6.2 Water Supply Fixture Units and Estimating Demand

Colorado Journeyworker Plumber Journeyman Plumber

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Passing the Colorado Journeyworker Plumber Exam

1.1 Exam Blueprint, Format, and the 2024 Code Changeover 1.2 Colorado Licenses, Experience Hours, and Apprentice Supervision 1.3 Permits, Inspections, Blue Tags, and Board Enforcement

2 Chapter 2: General Regulations (IPC Chapter 3)

2.1 Approved Materials, Certification, and General Installation Rules 2.2 Protection of Pipes: Contact, Notching, Shield Plates, and Freezing 2.3 Piping Support, Trenching, Bedding, and Backfill 2.4 Required Tests: Water, Air, and Backflow Assembly Testing

3 Chapter 3: Fixtures and Equipment (IPC Chapter 4)

3.1 Minimum Fixture Counts, Separate Facilities, and Toilet Room Location 3.2 Fixture Clearances, Compartments, and Setting Requirements 3.3 Water Closets, Urinals, Lavatories, Sinks, and Flush Devices 3.4 Showers, Bathtubs, Fixture Fittings, and Scald Protection

4 Chapter 4: Water Heaters (IPC Chapter 5)

4.1 Water Heater Installation, Location, Access, and Clearances 4.2 Relief Valves and Discharge Piping 4.3 Water Heater Pans, Pan Drains, and Storage Tank Requirements 4.4 Thermal Expansion Control and Hot Water Temperature Limits

5 Chapter 5: Water Supply Materials and Installation (IPC Chapter 6)

5.1 Water Service and Distribution Materials, and Sewer Separation 5.2 Joints, Connections, and Dissimilar Materials in Water Piping 5.3 Valves, Shutoffs, and Required Valve Locations

6 Chapter 6: Water Supply Sizing and Pressure (IPC Chapter 6 and Appendix E)

6.1 Pressure Limits, Pressure Reducing Valves, and Water Hammer 6.2 Water Supply Fixture Units and Estimating Demand 6.3 Sizing Water Piping with Appendix E and Table E104.1

7 Chapter 7: Cross-Connection Control and Backflow Prevention (IPC Sections 608-610, Chapter 13)

7.1 Cross-Connection Principles, Backsiphonage, and Backpressure 7.2 Air Gaps and the Backflow Preventer Family 7.3 Applying Backflow Protection to Specific Connections 7.4 Nonpotable Water Systems, Identification, and Reclaimed Water

8 Chapter 8: Sanitary Drainage Materials and Fittings (IPC Chapter 7)

8.1 Sanitary Drainage Materials and Where Each May Be Used 8.2 Drainage Joints, Transitions, and Prohibited Connections 8.3 Fittings for Change of Direction and Drainage Flow Patterns

9 Chapter 9: Sanitary Drainage Sizing (IPC Sections 704, 709-711)

9.1 Drainage Fixture Units and Load Estimation 9.2 Slope of Horizontal Drainage and Installation Rules 9.3 Sizing Building Drains, Building Sewers, and Horizontal Branches 9.4 Stacks, Branch Intervals, and Offsets in Tall Buildings

10 Chapter 10: Cleanouts, Sumps and Below-Sewer Drainage (IPC Sections 708, 712-716)

10.1 Cleanouts, Manholes, and Access Requirements 10.2 Backwater Valves and Fixtures Below the Sewer Level 10.3 Sumps, Sewage Ejectors, and Macerating Toilet Systems 10.4 Building Sewers, Private Disposal, and Special Drainage Conditions

11 Chapter 11: Vent Fundamentals and Terminals (IPC Sections 901-905, 908)

11.1 How Vents Work, Trap Seal Loss, and the One-Inch Rule 11.2 Vent Terminals, Roof Penetrations, and Sidewall Terminations 11.3 Vent Connections, Grade, and the Six-Inch Rules

12 Chapter 12: Vent Types and Sizing (IPC Sections 906-911, 917)

12.1 Individual Vents, Common Vents, and Vents for Stack Offsets 12.2 Trap-to-Vent Distance, Trap Arms, and Fixture Drains 12.3 Sizing Stack Vents, Vent Stacks, Branch Vents, and Headers 12.4 Putting a Vent System Together: A Worked Building

13 Chapter 13: Engineered and Special Venting (IPC Sections 912-916, 918-920)

13.1 Horizontal and Vertical Wet Venting 13.2 Waste Stack Vents, Circuit Vents, and Combination Waste and Vent 13.3 Island Fixture Venting and Air Admittance Valves

14 Chapter 14: Traps, Interceptors and Separators (IPC Chapter 10)

14.1 Fixture Traps, Trap Seals, and Prohibited Trap Types 14.2 Trap Seal Protection, Primers, and Barrier Devices 14.3 Grease Interceptors, Oil Separators, and Solids Interceptors

15 Chapter 15: Indirect and Special Waste (IPC Chapter 8)

15.1 Where Indirect Waste Is Required, and Air Gap Versus Air Break 15.2 Waste Receptors, Hub Drains, and Standpipes 15.3 Special Wastes, Chemical Neutralization, and Health Care Drainage

16 Chapter 16: Storm Drainage (IPC Chapter 11 and Appendix B)

16.1 Storm Drainage Scope, Disposal, and Prohibited Connections 16.2 Storm Drainage Materials, Roof Drains, and Conductors 16.3 Secondary Roof Drains, Scuppers, and Controlled Flow Systems 16.4 Rainfall Rates, Roof Area, and the Flow-Rate Conversion 16.5 Sizing Vertical Conductors, Leaders, and Storm Drains 16.6 Gutters, Subsoil Drains, Building Subdrains, and Storm Sumps

17 Chapter 17: Residential Fire Sprinklers (IRC Section P2904)

17.1 Residential Fire Sprinkler Systems (IRC Section P2904)

18 Chapter 18: Isometric Analysis and Plumbing Calculations

18.1 Reading Plumbing Isometrics and Riser Diagrams 18.2 Analyzing a DWV Isometric for Code Compliance 18.3 Offsets, Travel, and the Plumbing Math the Exam Assumes

6.2 Water Supply Fixture Units and Estimating Demand

Key Takeaways Explain This Topic AI

IPC Table E103.3(2) assigns a private bathroom group 3.6 water supply fixture units with a flush tank and 8.0 with a flushometer valve.

IPC Table E103.3(2) assigns a public water closet 5.0 wsfu with a flush tank and 10.0 wsfu with a flushometer valve.

Table E103.3(2) footnote a states that separate hot and cold water loads are each three-fourths of the total load for the fixture.

IPC Table E103.3(3) converts 10 wsfu to 14.6 gpm in a flush tank system but 27.0 gpm in a flushometer valve system.

IPC E104.1 requires supply load to be determined in water supply fixture units from Table E103.3(2), with unlisted fixtures assigned the value of a fixture with similar flow characteristics.

Last updated: September 2026

Why fixture units exist

No building ever runs every fixture at once. If you sized a 30-unit apartment building's water service for the simultaneous full flow of every fixture, you would install a main three times larger than anything the building will ever use.

The water supply fixture unit (wsfu) is a weighted probability index. Each fixture gets a load value reflecting how much water it uses, how fast, and how often. Add the load values, then convert the total to gallons per minute through a demand curve that flattens sharply as the count rises — the Hunter curve , tabulated in Table E103.3(3) .

Do not confuse wsfu with drainage fixture units (dfu) from IPC Table 709.1. They are different systems with different numbers for the same fixture. A private lavatory is 0.7 wsfu on the supply side and 1 dfu on the drainage side.

Table E103.3(2) — load values assigned to fixtures

  • Fixture Occupancy Supply control Cold Hot Total
  • Bathroom group Private Flush tank 2.7 1.5 3.6
  • Bathroom group Private Flushometer valve 6.0 3.0 8.0
  • Water closet Private Flush tank 2.2 — 2.2
  • Water closet Private Flushometer valve 6.0 — 6.0
  • Water closet Public Flush tank 5.0 — 5.0
  • Water closet Public Flushometer valve 10.0 — 10.0
  • Water closet Public or private Flushometer tank 2.0 — 2.0
  • Urinal Public 1-inch flushometer valve 10.0 — 10.0
  • Urinal Public 3/4-inch flushometer valve 5.0 — 5.0
  • Urinal Public Flush tank 3.0 — 3.0
  • Lavatory Private Faucet 0.5 0.5 0.7
  • Lavatory Public Faucet 1.5 1.5 2.0
  • Bathtub Private Faucet 1.0 1.0 1.4
  • Bathtub Public Faucet 3.0 3.0 4.0
  • Shower head Private Mixing valve 1.0 1.0 1.4
  • Shower head Public Mixing valve 3.0 3.0 4.0
  • Kitchen sink Private Faucet 1.0 1.0 1.4
  • Kitchen sink Hotel, restaurant Faucet 3.0 3.0 4.0
  • Service sink Offices, etc. Faucet 2.25 2.25 3.0
  • Laundry trays (1 to 3) Private Faucet 1.0 1.0 1.4
  • Dishwashing machine Private Automatic — 1.4 1.4
  • Washing machine (8 lb) Private Automatic 1.0 1.0 1.4
  • Washing machine (8 lb) Public Automatic 2.25 2.25 3.0
  • Washing machine (15 lb) Public Automatic 3.0 3.0 4.0
  • Bidet Private Faucet 1.5 1.5 2.0
  • Combination fixture Private Faucet 2.25 2.25 3.0
  • Drinking fountain Offices, etc. 3/8-inch valve 0.25 — 0.25

Footnote a carries two rules worth memorizing:

For fixtures not listed , assume loads by comparing to a listed fixture using water in similar quantities at similar rates.

The separate hot and cold water loads are each three-fourths of the total load for the fixture. Check it: a private lavatory is 0.7 total and 0.5 each side; 0.75 x 0.7 = 0.525, rounded to 0.5. A private bathtub is 1.4 total and 1.0 each side; 0.75 x 1.4 = 1.05.

The hot-plus-cold sum therefore exceeds the total (0.5 + 0.5 = 1.0 versus a total of 0.7), because hot and cold are rarely drawn at full rate simultaneously.

The bathroom group shortcut

A "bathroom group" bundles a water closet, a lavatory and a bathtub or shower into a single value. A private bathroom group with a flush tank water closet is 3.6 wsfu . Adding the same three fixtures individually would give 2.2 + 0.7 + 1.4 = 4.3 wsfu. The grouped value is lower because the code recognizes that one person uses one bathroom at a time.

Note the enormous jump for flushometer valves : the same private bathroom group goes from 3.6 to 8.0 wsfu . A public water closet goes from 5.0 to 10.0 . That reflects the instantaneous 25 gpm draw of a flushometer valve.

Table E103.3(3) — converting load to demand

The table has two separate sets of columns : systems predominantly for flush tanks and systems predominantly for flushometer valves .

  • Load (wsfu) Demand, flush tank (gpm) Demand, flushometer valve (gpm)
  • 5 9.4 15.0
  • 10 14.6 27.0
  • 15 17.5 31.0
  • 20 19.6 35.0
  • 30 23.3 42.0
  • 50 29.1 50.0
  • 100 43.5 67.5
  • 200 65.0 90.0
  • 500 124.0 143.0
  • 1,000 208.0 208.0

Three lessons from these numbers:

Demand is strongly nonlinear. Going from 10 to 100 wsfu — a tenfold increase in fixtures — raises flush-tank demand only from 14.6 to 43.5 gpm, a threefold increase.

Flushometer systems demand much more at low counts. At 10 wsfu, flushometer demand is nearly double flush-tank demand.

The two curves converge. At 1,000 wsfu both read 208 gpm , because with enough fixtures the statistics dominate the device type. The flushometer column does not even begin until 5 wsfu .

Worked example: a 12-unit apartment building

Each unit has one private bathroom group (flush tank), one kitchen sink and one clothes washer. The building also has a shared laundry with two 15-pound public washing machines and one service sink.

Total (combined) load:

  • Item Each Count Subtotal
  • Private bathroom group, flush tank 3.6 12 43.2
  • Kitchen sink, private 1.4 12 16.8
  • Washing machine (8 lb), private 1.4 12 16.8
  • Washing machine (15 lb), public 4.0 2 8.0
  • Service sink 3.0 1 3.0
  • Total 87.8 wsfu

Demand : this is a flush-tank building, so read the flush tank column. 80 wsfu gives 38.0 gpm and 90 wsfu gives 41.0 gpm. Interpolating at 87.8 wsfu gives roughly 40.3 gpm ; sizing conservatively at the next tabulated value, use 41 gpm .

Hot water side : use the hot column of Table E103.3(2) for the hot branch. Bathroom group hot is 1.5 each, kitchen sink hot 1.0, private washer hot 1.0, public washer hot 3.0, service sink hot 2.25:

(12 x 1.5) + (12 x 1.0) + (12 x 1.0) + (2 x 3.0) + 2.25 = 18 + 12 + 12 + 6 + 2.25 = 50.25 wsfu hot , which reads about 29 gpm from the flush tank column.

The five-step E104.1 procedure

Supply load in wsfu from Table E103.3(2), using the combined column for the service and main distribution pipe.

Minimum daily static service pressure from the local water authority, adjusted for:

0.5 psi deducted per foot the highest outlet is above the source (added per foot below);

where a PRV is installed, the available pressure is 80 percent of the minimum daily static pressure at the source, or the PRV set pressure, whichever is smaller ;

deduct all pressure losses from special equipment (backflow preventer, filter, softener) per the manufacturer;

deduct pressure in excess of 8 psi required by special fixtures such as a temperature-controlled shower or a flushometer tank water closet.

Maximum developed length = actual pipe length from the source to the most remote fixture, including hot (through the water heater) or cold branches, multiplied by 1.2 to account for fittings.

Read the service, meter and main distribution size from Table E104.1 at the intersection of the pressure range, developed length column and total demand.

Size each distribution pipe by working back from the most remote outlet on each branch, accumulating the related hot or cold column values. No branch or main needs to be larger than the main distribution pipe established in step 4.

Loading diagram... Fixture units to demand to pipe size