fixture Units and Load Estimation 9.2 Slope of Horizontal Drainage and Installation Rules 9.3 Sizing Building Drains, Building Sewers, and Horizontal Branches 9.4 Stacks, Branch Intervals, and Offsets in Tall Buildings
10 Chapter 10: Cleanouts, Sumps and Below-Sewer Drainage (IPC Sections 708, 712-716)
10.1 Cleanouts, Manholes, and Access Requirements 10.2 Backwater Valves and Fixtures Below the Sewer Level 10.3 Sumps, Sewage Ejectors, and Macerating Toilet Systems 10.4 Building Sewers, Private Disposal, and Special Drainage Conditions
11 Chapter 11: Vent Fundamentals and Terminals (IPC Sections 901-905, 908)
11.1 How Vents Work, Trap Seal Loss, and the One-Inch Rule 11.2 Vent Terminals, Roof Penetrations, and Sidewall Terminations 11.3 Vent Connections, Grade, and the Six-Inch Rules
12 Chapter 12: Vent Types and Sizing (IPC Sections 906-911, 917)
12.1 Individual Vents, Common Vents, and Vents for Stack Offsets 12.2 Trap-to-Vent Distance, Trap Arms, and Fixture Drains 12.3 Sizing Stack Vents, Vent Stacks, Branch Vents, and Headers 12.4 Putting a Vent System Together: A Worked Building
13 Chapter 13: Engineered and Special Venting (IPC Sections 912-916, 918-920)
13.1 Horizontal and Vertical Wet Venting 13.2 Waste Stack Vents, Circuit Vents, and Combination Waste and Vent 13.3 Island Fixture Venting and Air Admittance Valves
14 Chapter 14: Traps, Interceptors and Separators (IPC Chapter 10)
14.1 Fixture Traps, Trap Seals, and Prohibited Trap Types 14.2 Trap Seal Protection, Primers, and Barrier Devices 14.3 Grease Interceptors, Oil Separators, and Solids Interceptors
15 Chapter 15: Indirect and Special Waste (IPC Chapter 8)
15.1 Where Indirect Waste Is Required, and Air Gap Versus Air Break 15.2 Waste Receptors, Hub Drains, and Standpipes 15.3 Special Wastes, Chemical Neutralization, and Health Care Drainage
16 Chapter 16: Storm Drainage (IPC Chapter 11 and Appendix B)
16.1 Storm Drainage Scope, Disposal, and Prohibited Connections 16.2 Storm Drainage Materials, Roof Drains, and Conductors 16.3 Secondary Roof Drains, Scuppers, and Controlled Flow Systems 16.4 Rainfall Rates, Roof Area, and the Flow-Rate Conversion 16.5 Sizing Vertical Conductors, Leaders, and Storm Drains 16.6 Gutters, Subsoil Drains, Building Subdrains, and Storm Sumps
17 Chapter 17: Residential Fire Sprinklers (IRC Section P2904)
17.1 Residential Fire Sprinkler Systems (IRC Section P2904)
18 Chapter 18: Isometric Analysis and Plumbing Calculations
18.1 Reading Plumbing Isometrics and Riser Diagrams 18.2 Analyzing a DWV Isometric for Code Compliance 18.3 Offsets, Travel, and the Plumbing Math the Exam Assumes
4.3 Water Heater Pans, Pan Drains, and Storage Tank Requirements
Key Takeaways Explain This Topic AI
IPC 504.7 permits pans of galvanized steel or aluminum not less than 0.0236 inch thick, plastic not less than 0.036 inch thick, or other approved materials.
IPC 504.7 prohibits a plastic pan beneath a gas-fired water heater.
IPC 504.7.1 requires the pan to be not less than 1-1/2 inches deep and drained by an indirect waste pipe not less than 3/4 inch in diameter.
IPC 504.7.2 requires an exterior pan drain termination not less than 6 inches and not more than 24 inches above the adjacent ground surface.
IPC 504.7.2 exempts a replacement water heater from a pan drain where a pan drain was not previously installed.
Last updated: September 2026
When a pan is required
IPC 504.7 states the trigger condition rather than a list of locations:
Where a storage tank-type water heater or a hot water storage tank is installed in a location where water leakage from the tank will cause damage , the tank shall be installed in a pan.
The judgment is about consequence, not about floor level. A heater in a finished basement above a finished ceiling needs a pan. A heater in a detached, unfinished, sloped-to-drain utility shed generally does not. Local jurisdictions frequently make the requirement universal for interior installations; the code text itself is conditional.
Note two words: storage tank-type . A wall-hung tankless heater is not a storage tank-type water heater, so 504.7 does not reach it on its face — though manufacturers often require drainage protection independently, and IPC 301.7 makes the more restrictive provision control.
Pan material and thickness
- Material Minimum thickness Restriction
- Galvanized steel or aluminum 0.0236 inch none
- Plastic 0.036 inch Shall not be installed beneath a gas-fired water heater
- Other approved materials as approved as approved
The plastic prohibition under gas-fired heaters exists because a pan directly under a burner compartment can be exposed to flame rollout and to radiant heat from the draft hood area.
Colorado field note (not exam-scored): Board Rule 1.2(E)(1)(bb) adds a sentence permitting a pan that would otherwise be barred if it is constructed of material having a flame spread index of 25 or less and a smoke-developed index of 450 or less tested to ASTM E84 or UL 723. Rule 1.2(E)(1)(aa) adds an exception for replacements of water heaters that did not have a pan previously installed to the code in effect at the original installation. Answer the model code on the exam.
Pan size and drain — IPC 504.7.1
The pan shall be not less than 1-1/2 inches in depth .
It shall be of sufficient size and shape to receive all dripping or condensate from the tank or water heater.
It shall be drained by an indirect waste pipe having a diameter of not less than 3/4 inch .
Piping for safety pan drains shall be of the materials listed in IPC Table 605.4 .
"Indirect waste pipe" is the operative phrase. The pan drain is an indirect waste under IPC Chapter 8, so it may never connect directly to the drainage system; it terminates over a receptor with an air gap or air break. That places pan drains in the same family as relief valve discharge and condensate drainage.
Pan drain termination — IPC 504.7.2
The pan drain shall extend full size and terminate over a suitably located indirect waste receptor or floor drain , or extend to the exterior of the building and terminate not less than 6 inches and not more than 24 inches above the adjacent ground surface . Where a pan drain was not previously installed, a pan drain shall not be required for a replacement water heater installation .
Two dimensions, both frequently confused with the relief-valve rule of 504.6:
Pipe Termination requirement Section
Relief valve discharge not more than 6 inches above and not less than two times the pipe diameter above the floor or flood level rim 504.6 item 10
Pan drain, exterior not less than 6 inches and not more than 24 inches above the adjacent ground surface 504.7.2
Six inches is a maximum in one rule and a minimum in the other. Read the question carefully.
The replacement exemption is a practical, retroactivity-limiting rule: swapping a heater in a house that never had a pan drain does not compel you to cut a new drain line through finished construction. It does not exempt you from the pan itself.
Where the relief valve may discharge
IPC 504.6 item 5 expressly allows relief discharge " to the pan serving the water heater or storage tank ." That is why a correctly built installation often shows one 3/4-inch line from the T&P valve terminating over the pan, and a separate 3/4-inch pan drain running to a receptor. What is not permitted is tying the relief discharge into the pan drain piping — item 4 requires the discharge to serve a single relief device and not connect to piping serving other equipment.
Separate storage tanks
Where a system uses a water heater plus a separate storage tank:
IPC 504.4.1 requires an approved self-closing levered pressure and temperature relief valve (or combination) on both the storage water heater and the storage tank.
IPC 504.7 applies the pan requirement to a "hot water storage tank" in its own right.
IPC 503.2 requires the connection method to provide proper circulation of water through the heater.
IPC 505.1 requires unfired hot water storage tanks to be insulated to R-12.5 .
IPC 607.2.1.1 limits the pump that circulates between the heater and the storage tank to operating not greater than 5 minutes after the end of the heating cycle .
Worked example: sizing and routing the drains
A 75-gallon electric storage water heater sits on a second-floor mechanical closet slab above a finished dining room. The nearest floor drain is 14 feet away in the same closet's neighboring laundry.
Pan required? Yes — leakage will damage the ceiling below (504.7).
Pan material? Galvanized steel at 0.0236 inch or plastic at 0.036 inch. The heater is electric, so plastic is permitted.
Pan depth? Not less than 1-1/2 inches, sized to catch all dripping and condensate (504.7.1).
Pan drain? Not less than 3/4 inch, indirect waste, of a Table 605.4 material, full size to its termination (504.7.1, 504.7.2).
Termination? Over the laundry floor drain with an air gap, since an interior receptor is available. If it were routed through the exterior wall instead, the outlet would have to land 6 to 24 inches above the adjacent ground .
Relief valve discharge? A separate 3/4-inch line, not tied into the pan drain, terminating either over the pan or to the floor — not more than 6 inches above, and not less than 1-1/2 inches above, with no threaded end and no valve.
Thermal expansion? If the cold supply passes a check valve, pressure reducing valve or backflow preventer, an expansion control device is required downstream of them (607.3) — covered in the next section.