5.2 Joints, Connections, and Dissimilar Materials in Water Piping
Colorado Journeyworker Plumber Journeyman Plumber
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Passing the Colorado Journeyworker Plumber Exam
1.1 Exam Blueprint, Format, and the 2024 Code Changeover 1.2 Colorado Licenses, Experience Hours, and Apprentice Supervision 1.3 Permits, Inspections, Blue Tags, and Board Enforcement
2 Chapter 2: General Regulations (IPC Chapter 3)
2.1 Approved Materials, Certification, and General Installation Rules 2.2 Protection of Pipes: Contact, Notching, Shield Plates, and Freezing 2.3 Piping Support, Trenching, Bedding, and Backfill 2.4 Required Tests: Water, Air, and Backflow Assembly Testing
3 Chapter 3: Fixtures and Equipment (IPC Chapter 4)
3.1 Minimum Fixture Counts, Separate Facilities, and Toilet Room Location 3.2 Fixture Clearances, Compartments, and Setting Requirements 3.3 Water Closets, Urinals, Lavatories, Sinks, and Flush Devices 3.4 Showers, Bathtubs, Fixture Fittings, and Scald Protection
4 Chapter 4: Water Heaters (IPC Chapter 5)
4.1 Water Heater Installation, Location, Access, and Clearances 4.2 Relief Valves and Discharge Piping 4.3 Water Heater Pans, Pan Drains, and Storage Tank Requirements 4.4 Thermal Expansion Control and Hot Water Temperature Limits
5 Chapter 5: Water Supply Materials and Installation (IPC Chapter 6)
5.1 Water Service and Distribution Materials, and Sewer Separation 5.2 Joints, Connections, and Dissimilar Materials in Water Piping 5.3 Valves, Shutoffs, and Required Valve Locations
6 Chapter 6: Water Supply Sizing and Pressure (IPC Chapter 6 and Appendix E)
6.1 Pressure Limits, Pressure Reducing Valves, and Water Hammer 6.2 Water Supply Fixture Units and Estimating Demand 6.3 Sizing Water Piping with Appendix E and Table E104.1
7 Chapter 7: Cross-Connection Control and Backflow Prevention (IPC Sections 608-610, Chapter 13)
7.1 Cross-Connection Principles, Backsiphonage, and Backpressure 7.2 Air Gaps and the Backflow Preventer Family 7.3 Applying Backflow Protection to Specific Connections 7.4 Nonpotable Water Systems, Identification, and Reclaimed Water
8 Chapter 8: Sanitary Drainage Materials and Fittings (IPC Chapter 7)
8.1 Sanitary Drainage Materials and Where Each May Be Used 8.2 Drainage Joints, Transitions, and Prohibited Connections 8.3 Fittings for Change of Direction and Drainage Flow Patterns
9 Chapter 9: Sanitary Drainage Sizing (IPC Sections 704, 709-711)
9.1 Drainage Fixture Units and Load Estimation 9.2 Slope of Horizontal Drainage and Installation Rules 9.3 Sizing Building Drains, Building Sewers, and Horizontal Branches 9.4 Stacks, Branch Intervals, and Offsets in Tall Buildings
10 Chapter 10: Cleanouts, Sumps and Below-Sewer Drainage (IPC Sections 708, 712-716)
10.1 Cleanouts, Manholes, and Access Requirements 10.2 Backwater Valves and Fixtures Below the Sewer Level 10.3 Sumps, Sewage Ejectors, and Macerating Toilet Systems 10.4 Building Sewers, Private Disposal, and Special Drainage Conditions
11 Chapter 11: Vent Fundamentals and Terminals (IPC Sections 901-905, 908)
11.1 How Vents Work, Trap Seal Loss, and the One-Inch Rule 11.2 Vent Terminals, Roof Penetrations, and Sidewall Terminations 11.3 Vent Connections, Grade, and the Six-Inch Rules
12 Chapter 12: Vent Types and Sizing (IPC Sections 906-911, 917)
12.1 Individual Vents, Common Vents, and Vents for Stack Offsets 12.2 Trap-to-Vent Distance, Trap Arms, and Fixture Drains 12.3 Sizing Stack Vents, Vent Stacks, Branch Vents, and Headers 12.4 Putting a Vent System Together: A Worked Building
13 Chapter 13: Engineered and Special Venting (IPC Sections 912-916, 918-920)
13.1 Horizontal and Vertical Wet Venting 13.2 Waste Stack Vents, Circuit Vents, and Combination Waste and Vent 13.3 Island Fixture Venting and Air Admittance Valves
14 Chapter 14: Traps, Interceptors and Separators (IPC Chapter 10)
14.1 Fixture Traps, Trap Seals, and Prohibited Trap Types 14.2 Trap Seal Protection, Primers, and Barrier Devices 14.3 Grease Interceptors, Oil Separators, and Solids Interceptors
15 Chapter 15: Indirect and Special Waste (IPC Chapter 8)
15.1 Where Indirect Waste Is Required, and Air Gap Versus Air Break 15.2 Waste Receptors, Hub Drains, and Standpipes 15.3 Special Wastes, Chemical Neutralization, and Health Care Drainage
16 Chapter 16: Storm Drainage (IPC Chapter 11 and Appendix B)
16.1 Storm Drainage Scope, Disposal, and Prohibited Connections 16.2 Storm Drainage Materials, Roof Drains, and Conductors 16.3 Secondary Roof Drains, Scuppers, and Controlled Flow Systems 16.4 Rainfall Rates, Roof Area, and the Flow-Rate Conversion 16.5 Sizing Vertical Conductors, Leaders, and Storm Drains 16.6 Gutters, Subsoil Drains, Building Subdrains, and Storm Sumps
17 Chapter 17: Residential Fire Sprinklers (IRC Section P2904)
17.1 Residential Fire Sprinkler Systems (IRC Section P2904)
18 Chapter 18: Isometric Analysis and Plumbing Calculations
18.1 Reading Plumbing Isometrics and Riser Diagrams 18.2 Analyzing a DWV Isometric for Code Compliance 18.3 Offsets, Travel, and the Plumbing Math the Exam Assumes
5.2 Joints, Connections, and Dissimilar Materials in Water Piping
Key Takeaways Explain This Topic AI
IPC 605.9 prohibits cement or concrete joints, mastic or hot-pour bituminous joints, joints made with fittings not approved for the installation, solvent-cement joints between different types of plastic pipe, and saddle-type fittings.
IPC 605.12.3 and 605.13.6 require solder and fluxes used in potable water systems to contain not more than 0.2 percent lead.
IPC 605.23.1 requires a brass converter fitting or dielectric fitting where copper or copper-alloy tubing joins galvanized steel pipe.
IPC 605.14.2 and 605.21.3 require CPVC and PVC solvent-cement joints to be made with primer and cement complying with ASTM F493 and ASTM D2564 respectively.
IPC 605.5.1 permits mechanically formed tee fittings in copper tubing only when formed with an approved tool and brazed, not soldered.
Last updated: September 2026
Prohibited joints and connections — IPC 605.9
Start with the list of what you may never do, because exam items are often phrased as "which of the following is prohibited."
The following joints and connections shall be prohibited in the water supply system:
Cement or concrete joints.
Mastic or hot-pour bituminous joints.
Joints made with fittings not approved for the specific installation.
Solvent-cement joints between different types of plastic pipe , except as provided in 605.23.2.
Saddle-type fittings.
Compare the parallel drainage list in IPC 707.1 , which adds "joints between different diameter pipes made with elastomeric rolling O-rings" and also bans saddle-type fittings. Saddle fittings are prohibited on both the supply and the drainage side.
Joining methods by material
Material Permitted joints Key requirement
Copper pipe (605.12) Brazed, mechanical, solder , threaded, welded Solder and flux not more than 0.2 percent lead ; brazing filler per AWS A5.8
Copper tubing (605.13) Brazed, flared , grooved/shouldered mechanical, mechanical, press-connect , solder, push-fit Flared joints made with a flaring tool to the proper angle; press-connect fittings conform to ASSE 1061
CPVC (605.14) Mechanical, solvent cement , threaded, push-fit Primer per ASTM F656 , cement per ASTM F493 ; one-step cement permitted only where listed
PEX (605.16) Flared, mechanical (cold expansion, insert, compression), push-fit Fittings per ASTM F1807, F1960, F2080, F2159, F2434 and similar
PVC (605.21) Mechanical, grooved/shouldered, solvent cement , threaded Primer per ASTM F656 , cement per ASTM D2564
PE (605.18) Flared, heat fusion , mechanical Heat-fusion joints per the manufacturer; installation per 605.18.4
Polypropylene (605.19) Heat fusion , mechanical and compression sleeve Socket or butt fusion per the manufacturer
Steel (605.17) Threaded, mechanical, grooved/shouldered Threads per ASME B1.20.1 ; approved thread compound or tape on male threads
- Stainless steel (605.22) Mechanical, welded, grooved/shouldered Welded joints per approved procedures
- Gray/ductile iron (605.11) Gasketed per AWWA C111/A21.11 —
Two rules easy to forget:
IPC 605.5.1 Mechanically formed tee fittings — a collared branch outlet formed in copper tube with an approved tool is permitted, but the joint shall be brazed . A soldered mechanically formed tee is not code compliant.
IPC 605.8 Manufactured pipe nipples must conform to Table 605.8 (ASTM A733 for steel, ASTM B687 for brass).
Dissimilar materials — IPC 605.23
Galvanic corrosion is the reason. When two metals with different electrode potentials touch in the presence of an electrolyte (water), the less noble metal corrodes.
Connection Required method Section
Copper or copper-alloy tubing to galvanized steel pipe A brass converter fitting or a dielectric fitting ; the joint is made with the copper pipe end soldered or brazed into the converter fitting 605.23.1
- Plastic pipe or tubing to other piping material Approved adapter or transition fitting 605.23.2
- Stainless steel to other materials Approved manufactured transition fitting 605.23.3
The practical corollary: copper male adapter screwed directly into a galvanized fitting is a defect waiting to happen, and it fails 605.23.1 on its face.
The same principle appears in IPC 305.1 (metallic piping other than cast iron, ductile iron and galvanized steel may not contact steel framing, concrete or masonry) and IPC 308.3 (hangers and strapping of approved material that will not promote galvanic action ). A copper line hung in a bare steel strap through a steel stud assembly violates all three ideas at once.
Solder, flux and lead
Three numbers, three contexts:
- Rule Limit Section
- Solder and flux in potable water systems 0.2 percent lead 605.12.3, 605.13.6
- Pipe and fittings in the water supply system 8 percent lead 605.2
- Wetted surfaces conveying drinking or cooking water 0.25 percent weighted average 605.2.1
- Fixture supplies and connectors
IPC 604.5 sets the minimum fixture supply size from Table 604.5 and adds three installation rules:
The fixture supply pipe shall terminate not more than 30 inches from the point of connection to the fixture.
A reduced-size flexible water connector between the supply pipe and the fixture shall be of an approved type .
The supply pipe shall extend to the floor or wall adjacent to the fixture .
Table 604.5 minimum fixture supply sizes worth memorizing:
- Fixture Minimum supply
- Lavatory, bidet, drinking fountain 3/8 inch
- Water closet, flush tank or flushometer tank 3/8 inch
Bathtub, kitchen sink, dishwasher, laundry, single-head shower, hose bibb, wall hydrant, service sink, urinal flush tank, one-piece water closet 1/2 inch
- Flushing rim sink, urinal flushometer valve 3/4 inch
- Water closet, flushometer valve 1 inch
Footnote a permits one nominal tube size smaller for an individual distribution line from a manifold in a parallel water distribution system , where the developed length of the distribution line is 50 feet or less and available pressure at the meter is 35 psi or greater .
IPC 604.10 governs gridded and parallel manifolds. Manifolds are sized by Table 604.10.1 on total demand in gpm, at 4 feet per second (cold-water-only style installations) or 8 feet per second :
- Manifold nominal size Max demand at 4 fps Max demand at 8 fps
- 1/2 inch 2 gpm 5 gpm
- 3/4 inch 6 gpm 11 gpm
- 1 inch 10 gpm 20 gpm
- 1-1/4 inch 15 gpm 31 gpm
- 1-1/2 inch 22 gpm 44 gpm
604.10.2 requires individual fixture shutoff valves at the manifold to be identified as to the fixture supplied , and 604.10.3 requires access to manifolds with integral valves.
Installation details that get cited
IPC 604.2 System interconnection : at points of interconnection between hot and cold piping and individual fixtures, appliances or devices, provisions must prevent flow between the two systems . A failed single-lever cartridge that lets hot into the cold line violates this.
IPC 604.11 : individual pressure balancing in-line valves for individual fixture fittings comply with ASSE 1066 , must be installed with access, and shall not be used alone as a substitute for the ASSE 1016 shower valve required by 412.3.
IPC 608.10 Reutilization prohibited : water that has been used for cooling equipment or other processes shall not be returned to the potable water system; it may be reused for flushing water closets and urinals or for irrigation, provided it is not sprayed onto areas open to public use.
Colorado field note (not exam-scored): Board Rule 1.2(E)(1)(cc) deletes the exception in IPC 605.15.2 , and Rule 1.2(E)(1)(jj) deletes the exception in IPC 705.10.2 — the exceptions that otherwise allow one-step cements without primer on certain plastic joints. In Colorado, primer is not optional on those joints.