5.3 Valves, Shutoffs, and Required Valve Locations

Colorado Journeyworker Plumber Journeyman Plumber

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Passing the Colorado Journeyworker Plumber Exam

1.1 Exam Blueprint, Format, and the 2024 Code Changeover 1.2 Colorado Licenses, Experience Hours, and Apprentice Supervision 1.3 Permits, Inspections, Blue Tags, and Board Enforcement

2 Chapter 2: General Regulations (IPC Chapter 3)

2.1 Approved Materials, Certification, and General Installation Rules 2.2 Protection of Pipes: Contact, Notching, Shield Plates, and Freezing 2.3 Piping Support, Trenching, Bedding, and Backfill 2.4 Required Tests: Water, Air, and Backflow Assembly Testing

3 Chapter 3: Fixtures and Equipment (IPC Chapter 4)

3.1 Minimum Fixture Counts, Separate Facilities, and Toilet Room Location 3.2 Fixture Clearances, Compartments, and Setting Requirements 3.3 Water Closets, Urinals, Lavatories, Sinks, and Flush Devices 3.4 Showers, Bathtubs, Fixture Fittings, and Scald Protection

4 Chapter 4: Water Heaters (IPC Chapter 5)

4.1 Water Heater Installation, Location, Access, and Clearances 4.2 Relief Valves and Discharge Piping 4.3 Water Heater Pans, Pan Drains, and Storage Tank Requirements 4.4 Thermal Expansion Control and Hot Water Temperature Limits

5 Chapter 5: Water Supply Materials and Installation (IPC Chapter 6)

5.1 Water Service and Distribution Materials, and Sewer Separation 5.2 Joints, Connections, and Dissimilar Materials in Water Piping 5.3 Valves, Shutoffs, and Required Valve Locations

6 Chapter 6: Water Supply Sizing and Pressure (IPC Chapter 6 and Appendix E)

6.1 Pressure Limits, Pressure Reducing Valves, and Water Hammer 6.2 Water Supply Fixture Units and Estimating Demand 6.3 Sizing Water Piping with Appendix E and Table E104.1

7 Chapter 7: Cross-Connection Control and Backflow Prevention (IPC Sections 608-610, Chapter 13)

7.1 Cross-Connection Principles, Backsiphonage, and Backpressure 7.2 Air Gaps and the Backflow Preventer Family 7.3 Applying Backflow Protection to Specific Connections 7.4 Nonpotable Water Systems, Identification, and Reclaimed Water

8 Chapter 8: Sanitary Drainage Materials and Fittings (IPC Chapter 7)

8.1 Sanitary Drainage Materials and Where Each May Be Used 8.2 Drainage Joints, Transitions, and Prohibited Connections 8.3 Fittings for Change of Direction and Drainage Flow Patterns

9 Chapter 9: Sanitary Drainage Sizing (IPC Sections 704, 709-711)

9.1 Drainage Fixture Units and Load Estimation 9.2 Slope of Horizontal Drainage and Installation Rules 9.3 Sizing Building Drains, Building Sewers, and Horizontal Branches 9.4 Stacks, Branch Intervals, and Offsets in Tall Buildings

10 Chapter 10: Cleanouts, Sumps and Below-Sewer Drainage (IPC Sections 708, 712-716)

10.1 Cleanouts, Manholes, and Access Requirements 10.2 Backwater Valves and Fixtures Below the Sewer Level 10.3 Sumps, Sewage Ejectors, and Macerating Toilet Systems 10.4 Building Sewers, Private Disposal, and Special Drainage Conditions

11 Chapter 11: Vent Fundamentals and Terminals (IPC Sections 901-905, 908)

11.1 How Vents Work, Trap Seal Loss, and the One-Inch Rule 11.2 Vent Terminals, Roof Penetrations, and Sidewall Terminations 11.3 Vent Connections, Grade, and the Six-Inch Rules

12 Chapter 12: Vent Types and Sizing (IPC Sections 906-911, 917)

12.1 Individual Vents, Common Vents, and Vents for Stack Offsets 12.2 Trap-to-Vent Distance, Trap Arms, and Fixture Drains 12.3 Sizing Stack Vents, Vent Stacks, Branch Vents, and Headers 12.4 Putting a Vent System Together: A Worked Building

13 Chapter 13: Engineered and Special Venting (IPC Sections 912-916, 918-920)

13.1 Horizontal and Vertical Wet Venting 13.2 Waste Stack Vents, Circuit Vents, and Combination Waste and Vent 13.3 Island Fixture Venting and Air Admittance Valves

14 Chapter 14: Traps, Interceptors and Separators (IPC Chapter 10)

14.1 Fixture Traps, Trap Seals, and Prohibited Trap Types 14.2 Trap Seal Protection, Primers, and Barrier Devices 14.3 Grease Interceptors, Oil Separators, and Solids Interceptors

15 Chapter 15: Indirect and Special Waste (IPC Chapter 8)

15.1 Where Indirect Waste Is Required, and Air Gap Versus Air Break 15.2 Waste Receptors, Hub Drains, and Standpipes 15.3 Special Wastes, Chemical Neutralization, and Health Care Drainage

16 Chapter 16: Storm Drainage (IPC Chapter 11 and Appendix B)

16.1 Storm Drainage Scope, Disposal, and Prohibited Connections 16.2 Storm Drainage Materials, Roof Drains, and Conductors 16.3 Secondary Roof Drains, Scuppers, and Controlled Flow Systems 16.4 Rainfall Rates, Roof Area, and the Flow-Rate Conversion 16.5 Sizing Vertical Conductors, Leaders, and Storm Drains 16.6 Gutters, Subsoil Drains, Building Subdrains, and Storm Sumps

17 Chapter 17: Residential Fire Sprinklers (IRC Section P2904)

17.1 Residential Fire Sprinkler Systems (IRC Section P2904)

18 Chapter 18: Isometric Analysis and Plumbing Calculations

18.1 Reading Plumbing Isometrics and Riser Diagrams 18.2 Analyzing a DWV Isometric for Code Compliance 18.3 Offsets, Travel, and the Plumbing Math the Exam Assumes

5.3 Valves, Shutoffs, and Required Valve Locations

Key Takeaways Explain This Topic AI

IPC 606.1 requires full-open valves near the curb, at the entrance to the structure, on the discharge side of every water meter, at the base of risers, at the top of down-feed pipes, at the entrance to every dwelling unit, at water tanks, and on the supply to every water heater.

IPC 606.2 requires shutoff valves on the fixture supply to each fixture other than bathtubs and showers in one- and two-family dwellings, on the supply to each sillcock, and on the supply to each appliance or mechanical equipment.

IPC 606.3 requires access to all full-open valves and shutoff valves, and IPC 606.4 requires identification of valves not adjacent to the fixture or appliance served.

IPC 606.5.5 requires a low-pressure cutoff on all booster pumps to prevent a vacuum when suction-side pressure falls to 10 psi or less.

IPC 606.5.6 requires potable water inlets to gravity tanks to terminate with an air gap not less than 4 inches above the overflow.

Last updated: September 2026

Full-open valves versus shutoff valves

The IPC distinguishes two valve classes, and the distinction drives the required locations.

A full-open valve offers essentially unobstructed flow when open — a gate, ball or butterfly valve. It is used where the whole system or a major branch must be isolated without throttling normal flow.

A shutoff valve simply stops flow — the angle stop under a lavatory is the classic example.

Where full-open valves are required — IPC 606.1

Learn this as a list of eight :

On the building water service pipe from the public water supply near the curb.

On the water distribution supply pipe at the entrance into the structure.

2.1 In multiple-tenant buildings with a common water supply system serving other than one- and two-family dwellings, a main shutoff valve for each tenant .

On the discharge side of every water meter.

On the base of every water riser pipe in occupancies other than multiple-family residential occupancies two stories or less in height, and other than one- and two-family residential occupancies.

On the top of every water down-feed pipe in occupancies other than one- and two-family residential occupancies.

On the entrance to every water supply pipe to a dwelling unit , except where supplying a single fixture equipped with individual stops.

On the water supply pipe to a gravity or pressurized water tank.

On the water supply pipe to every water heater.

Item 8 dovetails with IPC 503.1 , which adds that the water heater's cold water branch valve must be near the equipment , serve only that heater, not disrupt the rest of the cold water system, and have access on the same floor level .

Note what items 4 and 5 exclude. In a single-family house you do not need a full-open valve at the base of the riser; in a four-story apartment building you do.

Where shutoff valves are required — IPC 606.2

Three locations:

On the fixture supply to each plumbing fixture , other than bathtubs and showers in one- and two-family residential occupancies, and other than in individual sleeping units provided with unit shutoff valves in hotels, motels, boarding houses and similar occupancies.

On the water supply pipe to each sillcock.

On the water supply pipe to each appliance or mechanical equipment.

The bathtub-and-shower carve-out is the exception everyone remembers wrong. It applies only in one- and two-family residential occupancies. In a hotel, an apartment building common bathroom, or a gym, the tub and shower supplies need stops unless the sleeping unit itself has a unit shutoff.

Access and identification

IPC 606.3 : access shall be provided to all full-open valves and shutoff valves. A valve buried behind unbroken drywall fails, no matter how correct its location.

IPC 606.4 : service and hose bibb valves shall be identified. Other valves installed in locations not adjacent to the fixture or appliance served shall be identified, indicating the fixture or appliance served . This is why a mechanical room valve tag set is not optional.

IPC 604.10.2 repeats the idea for manifolds: individual fixture shutoff valves at a manifold must be identified as to the fixture supplied.

Water pressure booster systems — IPC 606.5

IPC 604.7 triggers the requirement: wherever pressure from the street main or other source is insufficient to provide the flow pressures of Table 604.3 , a booster system conforming to Section 606.5 must be installed. IPC 606.5.1 lists the three permitted approaches: an elevated water tank , a hydropneumatic pressure booster system , or a water pressure booster pump .

The Section 606.5 subsections carry several very testable numbers:

  • Section Requirement
  • 606.5.2 Water supply tanks supported per the International Building Code

606.5.3 Tanks covered to keep out unauthorized persons, dirt and vermin; gravity tank covers vented with a return bend vent of area not less than the area of the down-feed riser , screened with corrosion-resistant screen not less than 16 by 20 mesh per inch

606.5.4 Overflow sized per Table 606.5.4; outlet discharges not less than 6 inches above the roof, roof drain, floor, floor drain, or over an open water-supplied fixture; covered with 16 by 20 mesh screen plus 1/4-inch hardware cloth , or terminating in a horizontal angle seat check valve ; drainage directed so as not to freeze on roof walks

606.5.5 Low-pressure cutoff on all booster pumps, preventing a vacuum or negative pressure on the suction side when positive suction pressure of 10 psi or less occurs

606.5.6 Potable water inlets to gravity tanks controlled by a fill valve or automatic supply valve; inlet terminated with an air gap not less than 4 inches above the overflow

606.5.7 A drain pipe with a valve at the lowest point of each tank, discharging as required for overflows, sized per Table 606.5.7 (1 inch up to 750 gallons, 1-1/2 inches for 751 to 1,500 gallons, larger above)

Overflow pipe sizing from Table 606.5.4 , keyed to the capacity of the water supply line to the tank :

  • Supply line capacity (gpm) Overflow diameter
  • 0 - 50 2 inches
  • 50 - 150 2-1/2 inches
  • 150 - 200 3 inches
  • 200 - 400 4 inches
  • 400 - 700 5 inches
  • 700 - 1,000 6 inches
  • Over 1,000 8 inches

606.5.5 is the safety rule to remember. A booster pump that keeps running as suction pressure collapses creates negative pressure on the street side — precisely the backsiphonage condition Chapter 7 of this guide exists to prevent. The low-pressure cutoff is a cross-connection control device as much as a pump control.

Worked layout: a four-story mixed-use building

A four-story building has retail on the ground floor and three floors of apartments, served by a 2-inch water service and a 2-inch meter, with an upfeed riser.

Full-open valves required:

At the curb on the service (606.1 item 1).

At the entrance into the structure on the distribution supply pipe (item 2).

A main shutoff for each tenant , because this is a multiple-tenant building with a common supply serving other than one- and two-family dwellings (item 2.1).

On the discharge side of the meter (item 3).

At the base of the riser — the building is four stories, so the "two stories or less" exclusion does not apply (item 4).

At the entrance to each dwelling unit (item 6).

On the supply to each water heater (item 8).

Shutoff valves required:

At each fixture supply . The apartments are not one- and two-family occupancies, so the tubs and showers need stops too .

At each sillcock and at each appliance , including the clothes washer boxes and the rooftop makeup air unit.

All of them must be accessible (606.3), and the mechanical room and roof valves must be tagged with what they serve (606.4).

Loading diagram... Required full-open valve locations (IPC 606.1)