6.1 Pressure Limits, Pressure Reducing Valves, and Water Hammer

Colorado Journeyworker Plumber Journeyman Plumber

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Passing the Colorado Journeyworker Plumber Exam

1.1 Exam Blueprint, Format, and the 2024 Code Changeover 1.2 Colorado Licenses, Experience Hours, and Apprentice Supervision 1.3 Permits, Inspections, Blue Tags, and Board Enforcement

2 Chapter 2: General Regulations (IPC Chapter 3)

2.1 Approved Materials, Certification, and General Installation Rules 2.2 Protection of Pipes: Contact, Notching, Shield Plates, and Freezing 2.3 Piping Support, Trenching, Bedding, and Backfill 2.4 Required Tests: Water, Air, and Backflow Assembly Testing

3 Chapter 3: Fixtures and Equipment (IPC Chapter 4)

3.1 Minimum Fixture Counts, Separate Facilities, and Toilet Room Location 3.2 Fixture Clearances, Compartments, and Setting Requirements 3.3 Water Closets, Urinals, Lavatories, Sinks, and Flush Devices 3.4 Showers, Bathtubs, Fixture Fittings, and Scald Protection

4 Chapter 4: Water Heaters (IPC Chapter 5)

4.1 Water Heater Installation, Location, Access, and Clearances 4.2 Relief Valves and Discharge Piping 4.3 Water Heater Pans, Pan Drains, and Storage Tank Requirements 4.4 Thermal Expansion Control and Hot Water Temperature Limits

5 Chapter 5: Water Supply Materials and Installation (IPC Chapter 6)

5.1 Water Service and Distribution Materials, and Sewer Separation 5.2 Joints, Connections, and Dissimilar Materials in Water Piping 5.3 Valves, Shutoffs, and Required Valve Locations

6 Chapter 6: Water Supply Sizing and Pressure (IPC Chapter 6 and Appendix E)

6.1 Pressure Limits, Pressure Reducing Valves, and Water Hammer 6.2 Water Supply Fixture Units and Estimating Demand 6.3 Sizing Water Piping with Appendix E and Table E104.1

7 Chapter 7: Cross-Connection Control and Backflow Prevention (IPC Sections 608-610, Chapter 13)

7.1 Cross-Connection Principles, Backsiphonage, and Backpressure 7.2 Air Gaps and the Backflow Preventer Family 7.3 Applying Backflow Protection to Specific Connections 7.4 Nonpotable Water Systems, Identification, and Reclaimed Water

8 Chapter 8: Sanitary Drainage Materials and Fittings (IPC Chapter 7)

8.1 Sanitary Drainage Materials and Where Each May Be Used 8.2 Drainage Joints, Transitions, and Prohibited Connections 8.3 Fittings for Change of Direction and Drainage Flow Patterns

9 Chapter 9: Sanitary Drainage Sizing (IPC Sections 704, 709-711)

9.1 Drainage Fixture Units and Load Estimation 9.2 Slope of Horizontal Drainage and Installation Rules 9.3 Sizing Building Drains, Building Sewers, and Horizontal Branches 9.4 Stacks, Branch Intervals, and Offsets in Tall Buildings

10 Chapter 10: Cleanouts, Sumps and Below-Sewer Drainage (IPC Sections 708, 712-716)

10.1 Cleanouts, Manholes, and Access Requirements 10.2 Backwater Valves and Fixtures Below the Sewer Level 10.3 Sumps, Sewage Ejectors, and Macerating Toilet Systems 10.4 Building Sewers, Private Disposal, and Special Drainage Conditions

11 Chapter 11: Vent Fundamentals and Terminals (IPC Sections 901-905, 908)

11.1 How Vents Work, Trap Seal Loss, and the One-Inch Rule 11.2 Vent Terminals, Roof Penetrations, and Sidewall Terminations 11.3 Vent Connections, Grade, and the Six-Inch Rules

12 Chapter 12: Vent Types and Sizing (IPC Sections 906-911, 917)

12.1 Individual Vents, Common Vents, and Vents for Stack Offsets 12.2 Trap-to-Vent Distance, Trap Arms, and Fixture Drains 12.3 Sizing Stack Vents, Vent Stacks, Branch Vents, and Headers 12.4 Putting a Vent System Together: A Worked Building

13 Chapter 13: Engineered and Special Venting (IPC Sections 912-916, 918-920)

13.1 Horizontal and Vertical Wet Venting 13.2 Waste Stack Vents, Circuit Vents, and Combination Waste and Vent 13.3 Island Fixture Venting and Air Admittance Valves

14 Chapter 14: Traps, Interceptors and Separators (IPC Chapter 10)

14.1 Fixture Traps, Trap Seals, and Prohibited Trap Types 14.2 Trap Seal Protection, Primers, and Barrier Devices 14.3 Grease Interceptors, Oil Separators, and Solids Interceptors

15 Chapter 15: Indirect and Special Waste (IPC Chapter 8)

15.1 Where Indirect Waste Is Required, and Air Gap Versus Air Break 15.2 Waste Receptors, Hub Drains, and Standpipes 15.3 Special Wastes, Chemical Neutralization, and Health Care Drainage

16 Chapter 16: Storm Drainage (IPC Chapter 11 and Appendix B)

16.1 Storm Drainage Scope, Disposal, and Prohibited Connections 16.2 Storm Drainage Materials, Roof Drains, and Conductors 16.3 Secondary Roof Drains, Scuppers, and Controlled Flow Systems 16.4 Rainfall Rates, Roof Area, and the Flow-Rate Conversion 16.5 Sizing Vertical Conductors, Leaders, and Storm Drains 16.6 Gutters, Subsoil Drains, Building Subdrains, and Storm Sumps

17 Chapter 17: Residential Fire Sprinklers (IRC Section P2904)

17.1 Residential Fire Sprinkler Systems (IRC Section P2904)

18 Chapter 18: Isometric Analysis and Plumbing Calculations

18.1 Reading Plumbing Isometrics and Riser Diagrams 18.2 Analyzing a DWV Isometric for Code Compliance 18.3 Offsets, Travel, and the Plumbing Math the Exam Assumes

6.1 Pressure Limits, Pressure Reducing Valves, and Water Hammer

Key Takeaways Explain This Topic AI

IPC 604.8 requires an approved pressure reducing valve conforming to ASSE 1003 or CSA B356 with strainer where water pressure within a building exceeds 80 psi static.

IPC 604.8.1 requires the pressure reducing valve to be designed to remain open to permit uninterrupted water flow in case of valve failure.

IPC Table 604.3 requires 25 psi flow pressure at a urinal flushometer valve, 35 psi at a siphonic water closet flushometer valve and 45 psi at a blowout water closet flushometer valve.

IPC Table 604.3 requires 8 psi flow pressure at most ordinary fixture outlets and 20 psi at balanced-pressure or thermostatic shower and bathtub valves.

IPC 604.9 requires a water hammer arrestor conforming to ASSE 1010 wherever quick-closing valves are used, installed per the manufacturer's instructions.

Last updated: September 2026

Two different pressures

Water Supply items regularly hinge on telling these apart:

Static pressure — pressure with no flow. Governed by IPC 604.8 , capped at 80 psi .

Flow pressure — the residual pressure at the fixture supply outlet while the fixture is flowing at its design rate . Governed by IPC Table 604.3 .

A house can have 78 psi static and still fail Table 604.3 at the top-floor shower, because undersized piping and long developed length eat the pressure once water moves.

Table 604.3 — required capacity at fixture supply outlets

IPC 604.3 : the distribution system must be designed and sized so that under peak demand the capacities at fixture supply outlets are not less than Table 604.3. For fixtures not listed, use the manufacturer's installation instructions .

  • Fixture supply outlet serving Flow rate (gpm) Flow pressure (psi)
  • Lavatory, private 0.8 8
  • Lavatory, public 0.4 8
  • Sink, residential 1.75 8
  • Sink, service 3 8
  • Laundry tray 4 8
  • Dishwasher, residential 2.75 8
  • Drinking fountain 0.75 8
  • Sillcock, hose bibb 5 8
  • Combination fixture 4 8
  • Shower 2.5 8
  • Shower, balanced-pressure / thermostatic valve 2.5 20
  • Bathtub, balanced-pressure / thermostatic valve 4 20
  • Bidet, thermostatic mixing valve 2 20
  • Water closet, tank, close coupled 3 20
  • Water closet, tank, one piece 6 20
  • Water closet, flushometer tank 1.6 20
  • Urinal, valve 12 25
  • Water closet, siphonic, flushometer valve 25 35
  • Water closet, blow out, flushometer valve 25 45

Read the pattern: 8 psi is the ordinary case, 20 psi applies where a mixing or pressure-balancing valve introduces a pressure drop, and 25, 35 and 45 psi belong to flushometer valve devices that need pressure to drive the flush. The blowout water closet at 45 psi is the highest requirement in the table, and the 25 gpm flow rate for flushometer water closets is the highest flow rate.

Footnote b: where the shower mixing valve manufacturer indicates a lower flow rating for the valve, the lower value applies.

Static pressure and the 80 psi ceiling

IPC 604.8 :

Where water pressure within a building exceeds 80 psi static , an approved water pressure-reducing valve conforming to ASSE 1003 or CSA B356 with strainer shall be installed to reduce the pressure in the building water distribution piping to not greater than 80 psi static .

Exception: service lines to sill cocks and outside hydrants , and main supply risers where pressure from the mains is reduced to 80 psi or less at individual fixtures.

Two design requirements follow:

604.8.1 Valve design : the PRV must be designed to remain open to permit uninterrupted water flow in case of valve failure . Fail-open, not fail-closed — a fail-closed regulator would strand a building without water and, worse, without fire-fighting supply.

604.8.2 Repair and removal : PRVs, regulators and strainers must be constructed and installed to permit repair or removal of parts without breaking a pipeline or removing the valve and strainer from the line.

And remember the knock-on effect covered in Chapter 4 of this guide: installing a PRV closes the system , so IPC 607.3 then requires a thermal expansion control device downstream of it.

Inadequate and variable pressure

IPC 604.6 Variable street pressures : where street main pressures fluctuate, the building distribution system shall be designed for the minimum pressure available . You size for the worst case, not the average.

IPC 604.7 Inadequate water pressure : wherever pressure from the street main or other source is insufficient to provide the Table 604.3 flow pressures , a water pressure booster system conforming to Section 606.5 shall be installed.

Water hammer — IPC 604.9

The flow velocity of the water distribution system shall be controlled to reduce the possibility of water hammer. A water-hammer arrestor shall be installed where quick-closing valves are utilized . Water-hammer arrestors shall be installed in accordance with the manufacturer's instructions and shall conform to ASSE 1010 .

Three separate obligations in one paragraph: control velocity , install arrestors at quick-closing valves , and follow the manufacturer for placement .

The physics: water hammer pressure rises with velocity , not with static pressure. A column of water moving at 8 feet per second that is stopped instantly can spike the line by several hundred psi. That is why designers hold distribution velocity near 8 feet per second or less on cold water and lower on hot — and why Table 604.10.1 gives manifold capacities at 4 and 8 feet per second . Quick-closing valves include solenoid valves on clothes washers, dishwashers and ice makers, and flushometer valves.

Arrestors are sealed, engineered devices under ASSE 1010. A capped vertical stub of pipe is not an arrestor; the air charge in an open standpipe dissolves into the water within weeks and the device stops working.

Worked pressure budget

A three-story house sits on a street main whose minimum daily static pressure is 55 psi at the meter. The highest fixture, a balanced-pressure shower valve, is 28 feet above the meter . A water softener in the line costs 8 psi.

Following the Appendix E104.1 method:

Start : 55 psi minimum daily static pressure.

Elevation : deduct 0.5 psi per foot of rise. 28 ft x 0.5 = 14 psi . Remaining: 41 psi.

Special equipment : deduct the softener's manufacturer-published loss of 8 psi . Remaining: 33 psi.

Special fixture allowance : deduct pressure in excess of 8 psi required by the special fixture. The balanced-pressure shower valve needs 20 psi flow pressure, so deduct 20 - 8 = 12 psi . Remaining: 21 psi .

Use 21 psi to select the pressure range column in Table E104.1 — the 30 to 39 psi band does not apply; you are below it, which is a signal the design will need larger pipe, a shorter developed length, or a booster.

That is the honest arithmetic behind IPC 604.7: when the remaining pressure cannot support the Table 604.3 requirement through the piping you can install, a booster system becomes mandatory rather than optional.

Checks an inspector will make

  • Observation Section
  • Static pressure above 80 psi with no PRV 604.8
  • PRV installed with no strainer 604.8
  • PRV installed, no thermal expansion control on the water heater cold supply 607.3
  • Clothes washer box with solenoid valves and no arrestor 604.9
  • Arrestor installed remote from the quick-closing valve, contrary to the manufacturer 604.9
  • Top-floor shower that will not hold 20 psi flow pressure at 2.5 gpm 604.3, Table 604.3