Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Passing the Colorado Journeyworker Plumber Exam
1.1 Exam Blueprint, Format, and the 2024 Code Changeover 1.2 Colorado Licenses, Experience Hours, and Apprentice Supervision 1.3 Permits, Inspections, Blue Tags, and Board Enforcement
2 Chapter 2: General Regulations (IPC Chapter 3)
2.1 Approved Materials, Certification, and General Installation Rules 2.2 Protection of Pipes: Contact, Notching, Shield Plates, and Freezing 2.3 Piping Support, Trenching, Bedding, and Backfill 2.4 Required Tests: Water, Air, and Backflow Assembly Testing
3 Chapter 3: Fixtures and Equipment (IPC Chapter 4)
3.1 Minimum Fixture Counts, Separate Facilities, and Toilet Room Location 3.2 Fixture Clearances, Compartments, and Setting Requirements 3.3 Water Closets, Urinals, Lavatories, Sinks, and Flush Devices 3.4 Showers, Bathtubs, Fixture Fittings, and Scald Protection
4 Chapter 4: Water Heaters (IPC Chapter 5)
4.1 Water Heater Installation, Location, Access, and Clearances 4.2 Relief Valves and Discharge Piping 4.3 Water Heater Pans, Pan Drains, and Storage Tank Requirements 4.4 Thermal Expansion Control and Hot Water Temperature Limits
5 Chapter 5: Water Supply Materials and Installation (IPC Chapter 6)
5.1 Water Service and Distribution Materials, and Sewer Separation 5.2 Joints, Connections, and Dissimilar Materials in Water Piping 5.3 Valves, Shutoffs, and Required Valve Locations
6 Chapter 6: Water Supply Sizing and Pressure (IPC Chapter 6 and Appendix E)
6.1 Pressure Limits, Pressure Reducing Valves, and Water Hammer 6.2 Water Supply Fixture Units and Estimating Demand 6.3 Sizing Water Piping with Appendix E and Table E104.1
7 Chapter 7: Cross-Connection Control and Backflow Prevention (IPC Sections 608-610, Chapter 13)
7.1 Cross-Connection Principles, Backsiphonage, and Backpressure 7.2 Air Gaps and the Backflow Preventer Family 7.3 Applying Backflow Protection to Specific Connections 7.4 Nonpotable Water Systems, Identification, and Reclaimed Water
8 Chapter 8: Sanitary Drainage Materials and Fittings (IPC Chapter 7)
8.1 Sanitary Drainage Materials and Where Each May Be Used 8.2 Drainage Joints, Transitions, and Prohibited Connections 8.3 Fittings for Change of Direction and Drainage Flow Patterns
9 Chapter 9: Sanitary Drainage Sizing (IPC Sections 704, 709-711)
9.1 Drainage Fixture Units and Load Estimation 9.2 Slope of Horizontal Drainage and Installation Rules 9.3 Sizing Building Drains, Building Sewers, and Horizontal Branches 9.4 Stacks, Branch Intervals, and Offsets in Tall Buildings
10 Chapter 10: Cleanouts, Sumps and Below-Sewer Drainage (IPC Sections 708, 712-716)
10.1 Cleanouts, Manholes, and Access Requirements 10.2 Backwater Valves and Fixtures Below the Sewer Level 10.3 Sumps, Sewage Ejectors, and Macerating Toilet Systems 10.4 Building Sewers, Private Disposal, and Special Drainage Conditions
11 Chapter 11: Vent Fundamentals and Terminals (IPC Sections 901-905, 908)
11.1 How Vents Work, Trap Seal Loss, and the One-Inch Rule 11.2 Vent Terminals, Roof Penetrations, and Sidewall Terminations 11.3 Vent Connections, Grade, and the Six-Inch Rules
12 Chapter 12: Vent Types and Sizing (IPC Sections 906-911, 917)
12.1 Individual Vents, Common Vents, and Vents for Stack Offsets 12.2 Trap-to-Vent Distance, Trap Arms, and Fixture Drains 12.3 Sizing Stack Vents, Vent Stacks, Branch Vents, and Headers 12.4 Putting a Vent System Together: A Worked Building
13 Chapter 13: Engineered and Special Venting (IPC Sections 912-916, 918-920)
13.1 Horizontal and Vertical Wet Venting 13.2 Waste Stack Vents, Circuit Vents, and Combination Waste and Vent 13.3 Island Fixture Venting and Air Admittance Valves
14 Chapter 14: Traps, Interceptors and Separators (IPC Chapter 10)
14.1 Fixture Traps, Trap Seals, and Prohibited Trap Types 14.2 Trap Seal Protection, Primers, and Barrier Devices 14.3 Grease Interceptors, Oil Separators, and Solids Interceptors
15 Chapter 15: Indirect and Special Waste (IPC Chapter 8)
15.1 Where Indirect Waste Is Required, and Air Gap Versus Air Break 15.2 Waste Receptors, Hub Drains, and Standpipes 15.3 Special Wastes, Chemical Neutralization, and Health Care Drainage
16 Chapter 16: Storm Drainage (IPC Chapter 11 and Appendix B)
16.1 Storm Drainage Scope, Disposal, and Prohibited Connections 16.2 Storm Drainage Materials, Roof Drains, and Conductors 16.3 Secondary Roof Drains, Scuppers, and Controlled Flow Systems 16.4 Rainfall Rates, Roof Area, and the Flow-Rate Conversion 16.5 Sizing Vertical Conductors, Leaders, and Storm Drains 16.6 Gutters, Subsoil Drains, Building Subdrains, and Storm Sumps
17 Chapter 17: Residential Fire Sprinklers (IRC Section P2904)
17.1 Residential Fire Sprinkler Systems (IRC Section P2904)
18 Chapter 18: Isometric Analysis and Plumbing Calculations
18.1 Reading Plumbing Isometrics and Riser Diagrams 18.2 Analyzing a DWV Isometric for Code Compliance 18.3 Offsets, Travel, and the Plumbing Math the Exam Assumes
6.3 Sizing Water Piping with Appendix E and Table E104.1
Key Takeaways Explain This Topic AI
IPC E104.1 requires the minimum water service pipe to be 3/4 inch, matching the floor in IPC 603.1.
IPC E104.1 step 3 multiplies the actual developed length from the source to the most remote fixture by a factor of 1.2 to compensate for fitting losses.
IPC E104.1 step 2.2 sets available pressure behind a pressure reducing valve at 80 percent of the minimum daily static pressure at the source, or the set pressure downstream, whichever is smaller.
IPC E104.1 step 2.4 deducts the pressure in excess of 8 psi required by special fixtures such as temperature-controlled showers and flushometer tank water closets.
IPC Table E104.1 is organized into four pressure ranges: 30 to 39 psi, 40 to 49 psi, 50 to 60 psi, and over 60 psi.
Last updated: September 2026
Two legitimate sizing methods
IPC Appendix E offers two paths, and the code official approves the method (IPC 604.1):
Table E104.1 — a lookup table that converts pressure range, developed length and fixture-unit load directly into meter, service and distribution pipe sizes. This is the method exam items use.
Segmented loss method (E103.3) — the engineered approach: compute available pressure, subtract losses segment by segment through friction charts, meter loss tables (E103.3(4)) and equivalent-length-of-fitting tables, and confirm velocity limits.
Reading Table E104.1
The table is built around three axes:
Row group = one of four pressure ranges : 30 to 39 psi, 40 to 49 psi, 50 to 60 psi, and over 60 psi .
Row = a pairing of meter and service pipe size with a distribution pipe size .
Column = the maximum developed length : 40, 60, 80, 100, 150, 200, 250, 300, 400 or 500 feet.
The cell value is the maximum water supply fixture unit load that combination can carry.
An extract from the 50 to 60 psi range shows the shape of the data:
- Meter / service Distribution pipe 40 ft 100 ft 200 ft 300 ft 500 ft
- 3/4 1/2 3 2 1 1 0.5
- 3/4 3/4 9.5 8.5 5 4 2.5
- 3/4 1 32 32 18.5 12 8
- 1 1 32 32 22 13 8
- 1 1-1/4 80 80 68 48 28
- 1 1-1/2 87 87 87 87 70
- 1-1/2 1-1/2 151 151 151 120 79
- 1-1/2 2 275 275 275 275 213
- 2 2 365 365 365 329 232
Two things to notice:
Developed length punishes capacity hard. A 3/4-inch meter with 1-inch distribution carries 32 wsfu at 40 feet but only 8 wsfu at 500 feet — a 75 percent loss of capacity.
Higher pressure buys capacity. The same 3/4-inch meter with 1-inch distribution at 200 feet carries 9 wsfu in the 30-to-39 psi range, 13.5 in the 40-to-49 range, 18.5 in the 50-to-60 range and 24 in the over-60 range.
Footnote a : the minimum size for building supply is 3/4-inch pipe , so the 1/2-inch distribution rows apply to distribution only, never to the service.
The pressure adjustments, restated
Step 2 of E104.1 is where most sizing errors occur. Apply all four adjustments in order:
Adjustment Rule
2.1 Elevation Deduct 0.5 psi per foot where the highest outlet is above the source; add 0.5 psi per foot where it is below
2.2 Pressure reducing valve Available pressure becomes 80 percent of the minimum daily static pressure at the source , or the PRV set pressure , whichever is smaller
2.3 Special equipment Deduct all losses for backflow preventers, filters and softeners, using manufacturer data
2.4 Special fixtures Deduct the pressure in excess of 8 psi required by a special fixture such as a temperature-controlled shower or a flushometer tank water closet
Then read the resulting pressure against the four pressure range groups.
Step 3: maximum developed length is the actual pipe length from the source to the most remote fixture — including either the hot branch through the water heater or the cold branch — multiplied by 1.2 . That 1.2 multiplier is the code's blanket allowance for fitting losses in the table method.
Full worked example
Building: a single-family house with two full private bathroom groups (flush tank), one kitchen sink, one dishwasher, one clothes washer, two hose bibbs, one laundry tray.
Step 1 — supply load (combined column, Table E103.3(2)):
- Fixture Each Count Subtotal
- Private bathroom group, flush tank 3.6 2 7.2
- Kitchen sink, private 1.4 1 1.4
- Dishwashing machine, private 1.4 1 1.4
- Washing machine (8 lb), private 1.4 1 1.4
- Laundry tray, private 1.4 1 1.4
- Total 12.8 wsfu
The two hose bibbs are not listed in Table E103.3(2); footnote a directs you to assume a load by comparing to a listed fixture using water in similar quantities at similar rates. A laundry tray at 1.4 wsfu is the closest listed analogue, so add 2 x 1.4 = 2.8, giving a design load of 15.6 wsfu .
Step 2 — pressure. Minimum daily static pressure at the meter is 58 psi . The highest outlet is 18 feet above the meter, so deduct 18 x 0.5 = 9 psi , leaving 49 psi. No PRV, no softener, and the shower uses a balanced-pressure valve requiring 20 psi , so deduct 20 - 8 = 12 psi . Available pressure: 37 psi -> use the 30 to 39 psi range.
Step 3 — developed length. Actual run from the meter to the most remote fixture (an upstairs shower, routed through the water heater) is 105 feet . 105 x 1.2 = 126 feet -> use the 150-foot column, the next tabulated value at or above 126.
Step 4 — service, meter and main distribution. In the 30-to-39 psi range, 150-foot column, look for a value equal to or greater than 15.6 wsfu :
3/4 meter / 3/4 distribution: 4 wsfu — too small.
3/4 meter / 1-inch distribution: 11 wsfu — too small.
1-inch meter / 1-inch distribution: 13.5 wsfu — still too small.
3/4 meter / 1-1/4-inch distribution: 30 wsfu — sufficient.
So a 3/4-inch meter and service with a 1-1/4-inch main distribution pipe carries the load. Selecting a 1-inch meter with 1-1/4-inch distribution would give 45 wsfu, a larger margin at a higher meter cost.
Step 5 — individual branches. Work back from the most remote outlet on each branch, accumulating hot or cold column values, and read each segment's size from the same pressure range and developed-length column. No branch needs to exceed the 1-1/4-inch main established in step 4.
Velocity as a second constraint
Table E104.1 addresses pressure, not velocity. Velocity control is a separate obligation under IPC 604.9 ("the flow velocity of the water distribution system shall be controlled to reduce the possibility of water hammer"). Practical design velocities:
- Service Typical maximum velocity
- Cold water distribution 8 feet per second
- Hot water distribution 5 feet per second
- Recirculating hot water return 2 to 3 feet per second
Table 604.10.1 encodes the same idea for manifolds, publishing capacity at both 4 and 8 feet per second . Copper erodes rapidly above about 8 fps in cold water and about 5 fps in hot; the lower hot-water limit exists because higher temperature accelerates erosion-corrosion.
- Sanity checks that catch sizing errors
- Is the service at least 3/4 inch? (603.1, E104.1 footnote a.)
Did you multiply developed length by 1.2? Forgetting it undersizes the system by roughly one column.
Did you use the combined column for the service and the hot or cold column for branches? Mixing them oversizes branches.
Did you deduct elevation before choosing a pressure range? A 30-foot rise is 15 psi and will usually move you down a whole range.
Is a PRV present? If so, available pressure is the smaller of 80 percent of source static pressure or the set pressure — not the set pressure automatically.
Does any branch exceed the main? Step 5 says it never needs to.