6.7 Tertiary Filtration, Effluent Polishing & Wastewater Disinfection with Chlorine, Dechlorination and UV

Colorado Water/Wastewater Operator Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: State Laws, Regulations & CCWP Certification

1.1 CDPHE CCWP Program & Regulatory Framework (Regulation 100 / 5 CCR 1003-2) 1.2 Facility Classification & Operator in Responsible Charge (ORC) Requirements 1.3 Certification Levels, Education, Experience & Exam Eligibility (Class D-A, Grade 1-4, Class S/T) 1.4 License Renewal, Training Units (TUs) & Mandatory Regulatory Training 1.5 Colorado Primary Drinking Water Regulations (Regulation 11) & Compliance 1.6 Colorado Discharge Permit System (Regulations 61/62), DMRs & Biosolids Reporting

2 Chapter 2: Source Water & Drinking Water Treatment Processes

2.1 Raw Water Sources, High-Altitude Characteristics & Reservoir Quality 2.2 Coagulation Chemistry, Rapid Mixing & Chemical Dosing (Alum, Ferric, Polymers) 2.3 Flocculation & Sedimentation Basin Design, Operation & Settling Zones 2.4 Granular Media Filtration, Backwash Procedures & Turbidity Standards 2.5 Advanced Treatment: Membranes, Softening, GAC/PAC Adsorption & Aeration 2.6 Groundwater Sources, Well Hydraulics, Static and Pumping Levels & Specific Capacity 2.7 Source Water Characteristics, Contaminant Categories & Watershed Protection Plans 2.8 Pretreatment: Presedimentation, Aeration, Algae Control & Taste-and-Odor Management 2.9 Direct, In-Line, Pressure, Cartridge & Diatomaceous Earth Filtration 2.10 Lime-Soda Softening, Ion Exchange & Water Stabilization 2.11 Water Treatment Plant Residuals: Lagoons, Drying Beds, Land Application & Recycle

3 Chapter 3: Disinfection & Chemical Addition

3.1 Chlorine Chemistry: Hypochlorous Acid, Free/Combined Residual & Breakpoint Chlorination 3.2 Disinfection Kinetics, Baffle Factors, T10 & CT Compliance Calculations 3.3 Disinfection Byproducts (TTHMs, HAA5s) & Stage 1/2 DBP Rules 3.4 Alternative Disinfection: Chloramination, Ultraviolet (UV) Light & Chlorine Dioxide 3.5 Corrosion Control, Lead & Copper Rule Revisions (LCRR) & Fluoridation Practices

4 Chapter 4: Water Treatment Plant Equipment, Instrumentation & Maintenance

4.1 Raw Water Intakes, Screening Equipment & Raw Water Pumping 4.2 Chemical Feed Equipment: Feeders, Day Tanks, Carrier Water & Feed-Rate Calibration 4.3 Chlorination Equipment: Gas Systems, Vacuum Regulators, Hypochlorite Storage & Onsite Generation 4.4 Filter Underdrains, Support Gravel, Surface Wash, Air Scour & Filter-to-Waste 4.5 Plant Process Control, SCADA and PLC Systems, Alarm Management & Records of Operation 4.6 Preventive, Corrective and Predictive Maintenance, Work Orders & Asset Management

5 Chapter 5: Wastewater Treatment Principles & Biological Processes

5.1 Preliminary Treatment: Bar Screens, Shredders, Grit Chambers & Flow Equalization 5.2 Primary Clarification, Solids Separation & Scum Removal Mechanics 5.3 Activated Sludge Fundamentals: Aerobic Microbiology, DO Control & Biomass Growth 5.4 Return & Waste Activated Sludge Management (RAS/WAS Operations & Sludge Age) 5.5 Activated Sludge Troubleshooting: Bulking, Nocardia Foaming, Rising Sludge & Pin Floc 5.6 Wastewater Characteristics, Organic and Hydraulic Loading, Diurnal Flow & Septicity 5.7 Activated Sludge Arrangements: Conventional, Complete Mix, Step Feed, Contact Stabilization, Extended Aeration, Oxidation Ditch, SBR & MBR 5.8 Aeration Systems: Blowers, Diffusers, Surface Aerators, Oxygen Transfer & Altitude Effects

6 Chapter 6: Advanced Wastewater Treatment & Solids Management

6.1 Biological Nutrient Removal: Nitrification, Denitrification & Anoxic Zones 6.2 Biological & Chemical Phosphorus Removal (EBPR & Coagulant Precipitation) 6.3 Sludge Thickening, Aerobic & Anaerobic Digestion (Mesophilic/Thermophilic) 6.4 Dewatering Equipment (Centrifuges, Belt Filter Presses) & Biosolids Standards (Reg 64) 6.5 Pond & Lagoon Operations, Trickling Filters & Rotating Biological Contactors (RBCs) 6.6 Secondary Clarification: Overflow and Solids Loading Rates, RAS Rate Setting & Clarifier Diagnostics 6.7 Tertiary Filtration, Effluent Polishing & Wastewater Disinfection with Chlorine, Dechlorination and UV 6.8 Effluent Disposal, Rapid Infiltration Basins, Colorado Water Reuse Law & Regulation 84

7 Chapter 7: Water Distribution Systems

7.1 Distribution Hydraulics, Pressure Zones, Static Head & Friction Headloss 7.2 Finished Water Storage Tanks, Standpipes, Mixing & Water Age Control 7.3 Distribution Piping, Valves (Gate, Butterfly, PRV), Hydrants & Main Flushing 7.4 Cross-Connection Control, Hazard Assessment & Backflow Preventers (RPZ, DCVA, PVB, Air Gap) 7.5 Water Main Installation, Trenching, Repair, Pressure Testing & Disinfection (AWWA C651) 7.6 Network Layout, Pressure Zones, Demand Patterns, Fire Flow & the Hydraulic Grade Line 7.7 Fire Hydrants, Dry Barrel Operation, Fire Flow Testing & Unidirectional Flushing 7.8 Booster Pump Stations, Hydropneumatic Systems, Controls & Surge Protection 7.9 Customer and Master Metering, Meter Sizing, Accuracy Testing, AMR & AMI 7.10 System Mapping, GIS, As-Builts, Operational Analysis & the AWWA Water Audit 7.11 Service Line Installation, Wet Tapping, Curb Stops & the Lead Service Line Inventory 7.12 Leak Detection, District Metered Areas, Minimum Night Flow & Pressure Management 7.13 Storage Facility Inspection, Sanitary Defects, Water Age Control, Cleaning & AWWA C652 Disinfection 7.14 Utility Locating, Colorado 811 Damage Prevention, the APWA Color Code & New Construction Inspection 7.15 Well and Wellhead Maintenance, Sanitary Condition, Rehabilitation & AWWA C654 Disinfection 7.16 Booster Chlorination, Remote Chemical Feed, Chemical Storage, Security & Supply Management 7.17 Distribution Sampling Technique, Chlorine Residual Monitoring & Nitrification Control in Chloraminated Systems

8 Chapter 8: Wastewater Collection Systems

8.1 Gravity Collection Systems: Flow Velocities, Slopes, Pipe Materials & Manholes 8.2 Wastewater Lift Stations: Wet Wells, Submersible Pumps, Level Controls & Force Mains 8.3 Inflow and Infiltration (I&I) Sources, Flow Monitoring, Smoke Testing & CCTV Inspection 8.4 Collection Maintenance: Hydraulic Jetting, Mechanical Rodding & FOG/Root Mitigation 8.5 Sanitary Sewer Overflows (SSOs): Root Causes, Containment, Reporting & Mitigation 8.6 Lift Station Electrical Devices, Level Detection, Telemetry, Gas Detection & Capacity Adjustment 8.7 Lift Station Configurations, Preventive Maintenance, Wet Well Cleaning, Troubleshooting & Emergency Bypass Pumping 8.8 Collection System Rehabilitation: CIPP, Pipe Bursting, Sliplining, Grouting, Manhole Repair & Tap Defects 8.9 Excavation, Hydro Excavation, Bedding and Haunching, Grade Control & Sewer Acceptance Testing 8.10 Collection System Flow Monitoring, Area-Velocity Metering, Weirs and Flumes & Capacity Assessment

9 Chapter 9: Pumps, Motors & Utility Mechanics

9.1 Centrifugal Pumps: Volutes, Impellers, Packing Seals & Mechanical Seals 9.2 Positive Displacement Pumps (Peristaltic, Diaphragm, Progressive Cavity) & Dosing Systems 9.3 Pump Performance Curves, System Head Curves, Cavitation & NPSH Calculations 9.4 Electric Motors (Single/Three Phase), Controls, Variable Frequency Drives (VFDs) & Power 9.5 Flow Meters (Venturi, Magnetic, Ultrasonic), Online Analyzers, PLCs & SCADA Telemetry 9.6 Air Compressors, Conveyors, Hoists and Cranes, Service Piping & Standby Power Generation 9.7 Valve Types and Duties, Air Release and Air-Vacuum Valves, Water Hammer & Surge Control

10 Chapter 10: Laboratory Analysis & Water Quality Monitoring

10.1 Regulatory Sampling Procedures, Chain of Custody, Holding Times & Preservation Techniques 10.2 Physical & Chemical Drinking Water Testing: Turbidity, pH, Alkalinity, Hardness & Chlorine (DPD) 10.3 Wastewater Laboratory Analysis: BOD5, COD, Total Suspended Solids (TSS) & Settleometry 10.4 Microbiological Testing: Total Coliform, E. coli (Colilert, Membrane Filtration) & QA/QC 10.5 Bench-Scale Jar Testing, Coagulant Optimization & Streaming Current Monitoring 10.6 Laboratory Equipment, Calibration and Verification, QA/QC Program & Certified Laboratory Requirements 10.7 Nutrient Series, Metals Sampling, Whole Effluent Toxicity & Electrode Measurements (DO, pH, ORP, H2S)

11 Chapter 11: Operator Mathematics & Applied Calculations

11.1 Core Conversions, Geometric Area, Pipe Volume & Continuous Flow Rate (MGD, GPM, cfs) 11.2 Chemical Dosage, The Standard "Pounds Formula", Active Chemical & Solution Purity 11.3 Hydraulic Retention Time (HRT), Surface Overflow Rate (SOR) & Weir Overflow Rates 11.4 Process Control Calculations: F/M Ratio, MCRT/Solids Retention Time (SRT) & Sludge Volume Index (SVI) 11.5 Distribution Pressure, Static vs Dynamic Head, Water Horsepower & Wire-to-Water Efficiency 11.6 CT Calculations: Baffling Factors, T10, Temperature and pH Corrections & Multi-Segment Compliance

12 Chapter 12: Safety, Emergency Operations & Compliance

12.1 Permit-Required Confined Space (PRCS) Entry, Atmospheric Testing (O2/LEL/H2S/CO) & Rescue 12.2 Control of Hazardous Energy: Lockout/Tagout (LOTO), Arc Flash & Electrical Safety 12.3 Chemical Safety: Chlorine Gas Handling, Ton Cylinders, Sulfur Dioxide, Ammonia & SDS/GHS 12.4 Trenching & Excavation: Soil Classification, Sloping, Shoring, Shielding & Competent Person Rules 12.5 Emergency Action Plans, Security Vulnerability, Spill Containment & CDPHE Tier 1/2/3 Public Notice 12.6 Work Zone Traffic Control, PPE, Fall Protection, Fire Extinguishers, First Aid & Bloodborne Pathogens 12.7 Standard Operating Procedures, Operating Records, Regulatory Reporting, Customer Complaints & Supervisory Duties

6.7 Tertiary Filtration, Effluent Polishing & Wastewater Disinfection with Chlorine, Dechlorination and UV

Key Takeaways Explain This Topic AI

Tertiary filtration reduces effluent TSS from 10 to 30 mg/L down to 5 mg/L or less, and because much residual BOD and phosphorus is particulate, it lowers those parameters at the same time.

A tertiary filter is a polishing device, so it blinds rapidly when secondary effluent TSS exceeds roughly 30 mg/L and cannot rescue a failing secondary process.

Filter backwash and reject streams are concentrated and must be equalized and returned to the plant head at a controlled rate rather than as a slug.

Ammonia in a non-nitrifying effluent converts applied chlorine to combined chlorine, so wastewater disinfection requires far higher doses and contact times than drinking water.

Ultraviolet dose is intensity multiplied by exposure time, is governed by UV transmittance, and quartz sleeve fouling is the most common cause of underperformance.

Last updated: August 2026

Polishing what the clarifier could not remove

WPI's outline lists tertiary treatment equipment: filtration, media filtration (sand, anthracite, disc filter) and tertiary treatment processes: filtration processes, media filtration . Tertiary filtration is added when a permit requires effluent TSS below what secondary clarification reliably achieves, when phosphorus limits require capture of chemical precipitate, when UV disinfection needs low turbidity to work, or when the effluent will be reused.

What tertiary filtration achieves

A well-operated secondary clarifier delivers roughly 10 to 30 mg/L TSS. Tertiary filtration takes that to 5 mg/L or below , and often to 2 to 3 mg/L. Because much of the residual BOD in a secondary effluent is particulate — it is the solids themselves — removing solids also removes BOD, typically bringing 15 to 25 mg/L down to under 5 mg/L. Filtration also removes the particulate fraction of phosphorus , which is why plants with total phosphorus limits below about 0.5 mg/L almost always need it.

Critically, filtration improves UV transmittance by removing the particles that shield organisms and scatter light. A UV system downstream of an unfiltered effluent must be sized for far more dose than one downstream of a filter.

Technologies

Technology Description Typical loading

Deep bed granular media Mono- or dual-media (sand, anthracite) 3 to 6 ft deep, gravity or pressure 2 to 5 gpm/sq ft

Shallow bed / traveling bridge Sand bed with a bridge that backwashes one cell at a time while others stay in service 2 to 4 gpm/sq ft

Continuous backwash (upflow sand) Sand moves downward against upflow water; an airlift continuously cleans and returns it 3 to 6 gpm/sq ft

Cloth media disc filter Rotating discs covered in pile cloth; solids captured on the outside, backwashed by suction shoe 4 to 8 gpm/sq ft

Membrane filtration (MF/UF) 0.02 to 0.1 micron barrier Flux based

Cloth media disc filters have become the default retrofit for existing plants because they need very little head, occupy a small footprint, backwash with only 1 to 3 percent of throughput, and have no media to lose. The pile cloth is inspected for wear and cleaned chemically on a schedule; solids that mat into the cloth cause rising differential and reduced capacity.

Continuous backwash upflow sand filters never come offline. Water enters at the bottom and flows upward through a downward-moving sand bed; an airlift in the center draws dirty sand up, washes it in a reject weir, and drops it back on top. There is no backwash cycle to sequence, but the reject stream runs continuously at about 5 percent of feed and must be returned to the head of the plant.

Deep bed media filters in tertiary service work exactly like drinking water filters and share the same failure modes: mudballs, gravel upset, air binding, and breakthrough. The difference is loading, since secondary effluent carries a lighter, more biological floc.

Operating essentials

Backwash return. Every filter backwash stream goes back to the head of the plant, and it is concentrated. Returning it as a slug upsets primary clarification and aeration. Backwash is equalized and returned at a controlled, steady rate , ideally during low-flow hours.

Chemical addition. A small dose of coagulant or filter-aid polymer ahead of the filter dramatically improves removal of fine, non-settleable particles and is essential when chemical phosphorus precipitate must be captured.

Biological growth. Secondary effluent still contains nutrients and organics, so filters grow biofilm. Periodic chlorination of the filter or a hypochlorite soak controls it, and unaddressed growth blinds the media and creates odor.

Solids loading limits. Tertiary filters are polishing devices, not clarifiers. If secondary effluent TSS rises above roughly 30 mg/L, the filter blinds rapidly and backwash frequency becomes unmanageable. A tertiary filter cannot rescue a failing secondary process , which is the most important operating fact about it.

Wastewater disinfection

Both the equipment and the process outlines list chlorination (chlorine, hypochlorite, chloramine) , dechlorination (sodium bisulfite, sodium thiosulfate, sulfur dioxide) , and ultraviolet (UV) .

Why wastewater disinfection is different

Drinking water disinfection starts from a clean, filtered water with low demand. Wastewater disinfection starts from an effluent with residual organics, ammonia, and particles. Three consequences follow:

Ammonia converts free chlorine to chloramines almost immediately. In a non-nitrifying effluent, essentially all the chlorine residual is combined . Chloramines are far weaker disinfectants, so wastewater chlorine doses and contact times are much larger than drinking water equivalents.

Particles shield organisms. Bacteria embedded in floc survive; this is why effluent TSS and disinfection performance are directly linked.

The residual usually must be removed before discharge, because chlorine is acutely toxic to aquatic life. Typical permit limits for total residual chlorine are extremely low, and many Colorado permits express them in the tens of micrograms per liter.

Chlorination and contact

Dose is set to achieve the permit's bacteriological limit, commonly expressed as E. coli or fecal coliform as a geometric mean with a daily maximum.

Contact time in the chlorine contact chamber is typically 15 to 30 minutes at peak flow , and the chamber is baffled to force plug flow. A poorly baffled chamber short-circuits, and the measured detention time overstates the actual contact time. Dye or tracer testing determines the true T10.

CT applies here too , but with combined chlorine the required CT is roughly two orders of magnitude greater than with free chlorine.

Solids deposits accumulate in contact chambers and must be cleaned out; they exert demand and harbor organisms.

Dechlorination

Reducing agents destroy the residual before discharge:

Sulfur dioxide gas (SO2) — equipment is nearly identical to gas chlorination, including all-vacuum design, and the same room and safety requirements apply. SO2 is also heavier than air and is a severe respiratory irritant.

Sodium bisulfite and sodium metabisulfite — liquid, most common on small and mid-size plants.

Sodium thiosulfate — used mostly for sample dechlorination and small applications.

Stoichiometric demand is roughly 1 part sulfur dioxide per part of total residual chlorine , with about 10 percent excess in practice. Overdosing dechlorination consumes dissolved oxygen in the effluent, which can itself violate a permit's minimum DO requirement, so the operator trims to just enough. Mixing at the point of addition must be rapid, since the reaction is fast but requires contact.

Ultraviolet disinfection

UV inactivates organisms by damaging nucleic acids, forming thymine dimers that prevent replication. It adds no chemical, creates no disinfection byproducts, leaves no toxic residual to remove, and is effective against chlorine-resistant protozoa .

Operating variables:

Dose equals intensity multiplied by exposure time , expressed in millijoules per square centimeter. Typical wastewater design doses are 30 mJ/cm² and upward.

UV transmittance (UVT) at 254 nanometers is the single most important water quality parameter. A secondary effluent might have 55 to 65 percent UVT; a filtered effluent 65 to 75 percent. Falling UVT means the lamps must work harder for the same dose.

Lamp fouling. Quartz sleeves scale with hardness and iron and film with organics. Cleaning is mechanical (wipers), chemical, or both. Fouled sleeves are the most common cause of UV underperformance.

Lamp aging. Output declines over lamp life, typically 9,000 to 15,000 hours, and the control system must account for it.

Ballast and lamp failure alarms , and intensity sensors calibrated against a reference.

No residual. UV provides no lasting protection, so regrowth downstream is possible.

Photoreactivation. Some bacteria can repair UV damage when exposed to visible light, which is one reason design doses carry safety factors.

  • Chlorination + dechlorination Ultraviolet
  • Byproducts THMs, chlorinated organics None
  • Residual toxicity Requires dechlorination None
  • Protozoa Poor Excellent
  • Sensitive to TSS Yes Yes, strongly
  • Sensitive to ammonia Yes, forms chloramines No
  • Principal hazard Toxic gas or corrosive chemical Electrical, UV eye exposure
  • Principal maintenance Feed equipment, contact chamber cleaning Sleeve cleaning, lamp replacement

Loading diagram... Tertiary Filtration and Effluent Disinfection Train